Carrier Infinity 25VNA Installation Instructions Manual Download Page 10

10

The control board accumulates compressor run time. As the
accumulated run time approaches the selected defrost interval time,

the control board monitors the coil temperature sensor for a defrost
demand. If a defrost demand exists, a defrost cycle will be initiated

at the end of the selected time interval. A defrost demand exists

when the coil temperature is at or below 32

_

F (0

_

C) for 4 minutes

during the interval. If the coil temperature does not reach 32

_

F

(0

_

C) within the interval, the interval timer will be reset and start

over.

S

Upon initial power up the first defrost interval is defaulted to 30
minutes. Remaining intervals are at selected times.

S

Defrost is only allowed to occur below 50

_

F (10

_

C) outdoor

ambient temperature.

The defrost cycle is terminated as described below.

S

When OAT is > 35

F (+1.67

C), defrost terminates if outdoor

coil temperature > 50

F (+10

C).

S

When OAT

35

F (+1.7

C), defrost will terminate if OCT is

>45

F (+4.4

C).

S

Or 10 minutes has passed.

At the defrost termination, the outdoor fan output (ODF) will turn

on 15 seconds before the reversing valve switching.

NOTE

: Compressor speed during defrost varies based on outdoor

conditions.

Step 13 — Check Charge
Charge in CHARGING mode

Factory charge amount and desired subcooling are shown in the

user interface (UI). To properly check or adjust charge, conditions
must be favorable for subcooling charging in cooling mode.

Favorable conditions exist when the outdoor temperature is
between 65

_

F and 100

_

F (18

_

C and 38

_

C), and the indoor

temperature is between 70

_

F and 80

_

F (21

_

C and 27

_

C). If the

temperatures are outside of these ranges, weigh--in charge only. If
confirmation is needed return and check subcooling when the

temperatures are within the desired range.

Charging Procedure

: Unit is factory charged for 15ft (4.57 m) of

lineset and for smaller rated indoor coil combinations. If any

refrigerant charge adjustment is required based on the indoor coil
combination you select and the line set length you input, the UI

will calculate and display the target subcooling and the amount of
additional charge to be added. Therefore UI is your source of

information for charging the system correctly. Refrigerant charge

adjustment amount for adding or removing 0.6 oz/ft (17.74 g/m) of
3/8 liquid line above or below 15ft (4.57 m) respectively, and an

additional amount of refrigerant charge adjustment (2 lbs) for a
large ID coil if required, is calculated and displayed by the UI.
Perform a final charge check only when in cooling and OD is
between 65

F (18

C) and 100

F (38

C).

NOTE

: UI indicates acceptable conditions if outside of this range.

Do not charge if outside 65

F (18

C) and 100

F (38

C) outdoor

temperature.
If the range is acceptable, go the CHARGING screen in the user

interface (UI). At cooling conditions, set the user interface (UI) to
check the charge in cooling mode. Allow system to operate in

cooling mode for the stabilization period as indicated in the user
interface (UI). Once conditions are indicated as favorable and

stable by the user interface (UI), check the system charge by

subcooling method. Compare the subcooling taken at the liquid
service valve to the subcooling target (LiqLin SC TGT) listed on

the charging screen. Add refrigerant if the subcooling is low and
remove charge if subcooling is high. Tolerance should be

2

F.

If any adjustment is necessary, add or remove the charge slowly

(no greater than 0.5 lb per minute) and allow system to operate for
15 minutes to stabilize before declaring a properly charged system.

The use of a commercial charge metering device (restrictor) such as

Imperial

liquid low side charger model 535--C or

Watsco

ChargeFaster model CH200 is recommended when adding
refrigerant to an operating system. This prevents potential damage

of liquid slugging of the compressor and allows the subcooling to

stabilize quicker.
If the indoor temperature is above 80

_

F (26.67

_

C), and the

outdoor temperature is in the favorable range, adjust system charge
by weight based on line length and allow the indoor temperature to

drop to 80

_

F (26.67

_

C) before attempting to check system charge

by subcooling method as described above.
If the indoor temperature is below 70

_

F (21.11

_

C), or the outdoor

temperature is not in the favorable range, adjust charge for line set
length above or below 15ft (4.57 m) only. Charge level should then

be appropriate for the system to achieve rated capacity. The charge

level could then be checked at another time when the both indoor
and outdoor temperatures are in a more favorable range. This

ensures maximum efficiency and reliability.

Heating Check Chart Procedure

In heating mode, the required charging method is by weigh--in. On

new installation or complete recharge, refer to the REQUIRED

CHARGE CALCULATION screen in the user interface (UI) to
obtain the required charge adjustment and/or total charge required.

Use the UI and Heating Check Charts (Fig. 12 and 13) to check
system operation during HEATING mode. The indoor conditions

must be between 60

F (15.6

_

C) and 80

F (26.7

_

C) to check the

charge. The outdoor coil must be dry and ice/frost free. Do not
check for pressure agreement if the outdoor has rain, mist or snow

present.
Use the Defrost CHECKOUT mode to remove ice or frost from

coil, if present, prior to checking the heating pressures.

To use the Heating Check Chart:

1. Place the system in EFFICIENCY mode by selecting

Service--> Setup--> Furnace or Fan Coil--> AC/HP Airflow,
for proper ID airflow during verification of system
pressures against those shown on the Heating Check Chart.

