– 17 –
1.SPECIFICATIONS
1-1. 208/230V model
Single unit (System with Non-ducted indoor units)
(*1) Rated conditions
Cooling : Indoor air temperature 80 °F DryBulb/67 °F WetBulb, Outdoor air temperature 95 °F DryBulb
Heating : Indoor air temperature 70 °F DryBulb, Outdoor air temperature 47 °F DryBulb/43 °F WetBulb
072,096 type :Equivalent piping length : 50ft , Hight difference : 0ft , 120 type :Equivalent piping length :
75ft , Hight difference : 0ft
Conditions based on Alternate Test Method guidelines provided by the U.S. Department of Energy(DOE)
(*2) Setting is necessary
(*3) The amount does not consider extra piping length. Refrigerant must be added on site in accordance with
the actual piping length.
(*4) High-pressure switch / High-pressure sensor / Low-pressure sensor / Fusible plug / PC board fuse /
Inverter overload protector
(*5) Select wire size based on the larger value of MCA.
MCA : Minimum Circuit Amps (minimum circuit Amps required for power supply design.)
(*6) MOCP : Maximum Overcurrent Protection(Amps)
Outdoor unit model name
MMY-
MAP0724FT9UL
MAP0964FT9UL
MAP1204FT9UL
(208 / 230) / 3 / 60
V/Ph/Hz
Center Voltage
Power Supply
96
72
120
Nominal capacity
(*1)
108
81
kBtu/h
kBtu/h
135
Nominal capacity
Cooling
Heating
(*1)
Soft Start
A
Starting Current
76.3
76.3
76.3
In
Height
Dimension
788
616
788
lbs
Packed
Total Weight
Silky shade (Munsell 1Y8.5/0.5)
Color
Hermetic twin rotary compressor
Type
Compressor
2.1 × 3
2.7 × 3
2.3 × 2
kW
Motor output
Propeller fan
Fan
1.0
1.0
1.0
kW
Motor output
Fan unit
7,060
7,620
5,120
cfm
Air volume
OFF:420 ON:540
High-pressure switch
psi
0.16
0.16
0.20
In WG
(*2)
Maximum external static pressure
Finned tube
Heat exchanger
R410A
Refrigerant
Name
25.4
25.4
25.4
lbs
(*3)
Charged refrigerant amount
751
583
751
lbs
Unit
50.5
41.8
50.5
In
Width
32.6
32.6
32.6
In
Depth
72.9
72.9
72.9
In
Height
47.6
39.0
47.6
In
Width
Packing
Unit
30.7
30.7
30.7
In
Depth
(*4)
Protective devices
50
34
52
Electrical
specifications
Unit
MCA
(*5)
A
60
40
60
MOCP
(*6)
A
Refrigerant piping
1/2"
1/2"
1/2"
Diameter
In
7/8"
7/8"
1-1/8"
Diameter
In
3/4"
3/4"
3/4"
Diameter
Liquid
Suction gas
Discharge gas
In
Flare
Type
Balance
3/8"
3/8"
3/8"
Diameter
In
16
12
Maximum number of indoor units
Indoor units
20
14 to 109
Cooling
Operation temperature range
– 4 to 60
Heating
FDB
FWB
62.0
Cooling
Sound pressure level
63.0
56.0
58.0
63.5
65.5
Heating
dB(A)
dB(A)
A value of the specifications list is numerical value
as of Jun., 2013 and may change it without a notice.
Summary of Contents for MMY-MAP0724FT6UL
Page 35: ...35 3 5 Parts Layout in Outdoor Unit 072 type Model MMY MAP0724FT...
Page 36: ...36 096 120 type Model MMY MAP0964FT MAP1204FT...
Page 37: ...37 3 6 Parts Layout in Inverter Assembly 208 230V model MMY MAP0724FT9UL...
Page 38: ...38 208 230V model MMY MAP0964FT9UL MMY MAP1204FT9UL...
Page 39: ...39 460V model MMY MAP0724FT6UL...
Page 40: ...40 460V model MMY MAP0964FT6UL MMY MAP1204FT6UL...
Page 41: ...41 3 7 Outdoor Inverter print circuit board 3 7 1 Interface P C board MCC 1606...
Page 42: ...42 3 7 2 Inverter P C board for compressor MCC 1595 A3 IPDU For 208 230V model MMY MAP 4FT9UL...
Page 43: ...43 3 7 3 Inverter P C board for compressor MCC 1596 A3 IPDU For 460V model MMY MAP 4FT6UL...
Page 44: ...44 3 7 4 Inverter P C board for fan motor MCC 1610 FAN IPDU...
Page 45: ...45 3 7 5 Noise Filter P C board MCC 1608 A B For 208 230V model MMY MAP 4FT9UL...
Page 46: ...46 3 7 6 Noise Filter P C board MCC 1625 A B C For 460V model MMY MAP 4FT6UL...
Page 195: ...195...
Page 197: ...197...
Page 257: ...257 15 EXPLODED DIAGRAM PARTS LIST Outdoor unit 15 1 MMY MAP0724FT9UL...
Page 258: ...258 15 1 MMY MAP0724FT9UL...
Page 262: ...262 15 1 Inverter Assembly MMY MAP0724FT9UL...
Page 264: ...264 15 2 MMY MAP0964FT9UL MMY MAP1204FT9UL...
Page 265: ...265 15 2 MMY MAP0964FT9UL MMY MAP1204FT9UL...
Page 269: ...269 15 2 Inverter Assembly MMY MAP0964FT9UL MMY MAP1204FT9UL...
Page 271: ...271 15 3 MMY MAP0724FT6UL...
Page 272: ...272 15 3 MMY MAP0724FT6UL...
Page 276: ...276 15 3 Inverter Assembly MMY MAP0724FT6UL...
Page 278: ...278 15 4 MMY MAP0964FT6UL MMY MAP1204FT6UL...
Page 279: ...279 15 4 MMY MAP0964FT6UL MMY MAP1204FT6UL...
Page 283: ...283 15 4 Inverter Assembly MMY MAP0964FT6UL MMY MAP1204FT6UL...