background image

IM-KSAIC03-03                                                                            Specifications subject to change without notice.                                                                                         

9

SCENARIO 5: SINGLE ZONE OUTDOOR 
UNIT 38MA*R WITH APPROVED 
RESIDENTIAL 24V FAN COILS FV4 

For the correct combinations, review the compatibility chart in “APPENDIX 

1 - COMPATIBILITY AND FAN SPEED WIRING” on page 15.

Installation Steps:

1. Remove TXV on the indoor unit.
2. Run the interconnecting piping from the outdoor unit to the indoor 

unit using the outdoor piping size and brazing to the mechanical 

fitting adapter that replaces the TXV (

part number 40MD000003

(available through RCD). If required, use the Bushing/Reducers 

listed in “APPENDIX 2 - PIPING ADAPTER BUSHINGS/

REDUCERS” on page 16.

3. Suction and liquid refrigerant lines must be properly insulated and

separated from each other to prevent condensation and energy loss.

4. Disconnect and remove the 24 volt transformer from the 24 Volt

Interface. Run the 2-conductor 18 AWG cable from R and C of the

indoor unit terminal board. Connect “R” to CN17 and “C” to CN16

on the 24 Volt Interface. Be sure to connect the primary (high

voltage) wire to the correct terminal (tap) on the FV4C transformer

(see “APPENDIX 3 - FV4C TRANSFORMER” on page 16).

5. Run the interconnecting wiring (14-3 AWG stranded power cable with

ground and 600 volt insulation rating) from the outdoor unit to the 24

Volt Interface using terminal connections L1, L2, S, and G. Connect

the ground wire (G) to the grounding connection in the case. Separate

power supplies are required for the outdoor unit and the indoor unit.

6. Run the 18 AWG thermostat wiring from the thermostat terminals

to the 24 Volt Interface and connect to R and C on CN15. Also

connect Y, W, and G on CN19. 

NOTE: 

Use an instrument size flat blade screwdriver 

with a maximum blade width of 1/8” for the screw 

terminals.

7. Run the 18 AWG thermostat wiring from “G1” on CN18 of the 24

Volt Interface to “G” on the indoor unit terminal board.

8. Install the T1 sensor (included with 24 Volt Interface) on CN5 of the 24 Volt

Interface and locate according to the 

NOTE

 addressing the indoor and

outdoor unit’s general installation in the next column.

9. Configure the dip switches on the 24V Interface for proper

operation:

For Heat Pump – all switches OFF except SW1-1 = ON
For Cooling Only – all switches OFF except SW1-1 = ON and 
SW2-1 = ON.

10. Configure the fan coil “Easy Select” Printed-Circuit Board 

following the instructions on the indoor unit’s installation manual.

11. Configure the thermostat to operate as a single stage cooling and 

heating (

DO NOT

 configure the thermostat as a Heat Pump).

NOTE: 

Follow the indoor and outdoor unit’s general installation instructions. 

The T1 (Return Air Temperature) sensor should be near or on the indoor unit 

on the air inlet side. The thermistor should be installed pointing down into the 

duct between 2.5 ft (0.75 m) and 4 ft (1.2 m) from the return side of the fan 

coil. Use a ½” drill and insert the thermistor no less than 6 in (15 cm) into the 

duct and seal air tight around the cable.

Auxiliary Heater on an FV4C:

Refer to and follow the steps of the FV4C Fan Coil Installation 

Instructions manual:

1. Wire W2 from the thermostat directly to the FV4 fan coil. See 

Figure 11 - FV4C Fan Coil Wiring with 1- Speed Heat Pump (page 

7) in the FV4C Installation Instructions manual. 

Do not remove the jumper on the fan coil between W1 and W2

2. Re-configure the wall thermostat to control the electric heat as a

2nd stage heat W2.

3. Use the FV4 standard molex 12-pin connector to connect the

Auxiliary Electric Heater element.

NOTE: 

When an auxiliary electric heater is connected and active by

W2 from the thermostat, the fan coil keeps blowing air regardless if

the outdoor unit is operating under 

DEFROST

 mode.

Fig. 13 — Wiring Diagram for FV4C Fan Coil Unit

When the outdoor unit is matched with a Residential fan coil and brazing 
the piping on the fan coil side is required, it is 

NECCESSARY

 to flow 

nitrogen into the system while brazing the line set since a filter drier is not 
recommended for use with these condensing units.

CAUTION

W2

Thermostat

70

G

G

G

FV4C
Indoor Unit

L1

L2

24V

D

H

R

W

1

W

2

Y

1

YY

1

G

O

C

Dash line 
means 
disconnect
transformer

Power supply from outdoor unit disconnect. 
Two wires are line voltage and the other is a 
ground wire.

Power supply from indoor unit 

BUS BAR

GROUND

Summary of Contents for KSAIC0301230

Page 1: ...y Understand these signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which may result in severe personal injury or de...

Page 2: ...refrigerant compressors Pressurized mixtures of air or gases containing oxygen can lead to an explosion WARNING INSTALLATION Entrust a licensed contractor to install the unit Installation by unskilled...

Page 3: ...ble 3 24V Interface Clearance Dimensions NOTE 24 in 610mm minimum for service access or use local code Fig 3 Clearances Clearances Unit Minimum Value In mm Sides 5 9 150 Front 24 610 Top and Bottom 3...

Page 4: ...er the screw SYSTEM CONFIGURATION NOTES The thermostat should be configured for use with a as a single stage Cooling and Heating DO NOT configure the thermostat as a Heat Pump The wireless remote cont...

Page 5: ...ndoor to the outdoor unit until the static pressure settings are complete refer to the Ducted unit installation manual On selected indoor units the Up Down Swing Louver functions as a control to turn...

Page 6: ...general installation instructions For Ducted units in order to initially setup the static pressure the 24V interface must be bridged Temporarily connect the communication wires S1 and S2 from the indo...

Page 7: ...it until the static pressure settings are complete see the Ducted unit installation manual When static pressure is adjusted reconnect L1 L2 S and G wires to the terminal blocks In the AUTO mode the sy...

Page 8: ...a single stage cooling and heating DO NOT configure the thermostat as Heat Pump NOTES Follow the indoor and outdoor unit s general installation instructions The T1 Return air temperature sensor should...

Page 9: ...oor unit s general installation in the next column 9 Configure the dip switches on the 24V Interface for proper operation For Heat Pump all switches OFF except SW1 1 ON For Cooling Only all switches O...

Page 10: ...he Teflon gasket on the brass tip of the Piping Adapter and insert into the aluminum distributor head Thread the piping adapter brass nut onto the distributor line and tighten finger tight 1 2 turn Fi...

Page 11: ...Using a Conventional Fan Coil The following steps should be taken when using this device with a conventional fan coil unit scenarios 4 and 5 1 Indoor coil metering device TXV Piston must be removed 2...

Page 12: ...il only available on scenarios 1 through 3 Table 11 DIP Switch 2 2 NOTE Applicable only to the Ductless Style Indoor Heat Pump units in the HEATING mode DIP Switch 3 1 On Ductless systems Dry is used...

Page 13: ...emperature sensor T5 malfunction Outdoor Service Manual F4 Outdoor unit EEPROM parameter error Outdoor Service Manual F5 Outdoor fan speed has been out of control Outdoor Service Manual F6 T2b sensor...

Page 14: ...opens and closes based on the system s alarm status This is normally a an open dry contact Work Output CN6 This contact is a dry contact that opens and closes based on the system s running or not run...

Page 15: ...minal System Size MBTUH Indoor Model Number Outdoor Model Number Recommended Maximum Indoor Fan Speed Tap Number FMA4 Vertical Fan Coil 208 230 1 KSAIC0301230 12 FMA4X1800AL 38MAQB12R 3 Tap 1 18 FMA4X...

Page 16: ...door coil s size No refrigerant addition is necessary for the FV4 any size All the outdoor units are shipped from the factory pre charged for 25ft of piping length See the outdoor unit s installation...

Reviews: