Fig. 8—Service Label

A99233

SERVICE

G

R

Y

W

Com

HUM

TES

T

LE
D

LED CODE

STATUS

24V

11

12

13

14
21

22

23

24

31

33

34

*

9

8

6

5

32

1

4

7

COMPONENT TEST

NO PREVIOUS CODE - Stored status codes are erased when power
(115VAC or 24VAC) to control is interrupted or 48 hours after each fault is cleared.
BLOWER ON AFTER POWER UP  (115VAC or 24 VAC)  -  Blower runs for 90
seconds, if unit is powered up during a call for heat (R-W closed).
LIMIT OR FLAME ROLL-OUT SWITCH LOCKOUT - Control will auto reset after
three hours. Reset switch or replace fuse link.  Refer to #33.
IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34.
GAS HEATING LOCKOUT - Control will NOT auto reset.
Check for: - Mis-wired gas valve          -Defective control (Valve relay)
ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is
de-energized. Inducer will run until fault is cleared.
Check for:    - Leaky gas valve              - Stuck-open gas valve
PRESSURE SWITCH DID NOT OPEN - Check for:
- Obstructed pressure tubing.           - Pressure switch stuck closed.
SECONDARY VOLTAGE FUSE IS OPEN
Check for:      - Short circuit in secondary voltage (24VAC) wiring.
PRESSURE, DRAFT SAFEGUARD, AUX-LIMIT SWITCH (when used*) OR BLOCKED
VENT SWITCH
 (when used) DID NOT CLOSE OR REOPENED
(DOWNFLOW ONLY*)
  If open longer than five minutes, inducer shuts off for 15
minutes before retry.      Check for:

- Proper vent sizing

- Low inducer voltage (115VAC)

- Defective inducer motor

- Defective Blower motor or capacitor

- Restricted vent

- Defective pressure switch

- Excessive wind

- Inadequate combustion air supply
- Disconnected or obstructed pressure tubing
If it opens after trial for ignition period, blower will come on for 90 second
recycle delay.
LIMIT OR FLAME ROLL-OUT SWITCH IS OPEN - If open longer than three
minutes, code changes to #13. Flame roll-out switch requires manual reset.
Check for:           - Defective blower motor or capacitor.
- Dirty filter or restricted duct system.
- Loose blower wheel.
- Defective switch or connections.
- Inadequate combustion air supply (Flame Roll-out Switch or fuse link open).
- Open Flame Roll-out Switch, or fuse link. Manual reset or replace.
IGNITION PROVING FAILURE - Control will try three more times before
lockout #14 occurs. If flame signal lost after trial for ignition period, blower
will come on for 90 second recycle delay. Check for:
- Oxide buildup on flame sensor (clean with fine steel wool).
- Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal).
- Gas valve defective or gas valve turned off.
- Defective Hot Surface Ignitor

- Manual valve shut-off.

- Low inlet gas pressure.

- Control ground continuity

- Green wire MUST be connected to furnace sheet metal.
- Inadequate flame carryover or rough ignition.
- Flame sensor must be ungrounded.

To initiate the component test sequence, shut OFF the room thermostat or
disconnect the "R" thermostat lead. Briefly short the TEST terminal to the "Com
24V" terminal. Status LED will flash code and then turn ON the inducer motor.
The inducer motor will run for the entire component test. The hot surface ignitor,
blower motor-heat speed, and blower motor-cool speed will be turned ON for
10-15 seconds each. Gas Valve and Humidifier will not be turned on.

If status code recall is needed, do not remove power or blower door. Briefly remove and then
reconnect one main limit wire to display stored status code.

CONTINUOUS OFF - Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and

SEC-2.

CONTINUOUS ON - Control has 24VAC power.
RAPID FLASHING -  Line voltage (115VAC) polarity reversed. If twinned, refer

to twinning kit instructions.

EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST
DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY
THE NUMBER OF LONG FLASHES.

320615-102 REV. K (LIT)

8

Summary of Contents for INDUCED COMBUSTION 58YAV

Page 1: ...hen you see this symbol on the furnace and in instructions or manuals be alert to the potential for personal injury Understand these signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION ...

Page 2: ...nsult your local dealer as to proper frequency of maintenance and availability of a maintenance contract Never store anything on near or in contact with furnace such as 1 Spray or aerosol cans rags brooms dust mops vacuum cleaners or other cleaning tools 2 Soap powders bleaches waxes or other cleaning com pounds plastic or plastic containers gasoline kerosene cigarette lighter fluid dry cleaning f...

Page 3: ...d not be dropped or bent as balance will be affected 8 If a greasy residue is present on blower wheel remove wheel from the blower housing and wash it with an appropriate degreaser To remove wheel a Mark blower wheel location on shaft before disassembly to ensure proper reassembly b Loosen setscrew holding blower wheel on motor shaft NOTE Mark blower mounting arms motor and blower housing so motor...

Page 4: ...itor See Fig 3 for correct ignitor location 9 Using field provided small wire brush steel spring cable reversible electric drill and vacuum cleaner clean cells as follows a Assemble wire brush and steel spring cable 1 Use 48 in of 1 4 in diameter high grade steel spring cable commonly known as drain clean out or Roto Rootert cable 2 Use 1 4 in diameter wire brush commonly known as 25 caliber rifle...

Page 5: ... must be maintained properly Refer to Fig 5 for field wiring information and to Fig 6 for furnace wiring information NOTE If the polarity is not correct the STATUS LED on the control will flash rapidly and prevent the furnace from heating The control system also requires an earth ground for proper operation of the control and flame sensing electrode The 24 v circuit contains an automotive type 3 a...

Page 6: ...C CONDUCTOR ON PCB FIELD WIRING TERMINAL FIELD GROUND EQUIPMENT GROUND FIELD SPLICE PLUG RECEPTACLE L1 L2 L1 BLWR HI LO TO 115VAC FIELD DISCONNECT NOTE 4 EQUIPMENT GROUND SPARE 2 HEAT SPARE 1 COOL NOTE 7 COM HSIR EAC 1 START OL COM HI MED HI MED LO LO BLWM SCHEMATIC DIAGRAM NATURAL GAS PROPANE EAC 2 1 1 HSI 2 PL5 2 PL2 3 PL3 PR2 115VAC PR1 TRAN 24VAC 1 2 IDR TEST TWIN FU1 NOTE 6 CAP L2 PL1 8 FSE 9...

Page 7: ...s and retrieval request is ignored 2 When above items have been completed the following will occur a LED flashes a status code 4 times Record this status code for further troubleshooting b Inducer motor starts and continues to run the entire component test c Hot surface ignitor is energized for 15 sec then de energized d Main blower operates at heating speed for 10 sec then turns off e Main blower...

Page 8: ...lame roll out switch requires manual reset Check for Defective blower motor or capacitor Dirty filter or restricted duct system Loose blower wheel Defective switch or connections Inadequate combustion air supply Flame Roll out Switch or fuse link open Open Flame Roll out Switch or fuse link Manual reset or replace IGNITION PROVING FAILURE Control will try three more times before lockout 14 occurs ...

Page 9: ...idly and test request will be ignored e Component Test will function as described in item 2 above f Check LED status g If LED status indicates proper operation RELEASE BLOWER ACCESS DOOR SWITCH replace blower access door and replace control access door WIRING DIAGRAMS Refer to Fig 5 6 and 7 for the 58YAV furnace wiring diagrams TROUBLESHOOTING Refer to service label See Fig 8 The Troubleshooting G...

Page 10: ...ill start and run for the entire component test The HSI blower motor heat speed and blower motor cool speed will run for 10 15 sec each Determine status code The status code is a 2 digit number with the first digit determined by the number of short flashes and the second digit by the number of long flashes Was there a previous fault code other than No 11 Does control respond to W Y or G 24 vac the...

Page 11: ...ed while gas valve was de energized Inducer will run until fault is cleared Check for Stuck open gas valve solenoid or leak Defective control center 23 PRESSURE SWITCH WILL NOT OPEN Check for Disconnected or obstructed pressure tubing Defective pressure switch 24 LOW VOLTAGE FUSE IS OPEN Check for Short in low voltage wiring including thermostat leads shorting to ductwork or furnace cabinet Discon...