background image

IM-KSAIC03-03                                                                            Specifications subject to change without notice.                                                                                         

13

ERROR CODES

For ease of service, the 24V Interface is equipped with a diagnostic code display LED on the control board (ensure the 24V interface is installed

with the directional arrow pointing up to successfully read the error code). Refer to the indoor or outdoor unit’s service manual as listed in

Table 16 for a troubleshooting breakdown.

Table 16 — Error Codes

Display

Malfunction and Protection Indication

Service Manual Reference

E0

Indoor EEPROM error

Indoor Service Manual

E2

Cross-zero detection error

Indoor or Outdoor Service Manual

E3

Indoor fan speed malfunction

Indoor Service Manual

E4

Indoor room temperature sensor error

Indoor Service Manual

E5

Evaporator coil temperature sensor error

Indoor Service Manual

EC

Refrigerant leak detection system malfunction

Indoor or Outdoor Service Manual

F0

Current overload protection

Outdoor Service Manual

F1

Outdoor ambient temperature sensor (T4) malfunction

Outdoor Service Manual

F2

Condenser coil temperature sensor (T3) malfunction

Outdoor Service Manual

F3

Condenser coil temperature sensor (T5) malfunction

Outdoor Service Manual

F4

Outdoor unit EEPROM parameter error

Outdoor Service Manual

F5

Outdoor fan speed has been out of control

Outdoor Service Manual

F6

T2b sensor error

Indoor or Outdoor Service Manual

P0

Inverter module (IPM) malfunction

Outdoor Service Manual

P1

Over-voltage or under-voltage protection

Outdoor Service Manual

P2

Compressor top high temperature protection (OLP)

Outdoor Service Manual

P3

Low ambient temperature cut off in heating

Outdoor Service Manual

P4

Compressor drive malfunction

Outdoor Service Manual

--

Mode conflict (when connected to a multi-zone)

Indoor Service Manual

P6

Compressor low-pressure protection

Outdoor Service Manual

IN

24V Interface and indoor unit communication malfunction

Indoor Service Manual (E1)

0U

24V Interface (indoor unit) and outdoor unit communication malfunction

Indoor Service Manual (E1)

00

24V Interface successful power up and in standby

Operational Code

01

System operating in cooling mode

Operational Code

02

System operating in heating mode

Operational Code

03

System operating in fan mode

Operational Code

04

System operating in dehumidify mode (not a recommended application for 

FV4C units)

Operational Code

05

System operating with Auxiliary heater active (not a recommended application)

Operational Code

Summary of Contents for KSAIC0301230

Page 1: ...y Understand these signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which may result in severe personal injury or de...

Page 2: ...refrigerant compressors Pressurized mixtures of air or gases containing oxygen can lead to an explosion WARNING INSTALLATION Entrust a licensed contractor to install the unit Installation by unskilled...

Page 3: ...ble 3 24V Interface Clearance Dimensions NOTE 24 in 610mm minimum for service access or use local code Fig 3 Clearances Clearances Unit Minimum Value In mm Sides 5 9 150 Front 24 610 Top and Bottom 3...

Page 4: ...er the screw SYSTEM CONFIGURATION NOTES The thermostat should be configured for use with a as a single stage Cooling and Heating DO NOT configure the thermostat as a Heat Pump The wireless remote cont...

Page 5: ...ndoor to the outdoor unit until the static pressure settings are complete refer to the Ducted unit installation manual On selected indoor units the Up Down Swing Louver functions as a control to turn...

Page 6: ...general installation instructions For Ducted units in order to initially setup the static pressure the 24V interface must be bridged Temporarily connect the communication wires S1 and S2 from the indo...

Page 7: ...it until the static pressure settings are complete see the Ducted unit installation manual When static pressure is adjusted reconnect L1 L2 S and G wires to the terminal blocks In the AUTO mode the sy...

Page 8: ...a single stage cooling and heating DO NOT configure the thermostat as Heat Pump NOTES Follow the indoor and outdoor unit s general installation instructions The T1 Return air temperature sensor should...

Page 9: ...oor unit s general installation in the next column 9 Configure the dip switches on the 24V Interface for proper operation For Heat Pump all switches OFF except SW1 1 ON For Cooling Only all switches O...

Page 10: ...he Teflon gasket on the brass tip of the Piping Adapter and insert into the aluminum distributor head Thread the piping adapter brass nut onto the distributor line and tighten finger tight 1 2 turn Fi...

Page 11: ...Using a Conventional Fan Coil The following steps should be taken when using this device with a conventional fan coil unit scenarios 4 and 5 1 Indoor coil metering device TXV Piston must be removed 2...

Page 12: ...il only available on scenarios 1 through 3 Table 11 DIP Switch 2 2 NOTE Applicable only to the Ductless Style Indoor Heat Pump units in the HEATING mode DIP Switch 3 1 On Ductless systems Dry is used...

Page 13: ...emperature sensor T5 malfunction Outdoor Service Manual F4 Outdoor unit EEPROM parameter error Outdoor Service Manual F5 Outdoor fan speed has been out of control Outdoor Service Manual F6 T2b sensor...

Page 14: ...opens and closes based on the system s alarm status This is normally a an open dry contact Work Output CN6 This contact is a dry contact that opens and closes based on the system s running or not run...

Page 15: ...minal System Size MBTUH Indoor Model Number Outdoor Model Number Recommended Maximum Indoor Fan Speed Tap Number FMA4 Vertical Fan Coil 208 230 1 KSAIC0301230 12 FMA4X1800AL 38MAQB12R 3 Tap 1 18 FMA4X...

Page 16: ...door coil s size No refrigerant addition is necessary for the FV4 any size All the outdoor units are shipped from the factory pre charged for 25ft of piping length See the outdoor unit s installation...

Reviews: