6. Reconnect drain cap to inducer housing.

7. Replace main furnace door.

8. Propylene glycol need not be removed before restarting

furnace.

WIRING DIAGRAM

See Fig. 16 for Wiring Diagram.

TROUBLESHOOTING

Use the Troubleshooting Guide, the status code LED on the
cotntrol and the Component Test to isolate furnace operation
problems.

STATUS CODES

For an explanation of status codes, refer to service label located on
back of main furnace door or Fig. 17 and the Troubleshooting
Guide. The stored status code will NOT be erased from the control
memory if 115- or 24-v power is interrupted.

NOTE:

Removing the blower access door will open the blower

access door switch and terminate 115-v power to the control.

To read current status code, remove main furnace door. The status
code LED can be viewed through the sight glass on the blower
access door.

NOTE:

NO thermostat signals may be present at control and all

blower off delays must be completed to view previous codes.

Make sure limit switch or flame rollout switch wire does not
contact any metal component, such as gas valve. If wire is
shorted, 3-amp fuse on furnace control will blow.

To retrieve previous codes, remove 1 of the red main limit or flame
rollout switch wires for 1 to 4 sec until the LED light goes out, then
reconnect it. (Do not leave red wire disconnected for longer
periods of time as the control will assume an overtemperature
condition exists and will respond with blower operation.) This
places the control in the status recall mode and displays the last
code stored in memory.

Record the code. After the last code is displayed the control will
perform the component test, and then return to normal standby
mode.

COMPONENT TEST

Blower access panel door switch opens 115-v power to
control board. No component operation can occur. Caution
must be taken when manually closing this switch for service
purposes. Failure to follow this warning could result in
electrical shock, personal injury, or death.

Use the Component Test to check furnace components for proper
operation. To initiate the component self-test sequence, shut off
the room thermostat or disconnect the

R

thermostat lead. Briefly

(approximately 2 sec) short the TWIN/TEST terminal to the C

OM

24V terminal. The status LED will turn off. The test sequence will
be as follows:

1. LED flashes last status code, or code 11, 4 times. Record this

status code for further troubleshooting.

2. The inducer will start and continue to run until test is over.

3. Hot surface igniter (HSI) is energized for 15 sec, then

de-energized.

4. Blower operates on continuous FAN speed for 10 sec, then

turns off.

5. The blower motor operates on HEATING speed for 10 sec,

then turns off.

6. The blower motor operates on COOLING speed for 10 sec,

then turns off.

7. Inducer turns off.

8. The gas valve and humidifier terminal HUM are not energized

for safety reasons.

11

Summary of Contents for GAS FURNACE 58MXA

Page 1: ...aning com pounds plastic or plastic containers gasoline kerosene cigarette lighter fluid dry cleaning fluids or other volatile fluids 3 Paint thinners and other painting compounds paper bags or other paper products Failure to follow this warning can cause corrosion of the heat exchanger fire personal injury or death NOTE Read the entire instruction manual before starting the installation This symb...

Page 2: ...talled in any of the 4 positions shown in Fig 2 you may need to revise your orientation to component location accordingly ELECTROSTATIC DISCHARGE ESD PRECAUTIONS Electrostatic discharge can affect electronic components Take precautions during furnace installation and servicing to protect the furnace electronic control Precautions will pre vent electrostatic discharges from personnel and hand tools...

Page 3: ...et adjacent to furnace 1 Turn off electrical supply to furnace 2 Remove filter cabinet door 3 Slide filter out of cabinet 4 If equipped with permanent washable filter clean filter by spraying cold tap water through filter in opposite direction of airflow Rinse filter and let dry Oiling or coating of the filter is not recommended 5 If equipped with factory specified disposable media filter replace ...

Page 4: ...stall blower assembly in furnace 11 Reinstall control box transformer and door switch assembly on blower shelf 12 Reinstall condensate trap and tubing if previously removed a Reinstall condensate trap in hole in blower shelf b Connect condensate trap drain tubes See Fig 8 or tubing diagram on main furnace door for proper tube location NOTE Ensure tubes are not kinked or pinched as this will affect...

Page 5: ...exchangers get an accumulation of light dirt or dust on the inside they may be cleaned by the following procedure NOTE If the heat exchangers get a heavy accumulation of soot and carbon both the primary and secondary heat exchangers should be replaced rather than trying to clean them thoroughly due to their intricate design A build up of soot and carbon indicates that a problem exists which needs ...

Page 6: ...ndary heat exchangers CANNOT be serviced or inspected A small number of bottom outlet openings can be inspected by removing the inducer assembly See Flushing Collector Box and Drainage System section for details on removing inducer assembly Step 5 Flushing Collector Box and Drainage System 1 Turn off gas and electrical supplies to furnace 2 Remove main furnace door 3 Disconnect inducer motor and p...

Page 7: ...UE PLUGGED END COLLECTOR BOXDRAIN TUBE BLUE WHITE STRIPED COLLECTOR BOX TUBE GREEN COLLECTOR BOX TUBE PINK COLLECTOR BOX EXTENSIONTUBE CONDENSATE TRAP INDUCER HOUSINGDRAIN TUBE VIOLET COLLECTOR BOX EXTENSION TUBE COLLECTOR BOXTUBE PINK COLLECTOR BOX DRAIN TUBE BLUE COLLECTOR BOX TUBE GREEN CONDENSATE TRAP INDUCER HOUSINGDRAIN TUBE VIOLET COLLECTOR BOX EXTENSION TUBE COLLECTOR BOXDRAIN TUBE BLUE WH...

Page 8: ...block out of bracket 6 To replace igniter igniter assembly reverse items 5a through 5d 7 Reconnect igniter wire connection 8 Turn on gas and electrical supplies to furnace 9 Verify igniter operation by initiating furnace control board self test feature or by cycling thermostat 10 Replace main furnace door Step 7 Electrical Controls and Wiring There may be more than 1 electrical supply to the unit ...

Page 9: ...d must be replaced use same type or equivalent wire W Y Y2 GND THERMOSTAT TERMINALS 1 2 3 Fig 12 Control Center A02142 BLW NUETRAL STATUS CODE LED SEC 2 SEC 1 EAC 2 L2 FUSE 3 AMP 0 5 AMP 24VAC HUM TEST TWIN Y1 DHUM G COM W W1 Y Y2 R 24V PLT 120 180 90 150 BLOWER OFF DELAY PLT 1 COOL HEAT SPARE 1 SPARE 2 FAN EAC 1 1 AMP 115VAC PR 1 L1 PL2 1 24 V THERMOSTAT TERMINALS 3 AMP FUSE LED OPERATION DIAGNOS...

Page 10: ... heat tape insulation If any damage or discolored insulation is evident replace heat tape 3 Check that heat tape power supply circuit is on Step 9 Winterizing Freezing condensate left in the furnace will damage the equipment If the furnace will be off for an extended period of time in a structure where the temperature will drop to 32 F or below winterize as follows 1 Turn off electrical supply to ...

Page 11: ...nger periods of time as the control will assume an overtemperature condition exists and will respond with blower operation This places the control in the status recall mode and displays the last code stored in memory Record the code After the last code is displayed the control will perform the component test and then return to normal standby mode COMPONENT TEST Blower access panel door switch open...

Page 12: ...UM 24VAC HUMIDIFIER CONNECTION 0 5 AMP MAX IDM INDUCED DRAFT MOTOR PSC IDR INDUCED DRAFT MOTOR RELAY SPST N O ILK BLOWER ACCESS PANEL INTERLOCK SWITCH SPST N O J1 BLOWER OFF DELAY JUMPER SELECTOR JB JUNCTION BOX LED LIGHT EMITTING DIODE FOR STATUS CODES AMBER LGPS LOW GAS PRESSURE SWITCH SPST N O LS LIMIT SWITCH AUTO RESET SPST N C OL AUTO RESET INTERNAL MOTOR OVERLOAD TEMPERATURE SWITCH N C PCB P...

Page 13: ...ing 31 PRESSURE SWITCH DID NOT CLOSE OR REOPENED If open longer than five minutes inducer shuts off for 15 minutes before retry Check for Excessive wind Proper vent sizing Defective inducer motor Low inducer voltage 115VAC Defective pressure switch Inadequate combustion air supply Restricted vent Disconnected or obstructed pressure tubing Low inlet gas pressure if LGPS used If it opens during blow...

Page 14: ...test sequence The inducer will start and run for the entire component test The HSI blower motor FAN speed AMBER LED boards only HEAT speed and COOL speed will run for 10 15 seconds each Gas valve and humidifier will not be turned on Was there a previous status code other than 11 Is door switch closed Is there 115V going to switch Replace door switch Replace transformer Does the control respond to ...

Page 15: ...stricted vent Proper vent sizing Excessive wind Blower motor on incorrect speed tap Input rate to furnace set too high 34 IGNITION PROVING FAILURE If flame is not sensed during the trial for ignition period the control will repeat the ignition sequence 3 more times before lockout 14 occurs If flame signal is lost during the blower on delay period blower will come on for the selected blower off del...