2. Go to Service--> Checkout--> Heating. Choose 25 minutes

and Choose Speed % consistent with 3200 compressor

RPM for 2T or 3T, and 3450 compressor RPM for 4T or
5T. The Speed % selection can be an iterative process that
may require more than a single try at starting to arrive at the

RPM required, allowing a tolerance of 50 RPM.

3. Upon starting the heating checkout mode at the proper com-

pressor RPM, keep it running frost free for 20 minutes be-
fore checking the pressures against the Heating Check Chart
label.

These charts indicate whether a correct relationship exists between
system operating pressure and air temperature entering indoor and

outdoor units. If pressure and temperature do not match on chart,

system refrigerant charge may not be correct. DO NOT USE
CHART TO ADJUST REFRIGERANT CHARGE. IF CHARGE

IS IN DOUBT, REMOVE CHARGE AND WEIGH--IN
CORRECT CALCULATED REFRIGERANT CHARGE.

NOTE

: High pressure is at vapor service valve. Add 12 psig if

high pressure is taken from liquid service valve.

NOTE:

When charging is necessary during heating season, charge

must be weighed in accordance with unit rating plate,

0.6 oz./ft

(

17.74 g/m). of 3/8--in. liquid--line above or below 15 ft (4.57

m)., respectively.

NOTE:

In heating mode, check refrigerant pressures only when

user interface is engaged in Checkout-->Heating mode. Upon
completing the Charge verification in Checkout mode, place the
system back in Comfort mode ID airflow by choosing:
Service-->Setup-->Furnace or Fan Coil-->AC/HP Airflow, and
choosing Comfort. This is required, unless the system was
previously deliberately placed in Efficiency or other modes.

Summary of Contents for Infinity 25VNA

Page 1: ...factory authorized kits or accessories when modifying this product Refer to the individual instructions packaged with the kits or accessories when installing Follow all safety codes Wear safety glass...

Page 2: ...tructure and unit to absorb vi bration 6 When passing refrigerant tubes through the wall seal open ing with RTV or other pliable silicon based caulk see Fig 1 7 Avoid direct tubing contact with water...

Page 3: ...tion to building Consult local codes governing rooftop applications Roof mounted units exposed to winds above 5 mph may require wind baffles Consult the Service Manual Residential Split System Air Con...

Page 4: ...INJURY AND UNIT DAMAGE HAZARD Failure to follow this warning could result in personal injury or death Relieve pressure and recover all refrigerant before system repair or final unit disposal Use all...

Page 5: ...LICATIONS Over 80 ft 24 38 m REQUIRED FOR SEA COAST APPLICATIONS Within 2 miles 3 22 km Installations with Radio Frequency Interference Concerns in the Range of 2 to 30 MHZ Crankcase Heater Standard S...

Page 6: ...urface is avoided S Insulating the muffler with Armaflext tape is recommended EXTERIOR WALL VAPOR LINE MUFFLER TO DWELLING A11543 Fig 5 Muffler Installation A05227 Fig 6 Liquid Line Filter Drier Refri...

Page 7: ...Fig 8 Line Power Connections Connect Control Wiring Connect to Infinity connections Only two wires AB to Infinity capable indoor unit furnace or fan coil is required Typical 4 wire ABCD may be connect...

Page 8: ...arge re moval may be necessary 3 Fully open liquid and vapor service valves A11104 Fig 9 Required Charge Adjustment Calculated in UI 4 Set User Interface to operate cooling in CHARGING mode Charging m...

Page 9: ...may not begin to cycle until about 40_F 4 4_C OAT The outdoor unit fan will cycle on and off based on outdoor coil temperature outdoor air temperature and suction pressure measurements to keep the com...

Page 10: ...ize before declaring a properly charged system The use of a commercial charge metering device restrictor such as Imperial liquid low side charger model 535 C or Watsco ChargeFaster model CH200 is reco...

Page 11: ...o be isolated in indoor coil and lineset Set desired time period Default time peri od for the procedure is 120 minutes 4 Select Start on UI to begin the pumpdown process Unit will begin running in sel...

Page 12: ...ard controls the operation of the contactor TROUBLESHOOTING Systems Communication Failure If communication with the Infinity control is lost with the User Interface UI the control will flash the appro...

Page 13: ...proper operating conditions The comparison is S In cooling if the outdoor air sensor indicates 10_F 5 6_C warmer than the coil sensor or the outdoor air sensor indicates 20_F 11_C cooler than the coil...

Page 14: ...N ECM Fan Motor If verification of proper operation is required for the ECM motor used in this unit follow these steps 1 Verify that the 230v input to the transformer is present 2 Verify that the cont...

Page 15: ...urnace or Fan Coil A12055 Fig 18 Infinity Furnace or Fan Coil Wiring with Communicating Variable Speed HP D C B A VS HP OAT G Y O W C HUM Furnace or Fan Coil C B A UT IL C LS O Y R G Y O W C R Convent...

Page 16: ...PL5 PL3 HPS Utility Interface A11544 Fig 20 Variable Speed Control Board with optional Utility Relay CB MODEL PL8 FORCED DEFROST J2 1 BRN RED SEC1 SEC2 PWM2 PWM1 INVERTER PL1 PL2 RVS CC PL11 PL4 PL6 O...

Page 17: ...p Out of Range Event 59 15 Compressor No Start 62 15 Compressor Sump Heater Active 68 NA Inverter Compressor Internal Fault 69 5 Compressor Motor Temp Out of Range Event 71 5 Suction Over Temp Event 7...

Page 18: ...ow side with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron refrigerant as with other HFCs is only com...

Reviews: