background image

18

FINAL CHECKS

IMPORTANT: IMPORTANT

: Before leaving job, be

sure to do the following:

1. Ensure that all wiring is routed away from tubing

and sheet metal edges to prevent rub--through or
wire pinching.

2. Ensure that all wiring and tubing is secure in unit

before adding panels and covers. Securely fasten
all panels and covers.

3. Tighten service valve stem caps to 1/12--turn past

finger tight.

4. Leave Users Manual with owner. Explain system

operation and periodic maintenance requirements
outlined in manual.

5. Fill out Dealer Installation Checklist and place in

customer file.

CARE AND MAINTENANCE

For continuing high performance and to minimize
possible equipment failure, periodic maintenance must be

performed on this equipment.
Frequency of maintenance may vary depending upon

geographic areas, such as coastal applications. See

Owner’s Manual for information.

PURON

R

(R--410A) REFRIGERANT QUICK REFERENCE GUIDE

S

Puron refrigerant operates at 50--70 percent higher pressures than R--22. Be sure that servicing equipment and replacement

components are designed to operate with Puron refrigerant.

S

Puron refrigerant cylinders are rose colored.

S

Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.

S

Puron refrigerant systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose

when charging into suction line with compressor operating.

S

Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low--side retard.

S

Use hoses with 700 psig service pressure rating.

S

Leak detectors should be designed to detect HFC refrigerant.

S

Puron refrigerant, as with other HFCs, is only compatible with POE oils.

S

Vacuum pumps will not remove moisture from oil.

S

Do not use liquid--line filter driers with rated working pressures less than 600 psig.

S

Do not leave Puron refrigerant suction line filter driers in line longer than 72 hours.

S

Do not install a suction--line filter drier in liquid--line.

S

POE oils absorb moisture rapidly. Do not expose oil to atmosphere.

S

POE oils may cause damage to certain plastics and roofing materials.

S

Wrap all filter driers and service valves with wet cloth when brazing.

S

A factory--approved liquid--line filter drier is required on every unit.

S

Do NOT use an R--22 TXV.

S

If indoor unit is equipped with an R--22 TXV or piston metering device, it must be changed to a hard--shutoff Puron refrigerant

TXV.

S

Never open system to atmosphere while it is under a vacuum.

S

When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter

driers. Evacuate to 500 microns prior to recharging.

S

Do not vent Puron refrigerant into the atmosphere.

S

Do not use capillary tube coils.

S

Observe all

warnings

,

cautions

, and

bold

text.

S

All indoor coils must be installed with a hard--shutoff Puron refrigerant TXV metering device.

Copyright 2014 Carrier Corp.

S

7310 W. Morris St.

S

Indianapolis, IN 46231

Edition Date: 04/14

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Catalog No: 25VNA---5SI

Replaces: 25VNA--- 4SI

Summary of Contents for Infinity 25VNA

Page 1: ...factory authorized kits or accessories when modifying this product Refer to the individual instructions packaged with the kits or accessories when installing Follow all safety codes Wear safety glass...

Page 2: ...tructure and unit to absorb vi bration 6 When passing refrigerant tubes through the wall seal open ing with RTV or other pliable silicon based caulk see Fig 1 7 Avoid direct tubing contact with water...

Page 3: ...tion to building Consult local codes governing rooftop applications Roof mounted units exposed to winds above 5 mph may require wind baffles Consult the Service Manual Residential Split System Air Con...

Page 4: ...INJURY AND UNIT DAMAGE HAZARD Failure to follow this warning could result in personal injury or death Relieve pressure and recover all refrigerant before system repair or final unit disposal Use all...

Page 5: ...LICATIONS Over 80 ft 24 38 m REQUIRED FOR SEA COAST APPLICATIONS Within 2 miles 3 22 km Installations with Radio Frequency Interference Concerns in the Range of 2 to 30 MHZ Crankcase Heater Standard S...

Page 6: ...urface is avoided S Insulating the muffler with Armaflext tape is recommended EXTERIOR WALL VAPOR LINE MUFFLER TO DWELLING A11543 Fig 5 Muffler Installation A05227 Fig 6 Liquid Line Filter Drier Refri...

Page 7: ...Fig 8 Line Power Connections Connect Control Wiring Connect to Infinity connections Only two wires AB to Infinity capable indoor unit furnace or fan coil is required Typical 4 wire ABCD may be connect...

Page 8: ...arge re moval may be necessary 3 Fully open liquid and vapor service valves A11104 Fig 9 Required Charge Adjustment Calculated in UI 4 Set User Interface to operate cooling in CHARGING mode Charging m...

Page 9: ...may not begin to cycle until about 40_F 4 4_C OAT The outdoor unit fan will cycle on and off based on outdoor coil temperature outdoor air temperature and suction pressure measurements to keep the com...

Page 10: ...ize before declaring a properly charged system The use of a commercial charge metering device restrictor such as Imperial liquid low side charger model 535 C or Watsco ChargeFaster model CH200 is reco...

Page 11: ...o be isolated in indoor coil and lineset Set desired time period Default time peri od for the procedure is 120 minutes 4 Select Start on UI to begin the pumpdown process Unit will begin running in sel...

Page 12: ...ard controls the operation of the contactor TROUBLESHOOTING Systems Communication Failure If communication with the Infinity control is lost with the User Interface UI the control will flash the appro...

Page 13: ...proper operating conditions The comparison is S In cooling if the outdoor air sensor indicates 10_F 5 6_C warmer than the coil sensor or the outdoor air sensor indicates 20_F 11_C cooler than the coil...

Page 14: ...N ECM Fan Motor If verification of proper operation is required for the ECM motor used in this unit follow these steps 1 Verify that the 230v input to the transformer is present 2 Verify that the cont...

Page 15: ...urnace or Fan Coil A12055 Fig 18 Infinity Furnace or Fan Coil Wiring with Communicating Variable Speed HP D C B A VS HP OAT G Y O W C HUM Furnace or Fan Coil C B A UT IL C LS O Y R G Y O W C R Convent...

Page 16: ...PL5 PL3 HPS Utility Interface A11544 Fig 20 Variable Speed Control Board with optional Utility Relay CB MODEL PL8 FORCED DEFROST J2 1 BRN RED SEC1 SEC2 PWM2 PWM1 INVERTER PL1 PL2 RVS CC PL11 PL4 PL6 O...

Page 17: ...p Out of Range Event 59 15 Compressor No Start 62 15 Compressor Sump Heater Active 68 NA Inverter Compressor Internal Fault 69 5 Compressor Motor Temp Out of Range Event 71 5 Suction Over Temp Event 7...

Page 18: ...ow side with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron refrigerant as with other HFCs is only com...

Reviews: