background image

10

TABLE 3 — REFRIGERATION SYSTEM SERVICE AND ANALYSIS CHART

(Refer to Figures 10-12 for wiring diagrams)

NOTE: All servicing must comply with state and federal regulations.

MALFUNCTION

POSSIBLE CAUSE

SOLUTION

Compressor Will Not Start  —
No Hum.

1. Line cord not plugged in.

1. Plug in the cord.

2. Power disconnect switch in OFF position. 

(

S

izes 1100L and 1300L only.)

2. Turn disconnect switch to ON position.

3. Fuse removed or blown.

3. Replace fuse.

4. Overload protector tripped.

4. Refer to electrical section.

5. Temperature control stuck in open

position.

5. Repair or replace temperature control.

6. Wiring improper or loose.

6. Check wiring against diagram.

Compressor Will Not Start — Hums 
but Trips on Overload Protector.

1. Low voltage to unit.

1. Determine reason and correct.

2. Relay failing to close.

2. Determine reason and correct, replace if 

necessary.

3.

S

tarting capacitor defective.

3. Determine reason and replace.

4. Improperly wired.

4. Check wiring against diagram.

Compressor Starts but Does Not 
Switch Off of Start Winding.

1. Low voltage to unit.

1. Determine reason and correct.

2. Relay failing to open.

2. Determine reason and correct; replace if 

necessary.

3. Run capacitor defective.

3. Determine reason and replace.

4. Compressor motor winding is open or 

shorted.

4. Determine cause, correct, and replace 

compressor.

Compressor Starts and Runs, but 
Short Cycles on Overload 
Protector.

1. Additional current passing through over-

load protector.

1. Check wiring diagram. Check for added 

fan motors, pumps, etc. connected to 
wrong side of protector.

2. Low voltage to unit.

2. Determine reason and correct.

3. Overload protector defective.

3. Check current, replace protector.

4. Run capacitor defective.

4. Determine reason and replace.

5. Excessive discharge pressure.

5. Check ventilation, restrictions in cooling 

medium, restrictions in refrigeration
system.

6. Compressor too hot — return gas hot.

6. Check refrigerant charge; fix leak if neces-

sary. Check airflow across condenser.

Unit Runs, but Short Cycles.

1. Overload protector.

1. Check wiring diagram for correct wiring.

2. Cold control.

2. Differential set too close.

3. Overcharge.

3. Reduce refrigerant charge.

4. Air in system.

4. Recover and recharge.

5. Undercharge.

5. Fix leak and recharge with refrigerant.

Unit Operates Long or 
Continuously.

1. Dirty condenser.

1. Clean condenser.

2.

S

hortage of refrigerant.

2. Fix leak, add charge, correct charge.

3. Temp control contacts stuck or frozen.

3. Replace Temp control.

4. Evaporator coil iced.

4. Defrost.

5. Restriction in refrigeration system.

5. Determine location and remove.

Start Capacitor Open, Shorted or 
Blown.

1. Relay contacts not opening properly.

1. Replace relay.

2. Low voltage to unit.

2. Determine reason and correct.

3. Improper relay.

3. Replace.

Run Capacitor Open, Shorted or 
Blown.

1. Improper capacitor.

1. Determine correct size and replace.

2. Excessively high line voltage (110% of 

rated max).

2. Determine reason and correct.

Relay Defective or Burned Out.

1. Incorrect relay.

1. Check and replace.

2. Line voltage too high or too low.

2. Determine reason and replace.

3. Relay being influenced by loose vibrating 

mounting.

3. Remount rigidly.

Space Temperature Too High.

1. Control setting too high.

1. Reset control.

2. Overcharged with refrigerant.

2. Recover refrigerant and recharge with 
     proper charge specified on dataplate.

3. Inadequate air circulation.

3. Improve air movement. 

Cooler Freezing Beverage.

1. Temperature control knob set too high.

1. Reset control.

Unit Noisy.

1. Loose parts or mountings.

1. Find and tighten.

2. Tubing rattle.

2. Reform to be free of contact.

3. Bent fan blade causing vibration. 

3. Replace blade.

4. Fan motor bearings worn.

4. Replace motor.

Summary of Contents for Miracool 1300L

Page 1: ...hout notice and without incurring obligations Printed in Mexico 6 06 79BC560002 01_C OWNER S MANUAL MIRACOOL GLASS DOOR MERCHANDISER 260L 1300L 300L 750L 1300L a79 13 a79 14 a79 15 Sales Office P O Bo...

Page 2: ...ll accessories and components including legs casters and shelves File a claim immediately with the shipping company if shipment is damaged or incomplete INSTALLATION LOCATE UNIT Refer to Figure 1 for...

Page 3: ...PER LEFT CORNER FLUORESCENT LAMP SIGNBOARD SIZES 750L 1100L AND 1300L ONLY WOOD SKID RETAINING SCREW IF USED HEX HEAD BOLT SCREW POWER CORD LEFT CONNECTOR LIGHTING CORD RIGHT CONNECTOR CARTRIDGE COMPA...

Page 4: ...ree Use caution to ensure that power and electrical cords do not get pinched between the cartridge and cabinet while removing cartridge TO LEVEL UNIT The door is equipped with gravity assisted cams an...

Page 5: ...retaining tab on the shelf clip captures the shelf as shown in Figure 6 7 Before loading the shelf ensure that the shelf is resting on each of 4 clips and that the clips are installed as shown in Figu...

Page 6: ...he lamp holder Refer to Figure 7 On units with safety shields the identification mark cannot be seen See Figure 8 Verify manually that the lamp has been rotated and locked into place Improperly instal...

Page 7: ...igher setting Adjust tempera ture control in small increments one position at a time NOTE For operation above 3 000 ft altitude ther mostat should be adjusted by a qualified service technician Before...

Page 8: ...r disconnecting the unit from the power supply remove the grille retaining screw located in the upper most part of the grille See Figure 1 2 Lift the grille up and away from the unit 3 Unplug the powe...

Page 9: ...itrogen Use care to purge air from the charging hose when breaking the vacuum CHARGING REFRIGERATION SYSTEM Refer to Table 2 for refrigerant type and amount of charge Since capillary tube systems have...

Page 10: ...lace 5 Excessive discharge pressure 5 Check ventilation restrictions in cooling medium restrictions in refrigeration system 6 Compressor too hot return gas hot 6 Check refrigerant charge fix leak if n...

Page 11: ...11 FIGURE 10 WIRING DIAGRAM SIZES 260L 300L a79 10...

Page 12: ...12 a79 12 FIGURE 11 WIRING DIAGRAM SIZE 750L...

Page 13: ...13 FIGURE 12 WIRING DIAGRAM SIZES 1100L 1300L a79 11...

Page 14: ...can be used to remove debris CABINET EXTERIOR Cabinets should be cleaned with a solution of mild soap and water or mild household cleaner Do not use caustic soap or abrasive cleaners since these might...

Page 15: ...Sponge with cloth then rinse with clear water and wipe dry Satisfactory for use on all finishes Stubborn Spots and Stains Caked on Splatter and other Light Discolorations Revere Ware Goddard s Twinkl...

Page 16: ...2006 Carrier Corporation Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Printed in Mexico 6 06 79BC560...

Reviews: