Carrier Infinity 25VNA Installation Instructions Manual Download Page 4

4

Step 6 — In Long--Line Applications, Install

Liquid--Line Solenoid Valve (LSV)

For refrigerant piping arrangements with equivalent lengths of
greater than 80 ft. (24.38 m) and/or when elevation difference

between indoor and outdoor unit is greater than

20 ft. (

6.10 m),

follow the piping configuration and liquid line solenoid valve
(LSV) accessory requirements from the Residential Piping and

Long--line guideline. CCH, start gear and piston changes do not
apply. If required by Long--Line Guideline, install LSV kit, part

no. KHALS0401LLS, specifically designed for Puron

refrigerant

heat pumps. LSV should be installed within 2 ft. (0.61 m) of
outdoor unit with flow arrow pointing toward outdoor unit.
Make the necessary electrical connections as shown on Fig. 21 and
by following the Installation Instructions included with accessory

kit.

IMPORTANT

: Flow arrow must point toward outdoor unit.

Green

Yellow

White

     ABCD
     Connection (optional)

Red

     LLS

LS

User Interface

Optional Remote

Room Sensor

                      Furnace or
                      Fan Coil

Variable
Speed
HP

A

B

C

D

C

S2

A

B

C

D

A

B

C

D

S1

A11107

Fig. 4 -- Liquid Line Solenoid Electrical Connection

(Required for long line applications)

Step 7 — Make Piping Connections

!

WARNING

PERSONAL INJURY AND UNIT DAMAGE

HAZARD

Failure to follow this warning could result in personal injury or

death.
Relieve pressure and recover all refrigerant before system

repair or final unit disposal. Use all service ports and open all

flow--control devices, including solenoid valves.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Do not leave system open to atmosphere any longer than

minimum required for installation. POE oil in compressor is

extremely susceptible to moisture absorption. Always keep

ends of tubing sealed during installation.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
If ANY refrigerant tubing is buried, provide a 6 in. (152.4

mm) vertical rise at service valve. Refrigerant tubing lengths

up to 36 in. (914.4 mm) may be buried without further

special consideration. Do not bury lines longer than 36 in.

(914.4 mm).

Outdoor units may be connected to indoor section using accessory
tubing package or field--supplied refrigerant grade tubing of correct

size and condition. For tubing requirements beyond 80 ft. (24.38

m), substantial capacity and performance losses can occur. Follow
the pipe sizing recommendations in the 25VNA Product data to

manage these losses.
Refer to Table 1 for field tubing diameters. Refer to Table 2 for

accessory requirements.

Summary of Contents for Infinity 25VNA

Page 1: ...factory authorized kits or accessories when modifying this product Refer to the individual instructions packaged with the kits or accessories when installing Follow all safety codes Wear safety glass...

Page 2: ...tructure and unit to absorb vi bration 6 When passing refrigerant tubes through the wall seal open ing with RTV or other pliable silicon based caulk see Fig 1 7 Avoid direct tubing contact with water...

Page 3: ...tion to building Consult local codes governing rooftop applications Roof mounted units exposed to winds above 5 mph may require wind baffles Consult the Service Manual Residential Split System Air Con...

Page 4: ...INJURY AND UNIT DAMAGE HAZARD Failure to follow this warning could result in personal injury or death Relieve pressure and recover all refrigerant before system repair or final unit disposal Use all...

Page 5: ...LICATIONS Over 80 ft 24 38 m REQUIRED FOR SEA COAST APPLICATIONS Within 2 miles 3 22 km Installations with Radio Frequency Interference Concerns in the Range of 2 to 30 MHZ Crankcase Heater Standard S...

Page 6: ...urface is avoided S Insulating the muffler with Armaflext tape is recommended EXTERIOR WALL VAPOR LINE MUFFLER TO DWELLING A11543 Fig 5 Muffler Installation A05227 Fig 6 Liquid Line Filter Drier Refri...

Page 7: ...Fig 8 Line Power Connections Connect Control Wiring Connect to Infinity connections Only two wires AB to Infinity capable indoor unit furnace or fan coil is required Typical 4 wire ABCD may be connect...

Page 8: ...arge re moval may be necessary 3 Fully open liquid and vapor service valves A11104 Fig 9 Required Charge Adjustment Calculated in UI 4 Set User Interface to operate cooling in CHARGING mode Charging m...

Page 9: ...may not begin to cycle until about 40_F 4 4_C OAT The outdoor unit fan will cycle on and off based on outdoor coil temperature outdoor air temperature and suction pressure measurements to keep the com...

Page 10: ...ize before declaring a properly charged system The use of a commercial charge metering device restrictor such as Imperial liquid low side charger model 535 C or Watsco ChargeFaster model CH200 is reco...

Page 11: ...o be isolated in indoor coil and lineset Set desired time period Default time peri od for the procedure is 120 minutes 4 Select Start on UI to begin the pumpdown process Unit will begin running in sel...

Page 12: ...ard controls the operation of the contactor TROUBLESHOOTING Systems Communication Failure If communication with the Infinity control is lost with the User Interface UI the control will flash the appro...

Page 13: ...proper operating conditions The comparison is S In cooling if the outdoor air sensor indicates 10_F 5 6_C warmer than the coil sensor or the outdoor air sensor indicates 20_F 11_C cooler than the coil...

Page 14: ...N ECM Fan Motor If verification of proper operation is required for the ECM motor used in this unit follow these steps 1 Verify that the 230v input to the transformer is present 2 Verify that the cont...

Page 15: ...urnace or Fan Coil A12055 Fig 18 Infinity Furnace or Fan Coil Wiring with Communicating Variable Speed HP D C B A VS HP OAT G Y O W C HUM Furnace or Fan Coil C B A UT IL C LS O Y R G Y O W C R Convent...

Page 16: ...PL5 PL3 HPS Utility Interface A11544 Fig 20 Variable Speed Control Board with optional Utility Relay CB MODEL PL8 FORCED DEFROST J2 1 BRN RED SEC1 SEC2 PWM2 PWM1 INVERTER PL1 PL2 RVS CC PL11 PL4 PL6 O...

Page 17: ...p Out of Range Event 59 15 Compressor No Start 62 15 Compressor Sump Heater Active 68 NA Inverter Compressor Internal Fault 69 5 Compressor Motor Temp Out of Range Event 71 5 Suction Over Temp Event 7...

Page 18: ...ow side with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron refrigerant as with other HFCs is only com...

Reviews: