10

50XL RIGGING WEIGHTS

-in. (914 mm)

DETAIL 

A

 

A06298

A06296

CABINET

MODEL

RIGGING WT

lb

kg

Small

50XL--024

382

173

50XL--030

387

176

Large

50XL--036

469

213

50XL--042

491

223

50XL--048

497

225

50XL--060

548

249

NOTE: See dimensional drawing for corner weight distribution. Corner

weights shown on drawing are based on unit---only weights and do not

include packaging.

Fig. 4 -- Suggested Rigging

SELECTION PROCEDURE

Determine cooling and heating requirements at design

conditions:

Given:
REQUIRED COOLING CAPACITY (TC)

34,500 BTUH

. . . . . .

SENSIBLE HEAT CAPACITY (SHC)

24,000 BTUH

. . . . . . . . .

REQUIRED HEATING CAPACITY (SHC)

15,000 BTUH

. . . . .

CONDENSER ENTERING AIR TEMPERATURE 95

°

F (35

°

C)

INDOOR--AIR TEMPERATURE

80

°

F (26.6

°

C) EDB, 67

°

F

. . .

(19.4

°

C) EWB

EVAPORATOR AIR QUANTITY

1200 CFM

. . . . . . . . . . . . . . .

ELECTRICAL CHARACTERISTICS

230--1--60

. . . . . . . . . . . . .

Select unit based on required cooling capacity

Enter Net Cooling Capacities table at condenser entering

temperature of 95

°

F (35

°

C). The 036 unit at 1200 cfm and 67

°

F

(19.4

°

C) ewb (entering wet bulb) will provide a total capacity of

34,600 Btuh and a SHC of 24,220 Btuh. Calculate SHC correction,

if required, using Note 4 under Cooling Capacities tables.

Select electric heat

The required heating capacity is 15,000 Btuh.
Determine additional electric heat capacity in kW.

15,000 Btuh

3414 Btuh/kW

= 4.4kW of heat required

Enter the Electric Heater table on page 5 for 208/230v,

single--phase unit. The 5--kW heater at 240v most closely satisfies
the heating required. To calculate kW at 230v, multiply the heater

kW by multiplication factor 0.92 found in the Multiplication
Factors table on page 17.
5 kW x 0.92 = 4.6 kW
4.6 kW x 3414 Btuh/kW = 15,704 Btuh (Total unit heating
capacity)

Select unit that corresponds to power source available

The Electrical Data table shows that the unit is designed to operate

at 208/230--1--60.

50X

L

Summary of Contents for Infinity 50XL

Page 1: ...t ground level Durable dependable components Compressors have two stages of cooling and are designed for high efficiency Each compressor is hermetically sealed against contamination to help promote lo...

Page 2: ...avy duty phosphated zinc coated pre painted steel capable of withstanding 500 hrs of salt spray Interior surfaces of the evaporator and electric heater compartments are insulated with cleanable semi r...

Page 3: ...1 4 15 5 030 2 1 2 1000 700 28 600 21 400 11 6 15 0 036 3 1200 850 34 600 24 400 12 15 0 042 3 1 2 1400 975 40 500 29 000 11 6 15 0 048 4 1600 1100 46 000 33 400 11 15 0 060 5 1750 1200 57 000 40 500...

Page 4: ...0 279x254 Motor HP RPM 1 2 1 2 3 4 3 4 3 4 1 HIGH PRESSURE SWITCH psig Cutout 670 10 Reset Auto 470 25 HIGH PRESSURE SWITCH 2 psig Compressor Solenoid Cutout 565 15 Reset Auto 455 15 LOSS OF CHARGE LO...

Page 5: ...les 024 048 size units to be fitted to 14 in 356 mm round ductwork Infinity User Interface coupled with the system s variable speed indoor blower delivers Carrier s patented IdealHumidity technology t...

Page 6: ...FILTER RACK EVAPORATOR COIL TOP FILTER RACK BEND FLANGE AT 90 SCREW TO DIVIDER WITH 1 IN SCREW BOTTOM FILTER RACK MANUAL OUTSIDE AIR DAMPER DAMPER BLADE MANUAL OUTSIDE AIR HOOD REPLACEMENT PANEL 50XL...

Page 7: ...7 A06596 Fig 2 50XL024 030 Unit Dimensions 50XL...

Page 8: ...8 A06597 Fig 3 50XL036 060 Unit Dimensions 50XL...

Page 9: ...t D F Return opening B X C Insulate d deck pan Short Support CTyp G E F G D E A05308 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM E IN MM F IN MM G IN MM 024 030 CPRFCURB006A00 8 203 1...

Page 10: ...quired cooling capacity Enter Net Cooling Capacities table at condenser entering temperature of 95 F 35 C The 036 unit at 1200 cfm and 67 F 19 4 C ewb entering wet bulb will provide a total capacity o...

Page 11: ...3 18 01 14 14 2 82 72 22 2 27 77 13 43 1 70 26 37 12 96 1 88 24 90 12 48 2 09 23 35 11 95 2 31 21 66 11 41 2 57 20 60 11 05 2 57 50XL024 Low Cool EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES _F...

Page 12: ...47 16 98 3 51 72 22 2 35 18 16 96 2 18 33 29 16 32 2 40 31 27 15 65 2 65 29 11 14 94 2 92 26 76 14 18 3 22 24 19 13 36 3 55 50XL030 Low Cool EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES _F _C 7...

Page 13: ...47 21 64 3 90 72 22 2 42 99 19 31 2 41 40 85 18 61 2 66 38 57 17 87 2 93 36 13 17 09 3 24 33 48 16 25 3 58 30 56 15 35 3 96 50XL036 Low Cool EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES _F _C 7...

Page 14: ...38 26 96 4 45 72 22 2 50 09 26 04 2 96 47 23 25 02 3 23 44 13 23 92 3 51 45 09 24 26 3 58 41 83 23 12 3 93 32 98 20 13 4 51 50XL042 Low Cool EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES _F _C 7...

Page 15: ...36 29 43 4 97 72 22 2 56 36 27 17 3 60 53 67 26 25 3 91 50 80 25 29 4 25 47 69 24 26 4 62 44 30 23 15 5 03 42 55 22 59 5 06 50XL048 Low Cool EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES _F _C 75...

Page 16: ...00 34 88 6 94 72 22 2 68 41 33 69 4 48 65 01 32 46 4 91 61 35 31 14 5 37 57 37 29 72 5 88 52 97 28 19 6 44 48 09 26 53 7 04 50XL060 Low Cool EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES _F _C 75...

Page 17: ...d heat 2 Direct interpolation is permissible Do not extrapolate 3 The following formulas may be used Example 15 0 kW at 240v heater on 208v 15 0 75 mult factor 11 25 capacity at 208v Sensible capacity...

Page 18: ...wc 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 024 COMFORT Default Variable based on Comfort Settings EFFICIENCY 700 700 700 700 700 700 700 700 700 700 MAX 800 800 800 800 800 800 800 800 800 800 030 COM...

Page 19: ...IR FLEXIBLE DUCT CEILING CONCENTRIC DIFFUSER BOX FIELD SUPPLIED SUPPLY AIR FLEXIBLE DUCT ROOF MOUNTING CURB C00023 USER INTERFACE DISCONNECT PER NEC FROM POWER SOURCE RETURN AIR TOP COVER FROM GAS LIN...

Page 20: ...45 7 5 10 0 36 1 41 7 50 5 57 5 60 60 11 3 15 0 54 2 62 5 73 1 83 5 80 90 036 208 230 1 60 187 253 16 7 82 0 0 9 6 8 28 5 28 5 45 45 3 8 5 0 18 1 20 8 31 1 34 5 45 45 5 4 7 2 26 0 30 0 41 0 46 0 45 50...

Page 21: ...21 TYPICAL WIRING SCHEMATIC 230 1 60 A08201 50XL...

Page 22: ...e User Interface After second stage is satisfied the unit returns to low stage operation until first stage is satisfied or until second stage is required again When both first stage and second stage c...

Page 23: ...insulation shall be used in the entire indoor air cavity seciton 5 Unit shall have a field supplied condensate trap C Fans 1 The indoor fan shall be variable speed motor and control as shown on equipm...

Page 24: ...k Kit Shall provide filter mounting for downflow and horizontal applications 7 Square To Round Duct Transitions Shall have the ability to convert the supply and return open ings from rectangular to ro...

Reviews: