Carrier INDUCED COMBUSTION 58YAV Service And Maintenance Instructions Download Page 4

14. If furnace is operating properly, REMOVE TAPE TO RE-

LEASE BLOWER ACCESS DOOR SWITCH, replace
blower access door.

Step 3—Cleaning Heat Exchanger

The following steps should be performed by a qualified service
technician:

NOTE:

If the heat exchangers get a heavy accumulation of soot

and carbon, they should be replaced rather than trying to clean
them thoroughly due to their intricate design. A build-up of soot
and carbon indicates that a problem exists which needs to be
corrected, such as improper adjustment of manifold pressure,
insufficient or poor quality combustion air, incorrect size, or
damaged manifold orifice(s), improper gas, or a restricted heat
exchanger. Action must be taken to correct the problem.
If it becomes necessary to clean heat exchanger because of light
dust or corrosion proceed as follows:

1. Turn gas and electrical power to furnace to OFF.

2. Remove control access door.

3. Disconnect vent connector from furnace flue collar.

4. Remove 2 screws that secure relief box. (See Fig. 2.)

5. Disconnect wires to the following components. Mark wires to

aid in reconnection of:

a. Blocked vent safeguard switch.

b. Inducer motor.

c. Pressure switch.

d. Limit overtemperature switch(es).

e. Gas valve.

f. Hot surface ignitor.

g. Flame-sensing electrode

h. Flame rollout switch(es), if applicable.

6. Remove complete inducer assembly and relief box from

furnace.

7. Remove 8 screws that secure flue collector box to center

panel. Be careful not to damage collector box.

8. Remove burner assembly and cell inlet plates. IMPORTANT:

Replace screws in center panel before cleaning.

NOTE:

Be very careful when removing burner assembly to avoid

breaking ignitor. See Fig. 3 for correct ignitor location.

9. Using field-provided small wire brush, steel spring cable,

reversible electric drill, and vacuum cleaner, clean cells as
follows:

a. Assemble wire brush and steel spring cable.

(1.) Use 48 in. of 1/4-in. diameter high-grade steel spring

cable (commonly known as drain clean-out or Roto-
Rooter

t

cable).

(2.) Use 1/4-in. diameter wire brush (commonly known as

25-caliber rifle cleaning brush).

NOTE:

The materials needed in items (1.) and (2.) can usually be

purchased at local hardware stores.

(3.) Insert twisted wire end of brush into end of spring

cable, and crimp tight with crimping tool or strike with
ball-peen hammer. TIGHTNESS IS VERY IMPOR-
TANT.

(4.) Remove metal screw fitting from wire brush to allow

insertion into cable.

b. Clean each heat exchanger cell.

(1.) Attach variable-speed, reversible drill to end of spring

cable (end opposite brush).

(2.) Insert brush end of cable into upper opening of cell

and slowly rotate with drill. DO NOT force cable.
Gradually insert at least 36 in. of cable into 2 upper
passes of cell. (See Fig. 4.)

(3.) Work cable in and out of cell 3 or 4 times to obtain

sufficient cleaning. DO NOT pull cable with great
force. Reverse drill and gradually work cable out.

(4.) Insert brush end of cable in lower opening of cell, and

proceed to clean 2 lower passes of cell in same manner
as 2 upper passes.

(5.) Repeat foregoing procedures until each cell in furnace

has been cleaned.

(6.) Using vacuum cleaner, remove residue from each cell.

(7.) Using vacuum cleaner with soft brush attachment,

clean burner assembly.

(8.) Reinstall cell inlet plates and burner assembly. Care

must be exercised to center burners in cell openings.

Fig. 3—Position of Ignitor to Burner

A93347

BURNER

IGNITOR

11 32

"

7 8

"

C

L

C

L

IGNITOR
ASSEMBLY

CELL
PANEL

BURNER

13 32

"

HOT
SURFACE
IGNITOR
ASSEMBLY

Fig. 4–Cleaning Heat Exchanger Cell

A91252

4

Summary of Contents for INDUCED COMBUSTION 58YAV

Page 1: ...hen you see this symbol on the furnace and in instructions or manuals be alert to the potential for personal injury Understand these signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION ...

Page 2: ...nsult your local dealer as to proper frequency of maintenance and availability of a maintenance contract Never store anything on near or in contact with furnace such as 1 Spray or aerosol cans rags brooms dust mops vacuum cleaners or other cleaning tools 2 Soap powders bleaches waxes or other cleaning com pounds plastic or plastic containers gasoline kerosene cigarette lighter fluid dry cleaning f...

Page 3: ...d not be dropped or bent as balance will be affected 8 If a greasy residue is present on blower wheel remove wheel from the blower housing and wash it with an appropriate degreaser To remove wheel a Mark blower wheel location on shaft before disassembly to ensure proper reassembly b Loosen setscrew holding blower wheel on motor shaft NOTE Mark blower mounting arms motor and blower housing so motor...

Page 4: ...itor See Fig 3 for correct ignitor location 9 Using field provided small wire brush steel spring cable reversible electric drill and vacuum cleaner clean cells as follows a Assemble wire brush and steel spring cable 1 Use 48 in of 1 4 in diameter high grade steel spring cable commonly known as drain clean out or Roto Rootert cable 2 Use 1 4 in diameter wire brush commonly known as 25 caliber rifle...

Page 5: ... must be maintained properly Refer to Fig 5 for field wiring information and to Fig 6 for furnace wiring information NOTE If the polarity is not correct the STATUS LED on the control will flash rapidly and prevent the furnace from heating The control system also requires an earth ground for proper operation of the control and flame sensing electrode The 24 v circuit contains an automotive type 3 a...

Page 6: ...C CONDUCTOR ON PCB FIELD WIRING TERMINAL FIELD GROUND EQUIPMENT GROUND FIELD SPLICE PLUG RECEPTACLE L1 L2 L1 BLWR HI LO TO 115VAC FIELD DISCONNECT NOTE 4 EQUIPMENT GROUND SPARE 2 HEAT SPARE 1 COOL NOTE 7 COM HSIR EAC 1 START OL COM HI MED HI MED LO LO BLWM SCHEMATIC DIAGRAM NATURAL GAS PROPANE EAC 2 1 1 HSI 2 PL5 2 PL2 3 PL3 PR2 115VAC PR1 TRAN 24VAC 1 2 IDR TEST TWIN FU1 NOTE 6 CAP L2 PL1 8 FSE 9...

Page 7: ...s and retrieval request is ignored 2 When above items have been completed the following will occur a LED flashes a status code 4 times Record this status code for further troubleshooting b Inducer motor starts and continues to run the entire component test c Hot surface ignitor is energized for 15 sec then de energized d Main blower operates at heating speed for 10 sec then turns off e Main blower...

Page 8: ...lame roll out switch requires manual reset Check for Defective blower motor or capacitor Dirty filter or restricted duct system Loose blower wheel Defective switch or connections Inadequate combustion air supply Flame Roll out Switch or fuse link open Open Flame Roll out Switch or fuse link Manual reset or replace IGNITION PROVING FAILURE Control will try three more times before lockout 14 occurs ...

Page 9: ...idly and test request will be ignored e Component Test will function as described in item 2 above f Check LED status g If LED status indicates proper operation RELEASE BLOWER ACCESS DOOR SWITCH replace blower access door and replace control access door WIRING DIAGRAMS Refer to Fig 5 6 and 7 for the 58YAV furnace wiring diagrams TROUBLESHOOTING Refer to service label See Fig 8 The Troubleshooting G...

Page 10: ...ill start and run for the entire component test The HSI blower motor heat speed and blower motor cool speed will run for 10 15 sec each Determine status code The status code is a 2 digit number with the first digit determined by the number of short flashes and the second digit by the number of long flashes Was there a previous fault code other than No 11 Does control respond to W Y or G 24 vac the...

Page 11: ...ed while gas valve was de energized Inducer will run until fault is cleared Check for Stuck open gas valve solenoid or leak Defective control center 23 PRESSURE SWITCH WILL NOT OPEN Check for Disconnected or obstructed pressure tubing Defective pressure switch 24 LOW VOLTAGE FUSE IS OPEN Check for Short in low voltage wiring including thermostat leads shorting to ductwork or furnace cabinet Discon...

Page 12: ...231 58yav3sm Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 6a 8a PC 101 Catalog No 535 771 Printed in U S A Form 58YAV 3SM Pg 12 10 00 Replaces 58YAV 2SM ...

Reviews: