i-Vu Open Link 

 

Turn on the i-Vu Open Link's power. 
 

For...

 

Use i-Vu Open Link 

port...

 

Wire Carrier 

terminal...

 

...to third-

party device 

terminal

 

EIA-232 

Set the port's 

jumper(s) on i-Vu 

Open Link 

S2 

TX 
Rx 
Signal Ground 

Rx 
Tx 
Gnd 

EIA-232 

EIA-485, 

2-wire 

 S2 

Net+ 
Net- 


EIA-485 
2-wire 
 

 

NOTES

 

 

If you cannot determine the media type or connections of the third-party device, contact your third-party 

representative. 

 

Use the same polarity throughout the network segment. 

 

Repeaters are required for more than 31 devices. See your third-party device manufacturer's 

recommendations. 

 

To reduce communication and data errors, terminate each end of an EIA-485 network with a resistor 

whose value equals the network's characteristic impedance. Some third-party manufacturers provide a 

built-in resistor that you enable or disable with a jumper. Make sure that only devices at the end of a 

network have termination enabled. 

EXAMPLE

  If an EIA-485 2-wire network's characteristic impedance is 120 Ohms, terminate one pair by 

placing a 120 Ohm resistor across the 

Net+

 and 

NET-

 connectors of the i-Vu Open Link. Terminate the 

other pair by placing a 120 Ohm resistor across the

 +

 and 

-

 connectors of the furthest third-party 

controller. 

 

A solid receive light on the i-Vu Open Link indicates a wiring or polarity problem. 

  
 

 

Addressing the i-Vu Open Link 

i-Vu Open Control hardware, when used in conjunction with i-Vu Open routers (i-Vu Open Link and i-Vu Open 

Router), has a convenient feature of automatic addressing. To address the i-Vu Open Link for third-party 

integration, using i-Vu/Field Assistant, go to 

Driver Properties 

Protocols

 > 

Properties 

tab. Refer to the 

appropriate protocol 

Integration Guide

 for further details.   

 
The i-Vu Open Link needs two addresses, one for the Open network and one for the IP Network. 

  

Summary of Contents for i-Vu Open Link

Page 1: ...in nk k I In ns st ta al ll la at ti io on n a an nd d S St ta ar rt t u up p G Gu ui id de e CARRIER CORPORATION 2010 A member of the United Technologies Corporation family Stock symbol UTX Catalog...

Page 2: ......

Page 3: ...se an IP addressing scheme 9 To obtain an IP address using DHCP 9 To assign a custom IP address 9 Configuring BACnet device instance and network number 12 Driver 13 To set up BACnet Broadcast Manageme...

Page 4: ......

Page 5: ...nected via a common BACnet IP backbone The i Vu Open Link can also integrate third party equipment supporting BACnet MS TP BACnet IP Modbus RTU Modbus IP and LON FT 10 protocols The i Vu Open Link has...

Page 6: ...5 may need to be installed on Port S1 if the i Vu Open Link is at the beginning or end of a network segment The BT485 adds bias and terminates a network segment Port S2 Configurable EIA 485 EIA 232 po...

Page 7: ...d brownout 0 to 140 F 18 to 60 C 0 to 90 relative humidity non condensing Storage temperature range 24 to 140 F 30 to 60 C 0 to 90 relative humidity non condensing Physical Rugged aluminum cover remov...

Page 8: ...te the printed circuit board with fingerprints moisture or any foreign material Do not touch components or leads Handle the board by its edges Isolate from high voltage or electrostatic discharge Ensu...

Page 9: ...the i Vu Open Link s power 9 Verify that the Run LED a dot in the lower right corner of the Module Status LED begins blinking The Module Status LED will display 8 for about 5 seconds and then reverts...

Page 10: ...orts and grounds 3 Verify that the Port S1 jumpers are set to 485 2w 4 Set the MS TP baud rate DIP switches 1 and 2 to match the baud rate of the Open network The default is 76 8k 5 Connect the i Vu O...

Page 11: ...able or disable with a jumper Make sure that only devices at the end of a network have termination enabled EXAMPLE If an EIA 485 2 wire network s characteristic impedance is 120 Ohms terminate one pai...

Page 12: ...8x where x router address subnet mask 255 255 255 0 default gateway 192 168 168 254 To set the i Vu Open Link address on the Open network CAUTION The router address must be unique on the IP and Open n...

Page 13: ...r assigned IP addressing The default IP address settings are as follows IP address 192 168 168 x where x i Vu Open Link address rotary switch settings Subnet Mask 255 255 255 0 Default Gateway 192 168...

Page 14: ...ng Standard desktop select Start right click on My Computer and select Manage b In the Computer Management window select Device Manager and expand Ports COM LPT 4 Ensure that i Vu Open Link s Router C...

Page 15: ...ault Gateway Click Enter 16 Type in the new Default Gateway Click Enter This Default Gateway will now show up on the Router Configuration screen 17 After entering your settings type 1 to reset and cli...

Page 16: ...n 5 Ground pin 5 4 Follow steps 4 19 above to launch a terminal program and access the Router Configuration screen to set the IP parameters 5 Reset the Port S2 jumper to the EIA 485 position 6 Cycle t...

Page 17: ...Router Configuration screen 2 Cycle power to the router for the new settings to effect NOTE If the BACnet MS TP network number of the router is assigned and not auto generated and the Open controllers...

Page 18: ...program uses when controller s real time clock is invalid Clock Fail Date and Time TIP Use an occupied date and time such as a Tuesday at 10 a m so the equipment does not operate in unoccupied mode i...

Page 19: ...ollers on one subnet to communicate with controllers on other subnets Enable i Vu to see upload or configure controllers on different subnets NOTE In this document the term router refers to the i Vu O...

Page 20: ...the BBMD BACnet Broadcast Management Device for its subnet 8 To check if the router has an existing BBMD table click Broadcast Distribution Table Read button 9 If the Broadcast Distribution Table con...

Page 21: ...Using the next IP address in the bdt file repeat steps 7 through 14 until every file has been updated NOTE To clear the BBMD entries from a router follow the steps above using an empty blank bdt file...

Page 22: ...set to 16 since this is the highest MS TP MAC address on the network This property optimizes MS TP network communications by preventing token passes and poll for master requests to non existent Master...

Page 23: ...turn to normal message stored in the i Vu Field Assistant database change the acknowledgement settings on i Vu Field Assistant s Alarm Enable Disable tab for an alarm source or an alarm category Recip...

Page 24: ...ctions in i Vu Help Controller generated Alarm Short message shown on i Vu s Alarm page or in an alarm action when this type of alarm is generated Description Events Clear these checkboxes to disable...

Page 25: ...oller alarms After this period minutes seconds of non response from an Open controller the router sends an alarm to the server Dead Module Timeout Alarm Store Forward On the Alarm Store and Forward pa...

Page 26: ...look for error conditions If you cannot determine the error from the Modstat send a screenshot of the Modstat to Carrier Technical Support To obtain a Modstat Go to the the Enhanced Access menu Select...

Page 27: ...he i Vu Open Link s 10 year Lithium CR123A battery provides a maximum of 720 hours data retention during power outages To conserve battery life battery backup turns off after a specified number of day...

Page 28: ...Vu Open Link Serial number If you need the i Vu Open Link s serial number when troubleshooting the number is on a sticker on the back of the main controller board a Module Status report modstat from...

Page 29: ...harmful interference in which case the user will be required to correct the interference at his own expense CAUTION Changes or modifications not expressly approved by the responsible party for compli...

Page 30: ...e Statement 26 i Vu Open Link The PIC statements are updated regularly Please refer to the BACnet website http www bacnetinternational net catalog index php m 28 for the latest information Appendix A...

Page 31: ......

Page 32: ...CARRIER CORPORATION 2010 A member of the United Technologies Corporation family Stock symbol UTX Catalog No 11 808 462 01 11 19 2010...

Reviews: