PHYSICAL DATA

UNIT SIZE

024

030

036

042

048

060

NOMINAL CAPACITY ton

2

2--1/2

3

3--1/2

4

5

OPERATING WEIGHT lb

(kg)

363

(165)

368

(167)

447

(203)

469

(213)

475

(215)

526

(239)

COMPRESSOR

Two--Stage Scroll

REFRIGERANT: PURON (R--410A) Quantity lb

(kg)

10.1

(4.6)

11.3

(5.1)

9.5

(4.3)

13.8

(6.3)

15.3

(6.9)

15.8

(7.2)

REFRIGERANT METERING DEVICE

TXV

Size

2 Ton

3 Ton

3 Ton

4 Ton

4 Ton

5 Ton

Part Number

EA36DY129

EA36DY139

EA36DY139

EA36DY149

EA36DY149

EA36DY159

OUTDOOR COIL

Rows

Fins/in.

2

21

2

21

2

21

2

21

2

21

2

21

Face Area (sq. ft.)

13.6

15.3

17.5

19.4

19.4

23.3

OUTDOOR FAN

Nominal Cfm

2700

2700

2800

2800

3300

3300

Diameter (in.)

(mm)

22

559

22

559

22

559

22

559

22

559

22

559

Motor HP (RPM)

1/8 (825)

1/8 (825)

1/8 (825)

1/8 (825)

1/4 (1100)

1/3 (1110)

INDOOR COIL

Rows

Fins/in.

3

17

3

17

3

17

3

17

3

17

4

17

Face Area (sq. ft.)

3.7

3.7

4.7

4.7

5.7

5.7

INDOOR FAN
Nominal Airflow (Cfm)

Comfort

Variable based on Comfort Settings (see User Interface instructions for more information).

Efficiency

700

875

1050

1225

1400

1750

Max

800

1000

1200

1400

1600

2000

Size in.

(mm)

10x10

(254x254)

10x10

(254x254)

11x10

(279x254)

11x10

(279x254)

11x10

(279x254)

11x10

(279x254)

Motor HP (RPM)

1/2

1/2

3/4

3/4

3/4

1

HIGH--PRESSURE SWITCH (psig)

Cutout

670

±

10

Reset (Auto)

470

±

25

HIGH--PRESSURE SWITCH 2 (psig)

(Compressor Solenoid

)

Cutout

565

±

15

Reset (Auto)

455

±

15

LOSS--OF--CHARGE/LOW--PRESSURE SWITCH

(Liquid Line) (psig)
Cutout

23

±

5

Reset (Auto)

55

±

5

RETURN--AIR FILTERS

Throwaway

in.*

20x24x1

(508x610x25)

24x30x1

(610x762x25)

24x36x1

(610x914x25)

(mm)

*Recommended filter sizes for field---installed air filter grilles mounted on the wall or ceiling of the conditioned structure. Required filter sizes shown are based on

the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft (91.4 m) /minute for throwaway type

or 450 ft (137 m) /minute for high---capacity type. Air filter pressure drop for non---standard filters must not exceed 0.08 in. wc.

A--Weighted Sound Power Level (dBA)

MODEL

50XL

Sound Ratings

(dBA)

Typical Octive Band Spectrum (dBA without tone adjustment)

125

250

500

1000

2000

4000

8000

024

75

58.8

63.5

67.2

66.9

63.7

58.3

50.0

030

75

58.8

63.5

67.2

66.9

63.7

58.3

50.0

036

75

63.7

63.3

66.8

66.5

64.2

60.3

53.0

042

75

62.8

62.8

67.8

67.4

63.7

57.7

50.8

048

78

69.9

69.9

71.3

73.4

70.0

66.3

60.1

060

78

67.6

67.6

71.8

75.5

71.0

68.1

59.9

NOTE

: Tested in accordance with ARI Standard 270---95 (not listed in ARI).

50X

L

Summary of Contents for Infinity 50XL

Page 1: ...t ground level Durable dependable components Compressors have two stages of cooling and are designed for high efficiency Each compressor is hermetically sealed against contamination to help promote lo...

Page 2: ...avy duty phosphated zinc coated pre painted steel capable of withstanding 500 hrs of salt spray Interior surfaces of the evaporator and electric heater compartments are insulated with cleanable semi r...

Page 3: ...1 4 15 5 030 2 1 2 1000 700 28 600 21 400 11 6 15 0 036 3 1200 850 34 600 24 400 12 15 0 042 3 1 2 1400 975 40 500 29 000 11 6 15 0 048 4 1600 1100 46 000 33 400 11 15 0 060 5 1750 1200 57 000 40 500...

Page 4: ...0 279x254 Motor HP RPM 1 2 1 2 3 4 3 4 3 4 1 HIGH PRESSURE SWITCH psig Cutout 670 10 Reset Auto 470 25 HIGH PRESSURE SWITCH 2 psig Compressor Solenoid Cutout 565 15 Reset Auto 455 15 LOSS OF CHARGE LO...

Page 5: ...les 024 048 size units to be fitted to 14 in 356 mm round ductwork Infinity User Interface coupled with the system s variable speed indoor blower delivers Carrier s patented IdealHumidity technology t...

Page 6: ...FILTER RACK EVAPORATOR COIL TOP FILTER RACK BEND FLANGE AT 90 SCREW TO DIVIDER WITH 1 IN SCREW BOTTOM FILTER RACK MANUAL OUTSIDE AIR DAMPER DAMPER BLADE MANUAL OUTSIDE AIR HOOD REPLACEMENT PANEL 50XL...

Page 7: ...7 A06596 Fig 2 50XL024 030 Unit Dimensions 50XL...

Page 8: ...8 A06597 Fig 3 50XL036 060 Unit Dimensions 50XL...

Page 9: ...t D F Return opening B X C Insulate d deck pan Short Support CTyp G E F G D E A05308 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM E IN MM F IN MM G IN MM 024 030 CPRFCURB006A00 8 203 1...

Page 10: ...quired cooling capacity Enter Net Cooling Capacities table at condenser entering temperature of 95 F 35 C The 036 unit at 1200 cfm and 67 F 19 4 C ewb entering wet bulb will provide a total capacity o...

Page 11: ...3 18 01 14 14 2 82 72 22 2 27 77 13 43 1 70 26 37 12 96 1 88 24 90 12 48 2 09 23 35 11 95 2 31 21 66 11 41 2 57 20 60 11 05 2 57 50XL024 Low Cool EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES _F...

Page 12: ...47 16 98 3 51 72 22 2 35 18 16 96 2 18 33 29 16 32 2 40 31 27 15 65 2 65 29 11 14 94 2 92 26 76 14 18 3 22 24 19 13 36 3 55 50XL030 Low Cool EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES _F _C 7...

Page 13: ...47 21 64 3 90 72 22 2 42 99 19 31 2 41 40 85 18 61 2 66 38 57 17 87 2 93 36 13 17 09 3 24 33 48 16 25 3 58 30 56 15 35 3 96 50XL036 Low Cool EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES _F _C 7...

Page 14: ...38 26 96 4 45 72 22 2 50 09 26 04 2 96 47 23 25 02 3 23 44 13 23 92 3 51 45 09 24 26 3 58 41 83 23 12 3 93 32 98 20 13 4 51 50XL042 Low Cool EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES _F _C 7...

Page 15: ...36 29 43 4 97 72 22 2 56 36 27 17 3 60 53 67 26 25 3 91 50 80 25 29 4 25 47 69 24 26 4 62 44 30 23 15 5 03 42 55 22 59 5 06 50XL048 Low Cool EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES _F _C 75...

Page 16: ...00 34 88 6 94 72 22 2 68 41 33 69 4 48 65 01 32 46 4 91 61 35 31 14 5 37 57 37 29 72 5 88 52 97 28 19 6 44 48 09 26 53 7 04 50XL060 Low Cool EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES _F _C 75...

Page 17: ...d heat 2 Direct interpolation is permissible Do not extrapolate 3 The following formulas may be used Example 15 0 kW at 240v heater on 208v 15 0 75 mult factor 11 25 capacity at 208v Sensible capacity...

Page 18: ...wc 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 024 COMFORT Default Variable based on Comfort Settings EFFICIENCY 700 700 700 700 700 700 700 700 700 700 MAX 800 800 800 800 800 800 800 800 800 800 030 COM...

Page 19: ...IR FLEXIBLE DUCT CEILING CONCENTRIC DIFFUSER BOX FIELD SUPPLIED SUPPLY AIR FLEXIBLE DUCT ROOF MOUNTING CURB C00023 USER INTERFACE DISCONNECT PER NEC FROM POWER SOURCE RETURN AIR TOP COVER FROM GAS LIN...

Page 20: ...45 7 5 10 0 36 1 41 7 50 5 57 5 60 60 11 3 15 0 54 2 62 5 73 1 83 5 80 90 036 208 230 1 60 187 253 16 7 82 0 0 9 6 8 28 5 28 5 45 45 3 8 5 0 18 1 20 8 31 1 34 5 45 45 5 4 7 2 26 0 30 0 41 0 46 0 45 50...

Page 21: ...21 TYPICAL WIRING SCHEMATIC 230 1 60 A08201 50XL...

Page 22: ...e User Interface After second stage is satisfied the unit returns to low stage operation until first stage is satisfied or until second stage is required again When both first stage and second stage c...

Page 23: ...insulation shall be used in the entire indoor air cavity seciton 5 Unit shall have a field supplied condensate trap C Fans 1 The indoor fan shall be variable speed motor and control as shown on equipm...

Page 24: ...k Kit Shall provide filter mounting for downflow and horizontal applications 7 Square To Round Duct Transitions Shall have the ability to convert the supply and return open ings from rectangular to ro...

Reviews: