GUIDE SPECIFICATIONS

SINGLE--PACKAGED ELECTRIC COOLING UNITS

CONSTANT VOLUME APPLICATION

HVAC GUIDE SPECIFICATIONS
SIZE RANGE:

2 TO 5 TONS, NOMINAL COOLING

MODEL NUMBER: 50XL

PART I -- GENERAL

SYSTEM DESCRIPTION

Outdoor rooftop or ground mounted electric cooling unit utiliz-

ing a 2 stage hermetic compressor for cooling duty and optional

electric heating. Unit shall discharge supply air vertically or hori-
zontally as shown on contract drawings. Outdoor fan/coil section

shall have a draw--thru design with vertical discharge for mini-
mum sound levels.

QUALITY ASSURANCE

A. Unit shall be rated in accordance with ARI Standards

210/240, and 270.

B. Unit shall be designed in accordance with UL Standard

1995.

C. Unit shall be manufactured in a facility registered to ISO

9001 manufacturing quality standard

D. Unit shall be UL listed and c--UL certified as a total

package for safety requirements.

E. Roof curb shall be designed to conform to NRCA

Standards.

F. Insulation and adhesives shall meet NFPA 90A

requirements for flame spread and smoke generation.

G. Cabinet insulation shall meet ASHRAE Standard 62P.

DELIVERY, STORAGE, AND HANDLING

Unit shall be stored and handled per manufacturer’s recommen-

dations.

PART 2-- PRODUCTS

EQUIPMENT

A. General:

Factory--assembled, single--piece, cooling unit. Contained with-
in the unit enclosure shall be all factory wiring, piping, controls,

refrigerant charge (R--410A), and special features required prior

to field start--up.

B. Unit Cabinet:

1. Unit cabinet shall be constructed of phosphated, zinc--coated,

prepainted steel capable of withstanding 500 hrs of salt spray.

2. Normal service shall be through a single removable cabinet

panel.

3. The unit shall be constructed on a rust proof unit base that has

an externally trapped, integrated sloped drain pan.

4. Indoor fan compartment top surface shall be insulated with a

minimum 1/2--in. (13 mm)

thick, flexible fiberglass

insulation, coated on the air side and retained by adhesive and

mechanical means. The indoor wall sections will be insulated
with a foil--faced insulation capable of being wiped clean.

Aluminum foil--faced fiberglass insulation shall be used in the
entire indoor air cavity seciton.

5. Unit shall have a field--supplied condensate trap.

C. Fans:

1. The indoor fan shall be variable--speed motor and control, as

shown on equipment drawings.

2. Fan wheel shall be made from steel, be double--inlet type. It

shall have forward--curved blades with a corrosion--resistant

finish and shall be dynamically balanced.

3. Outdoor fan shall be of the direct--driven propeller type with

aluminum blades, riveted to corrosion--resistant steel spiders.
It shall be dynamically balanced and discharge air vertically.

D. Compressor:

1. Fully hermetic 2 stage compressors with factory--installed

vibration isolation.

2. Two stage scroll compressors shall be standard on all units.

E. Coils:

1. Indoor and outdoor coils shall have aluminum plate fins

mechanically bonded to seamless copper tubes with all joints
brazed.

2. Tube sheet openings shall be bellied to prevent tube wear.

F. Refrigerant Metering Device:

Refrigerant metering device shall be of the TXV type.

G. Filters:

Filter section shall consist of field--installed, throw--away,

1--in. thick fiberglass filters of commercially available sizes.

H. Controls and Safeties:

1. Unit controls shall be complete with self--contained low

voltage control circuit.

2. Units shall incorporate an internal compressor protector that

provides reset capability.

3. Unit shall provide high and low/loss--of--charge pressure

safety protection.

I. Operating Characteristics:

1. Unit shall be capable of starting and running at 125

°

F

(51.6

°

C) ambient outdoor temperature, exceeding maximum

load criteria of ARI Standard 210.

2. Compressor with standard controls shall be capable of

operation down to 55

°

F (12.7

°

C) ambient outdoor

temperature.

3. Unit shall be capable of low--ambient cooling (below 55

_

F

(12.7

°

C) ambient outdoor temperature) with low--ambient

cooling enabled on the UI.

J. Electrical Requirements:

All unit power wiring shall enter unit cabinet at a single location.

K. Motors:

1. Compressor motors shall be of the refrigerant--cooled type

with line--break thermal and current overload protection.

2. All fan motors shall have permanently lubricated bearings and

inherent automatic reset thermal overload protection.

3. Outdoor fan motor shall be totally enclosed.

L. Grille

1. Louvered Grille:

Louvered grille shall be standard on all units.

50X

L

Summary of Contents for Infinity 50XL

Page 1: ...t ground level Durable dependable components Compressors have two stages of cooling and are designed for high efficiency Each compressor is hermetically sealed against contamination to help promote lo...

Page 2: ...avy duty phosphated zinc coated pre painted steel capable of withstanding 500 hrs of salt spray Interior surfaces of the evaporator and electric heater compartments are insulated with cleanable semi r...

Page 3: ...1 4 15 5 030 2 1 2 1000 700 28 600 21 400 11 6 15 0 036 3 1200 850 34 600 24 400 12 15 0 042 3 1 2 1400 975 40 500 29 000 11 6 15 0 048 4 1600 1100 46 000 33 400 11 15 0 060 5 1750 1200 57 000 40 500...

Page 4: ...0 279x254 Motor HP RPM 1 2 1 2 3 4 3 4 3 4 1 HIGH PRESSURE SWITCH psig Cutout 670 10 Reset Auto 470 25 HIGH PRESSURE SWITCH 2 psig Compressor Solenoid Cutout 565 15 Reset Auto 455 15 LOSS OF CHARGE LO...

Page 5: ...les 024 048 size units to be fitted to 14 in 356 mm round ductwork Infinity User Interface coupled with the system s variable speed indoor blower delivers Carrier s patented IdealHumidity technology t...

Page 6: ...FILTER RACK EVAPORATOR COIL TOP FILTER RACK BEND FLANGE AT 90 SCREW TO DIVIDER WITH 1 IN SCREW BOTTOM FILTER RACK MANUAL OUTSIDE AIR DAMPER DAMPER BLADE MANUAL OUTSIDE AIR HOOD REPLACEMENT PANEL 50XL...

Page 7: ...7 A06596 Fig 2 50XL024 030 Unit Dimensions 50XL...

Page 8: ...8 A06597 Fig 3 50XL036 060 Unit Dimensions 50XL...

Page 9: ...t D F Return opening B X C Insulate d deck pan Short Support CTyp G E F G D E A05308 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM E IN MM F IN MM G IN MM 024 030 CPRFCURB006A00 8 203 1...

Page 10: ...quired cooling capacity Enter Net Cooling Capacities table at condenser entering temperature of 95 F 35 C The 036 unit at 1200 cfm and 67 F 19 4 C ewb entering wet bulb will provide a total capacity o...

Page 11: ...3 18 01 14 14 2 82 72 22 2 27 77 13 43 1 70 26 37 12 96 1 88 24 90 12 48 2 09 23 35 11 95 2 31 21 66 11 41 2 57 20 60 11 05 2 57 50XL024 Low Cool EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES _F...

Page 12: ...47 16 98 3 51 72 22 2 35 18 16 96 2 18 33 29 16 32 2 40 31 27 15 65 2 65 29 11 14 94 2 92 26 76 14 18 3 22 24 19 13 36 3 55 50XL030 Low Cool EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES _F _C 7...

Page 13: ...47 21 64 3 90 72 22 2 42 99 19 31 2 41 40 85 18 61 2 66 38 57 17 87 2 93 36 13 17 09 3 24 33 48 16 25 3 58 30 56 15 35 3 96 50XL036 Low Cool EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES _F _C 7...

Page 14: ...38 26 96 4 45 72 22 2 50 09 26 04 2 96 47 23 25 02 3 23 44 13 23 92 3 51 45 09 24 26 3 58 41 83 23 12 3 93 32 98 20 13 4 51 50XL042 Low Cool EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES _F _C 7...

Page 15: ...36 29 43 4 97 72 22 2 56 36 27 17 3 60 53 67 26 25 3 91 50 80 25 29 4 25 47 69 24 26 4 62 44 30 23 15 5 03 42 55 22 59 5 06 50XL048 Low Cool EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES _F _C 75...

Page 16: ...00 34 88 6 94 72 22 2 68 41 33 69 4 48 65 01 32 46 4 91 61 35 31 14 5 37 57 37 29 72 5 88 52 97 28 19 6 44 48 09 26 53 7 04 50XL060 Low Cool EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES _F _C 75...

Page 17: ...d heat 2 Direct interpolation is permissible Do not extrapolate 3 The following formulas may be used Example 15 0 kW at 240v heater on 208v 15 0 75 mult factor 11 25 capacity at 208v Sensible capacity...

Page 18: ...wc 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 024 COMFORT Default Variable based on Comfort Settings EFFICIENCY 700 700 700 700 700 700 700 700 700 700 MAX 800 800 800 800 800 800 800 800 800 800 030 COM...

Page 19: ...IR FLEXIBLE DUCT CEILING CONCENTRIC DIFFUSER BOX FIELD SUPPLIED SUPPLY AIR FLEXIBLE DUCT ROOF MOUNTING CURB C00023 USER INTERFACE DISCONNECT PER NEC FROM POWER SOURCE RETURN AIR TOP COVER FROM GAS LIN...

Page 20: ...45 7 5 10 0 36 1 41 7 50 5 57 5 60 60 11 3 15 0 54 2 62 5 73 1 83 5 80 90 036 208 230 1 60 187 253 16 7 82 0 0 9 6 8 28 5 28 5 45 45 3 8 5 0 18 1 20 8 31 1 34 5 45 45 5 4 7 2 26 0 30 0 41 0 46 0 45 50...

Page 21: ...21 TYPICAL WIRING SCHEMATIC 230 1 60 A08201 50XL...

Page 22: ...e User Interface After second stage is satisfied the unit returns to low stage operation until first stage is satisfied or until second stage is required again When both first stage and second stage c...

Page 23: ...insulation shall be used in the entire indoor air cavity seciton 5 Unit shall have a field supplied condensate trap C Fans 1 The indoor fan shall be variable speed motor and control as shown on equipm...

Page 24: ...k Kit Shall provide filter mounting for downflow and horizontal applications 7 Square To Round Duct Transitions Shall have the ability to convert the supply and return open ings from rectangular to ro...