background image

36" MAX.

CENTER LINE

OUTSIDE WALL

STEP 9:

Route the Wire from Control to Sensor

Run wire to the outdoor temperature sensor. Sensor is not affected by lead length. In either case, do not run outdoor temperature sensor alongside wires
carrying high voltage (120 VAC or higher). Secure the sensor bracket with a #8 galvanized screw.

STEP 10:

Attach Sensor Wire to
Humidifier Control

Strip wire 1/4 inch, and insert the wires from
the Sensor into the terminals labeled “ODT”
on the Humidifier Control. See 

Figure F

for

location of terminals.

Installing the Humidifier Control for Manual Operation

If it is not feasible to use the Outdoor Temperature Sensor, the Humidifier Control can be operated
in Manual Mode.

1. Connect the Manual Mode Resistor Case

wires to the terminals labeled “ODT” on the
Humidifier Control.

2. Snap the Manual Mode Resistor Case into the

slot provided so that Resistor Case sticks out
from the bottom edge of the base.

3. Remove the control knob and apply the

Manual Mode label to the cover, aligning the
sticker and knob holes. Re-install the knob.

STEP 8:

Alternate Location for Outdoor Temperature Sensor

The Sensor can also be mounted in the center of either:

• 2 inch PVC fresh air intake pipe for the furnace

OR

• 6 inch fresh air intake duct. Mount the sensor with a #8 galvanized screw.

In both cases, the Sensor must be no more than 3 feet from the outside wall. 
See Figure E.

If it is not feasible to use the Outdoor Temperature Sensor in any of the ways
described, the Humidifier Control can be installed for Manual Operation. 
See box below and 

Figure G

for details.

STEP 11:

Determine Power Source for Humidifier Control

Determine where you will get 24 VAC to power the Humidifier Control based on the 2 options below:

OPTION 1: 

FURNACES WITH ACCESSORY TERMINALS. If the accessory terminals provide:

• 24 VAC: Wire these directly to the “R” and “C” terminals on the Humidifier Control.

• 120 VAC: Wire to a 24 VAC transformer, which in turn connects to the “R” and “C” 

terminals on the Humidifier Control.

In either case, the voltage to the Humidifier Control must be between 22 VAC – 30 VAC.

OPTION 2: 

EXTERNAL 24 VAC TRANSFORMER: 

Wire into a power source other than the furnace
blower circuit. The transformer can be powered off
the 120 VAC line at the junction box before it enters
the furnace. The 24 volt side of the transformer is
connected to the “R” and “C” terminals on the
Humidifier Control.

STEP 12:

Wiring

NOTE:

The control will function with either a switched or continuous 24 VAC power source. See 

Diagrams A-D

for wiring options.

Figure E

Figure F

NOTES:

• The Humidifier Control will operate properly with either a switched or continuous power source.

• Whether using ACCESSORY TERMINALS OR an EXTERNAL TRANSFORMER, the minimum VA required is; 2.0 VA for 

Power Humidifiers; or 10.0 VA for Bypass Humidifiers.

• When power is connected for the first time, the red and green LEDs will light momentarily.

24V

R

C

BYP

ASS

ODT

H

PO

WER

R

24V

BYP

ASS

C

ODT

H

PO

WER

Figure G

NORTH, EAST
OR WEST SIDE
OF HOME

OUTDOOR

TEMPERATURE

SENSOR

SENSOR

BRACKET

SENSOR

ABOVE EXPECTED 

SNOW LINE

OUTDOOR

TEMPERATURE SENSOR

LEADS

Figure D

STEP 6:

Determine Location for Outdoor Temperature Sensor

The location of the Outdoor Temperature Sensor must meet these three requirements:

1. Must be mounted on North, East or West side of house out of direct sunlight
2. Must be at least 3 feet from all exhaust vents
3. Must be above expected snow line (See 

Figure D

)

Incorrect humidity levels will result if these requirements are not met.

STEP 7:

Locate Existing Access Hole to Outside

A convenient way to get the Sensor wire outside is to make use of unused
wires running to the A/C condensing unit (if applicable). Other ways are to use
existing holes for Cable TV lines, telephone lines, A/C lines, etc. Read all
equipment instructions beforehand for possible conflicts and warnings.

90-998

90-999

90-1012

90-1013

Reviews: