Step 6 — Attach Water Line to Humidifier and

Supply Line

1. Turn off the water supply to the line where the saddle valve

will be located. Mount the saddle valve (included) on the

water supply line. Do not pierce the supply line at this time.
Note: Saddle valve is self--piercing on copper lines. If steel
or iron pipe is used, a 1/4--in. (6.4 mm) hole must be drilled

in steel or iron pipe. Use only a grounded drill or hand drill
to avoid a shock hazard. Prior to drilling, turn off water sup-

ply and drain the pipe. The humidifier will function with
hot, cold, softened or unsoftened water, although hot water

will provide maximum evaporative capacity. Where water
pressure exceeds 125 psi, follow proper procedures and
codes to reduce pressure.

2. Run 1/4--in. (6.4 mm) diameter water line grade copper tub-

ing from saddle valve to solenoid valve.

3. Connect solenoid valve to 1/4--in. water line using compres-

sion fittings. Use two wrenches to tighten.

A13325

Fig. 9 -- Connect Solenoid Valve

4. Pierce the water line with the saddle valve. The saddle valve

should completely penetrate the supply line and be fully
open. (Refer to instructions on packaging of saddle valve.)

A13326

Fig. 10 -- Pierce Water Line with Saddle Valve

5. Open the water supply line.
6. Check for leaks at saddle valve and at solenoid valve con-

nections.

Step 7 — Install the Humidistat

The humidistat included with this unit can be either wall mounted
or duct mounted. Refer to installation instructions included in

humidistat box.

Step 8 — Wiring the Humidistat to Furnace or

Fan Coil

1. DISCONNECT ELECTRICAL POWER TO FUR-

NACE OR FAN COIL BEFORE PROCEEDING.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Before installing or servicing system, always turn off main

power to system. There may be more than one disconnect

switch. Lock out and tag switch with a suitable warning label.

!

WARNING

2. Use humidistat in low voltage (24VAC) applications only.

Install 24VAC wiring to humidifier control as shown in the

following wiring diagrams:

HUMIDIFIER

24 VAC LEADS

C

HUM

MANUAL
HUMIDIFIER
CONTROL

HUMIDIFIER CORD
PLUGGED INTO
120 VAC POWER SOURCE

A13315

Fig. 11 -- Typical Wiring to Standard Furnace

Summary of Contents for HUMXXSFP1012

Page 1: ...ry or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or d...

Page 2: ...evaporator pad removal NOTE The humidifier is not suitable for installation on ducts with horizontal airflow Performance will be reduced VERTICAL EVAP COIL A13330 Fig 3 Installation Location of Fan type Humidifier Step 3 Prepare Plenum Opening 1 In the selected location on the supply plenum carefully mark the maximum dimensions of the opening 11 3 8 in 29 2 cm wide by 11 1 4 in 28 6 cm high NOTE T...

Page 3: ...t tached to that end Distribution Tray Note Black Marking indicates top of pad A13327 Fig 6 Water Distribution Tray Placement 8 Place the water panel with attached distribution tray inside the base frame making sure the tray ends slide over the guide flanges and that the tray top flange seats flush The black marking indicates the top of pad 9 Attach the front panel assembly to the frame ensuring t...

Page 4: ...r line with the saddle valve The saddle valve should completely penetrate the supply line and be fully open Refer to instructions on packaging of saddle valve A13326 Fig 10 Pierce Water Line with Saddle Valve 5 Open the water supply line 6 Check for leaks at saddle valve and at solenoid valve con nections Step 7 Install the Humidistat The humidistat included with this unit can be either wall mount...

Page 5: ... 24VAC MIN 10 VA A13316 Fig 12 Typical Wiring to Standard Fan Coil INDOOR UNIT EQUIPMENT CONTROLLER C HUM 24 VAC LEADS HUMIDIFIER HUMIDIFIER CORD PLUGGED INTO 120 VAC POWER SOURCE A13317 Fig 13 Typical Wiring for Zoning Hook Up HUMIDIFIER 24 VAC LEADS HUM C D C B A INDOOR UNIT HUMIDIFIER CORD PLUGGED INTO 120 VAC POWER SOURCE A13318 Fig 14 Wiring for New Communicating Control Hook Up ...

Page 6: ...ult Lower humidistat setting in small steps until condensation disappears However if air is too dry raise the setting The table below should be used as a guideline for recommended humidistat settings RECOMMENDED HUMIDISTAT SETTING OUTSIDE TEMPERATURES RECOMMENDED HUMIDISTAT SETTING 20 F 29 C 15 10 F 23 C 20 LO 0 F 18 C 25 10 F 12 C 30 20 F 7 C 35 30 F 1 C 40 MED Step 10 Final Steps 1 Inform homeow...

Reviews: