background image

FZ4ANP: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

8

A03003

Fig. 17 – Condensate Drain

NOTE: 

If unit is located in or above a living space where damage may

result  from  condensate  overflow,  a  field-supplied,  external  condensate

pan  should  be  installed  underneath  the  entire  unit,  and  a  secondary

condensate line (with appropriate trap) should be run from the unit into

the  pan.  Any  condensate  in  this  external  condensate  pan  should  be

drained  to  a  noticeable  place. As  an  alternative  to  using  an  external

condensate pan, some localities may allow the use of a separate 3/4-in

(19 mm)  condensate  line  (with  appropriate  trap) to  a  place where  the

condensate  will  be  noticeable.  The  owner  of  the  structure  must  be

informed  that  when  condensate  flows  from  the  secondary  drain  or

external condensate pan, the unit requires servicing or water damage will

occur.
Install  traps  in  the  condensate  lines  as  close  to  the  coil  as  possible

(

Fig. 17

). Make sure that the outlet of each trap is below its connection

to the condensate pan to prevent condensate from overflowing the drain

pan. Prime all traps, test for leaks, and insulate traps if located above a

living  area.  Condensate  drain  lines  should  be  pitched  downward  at  a

minimum slope of 1-in (25 mm) for every 10-ft (3 m) of length. Consult

local codes for additional restrictions or precautions.

ACCESSORIES

HUMIDIFIER

Connect humidifier and humidistat to fan coil unit as shown in 

Fig. 18

and 

Fig. 19

. The cooling lockout relay is optional.

SEQUENCE OF OPERATION

CONTINOUS FAN

Thermostat  closes  R  to  G.  G  energizes  fan  relay  on  PCB  which

completes circuit to indoor blower motor. When G is de-energized, there

is a 90 second delay before relay opens.

COOLING MODE

Thermostat energizes R to G, R to Y, and R to O (heat pump only). G

energizes  fan relay  on  PCB which completes  circuit to  indoor blower

motor. When G is de-energized, there is a 90 second delay before fan

relay opens.

HEAT PUMP HEATING WITH AUXILIARY 

ELECTRIC HEAT

Thermostat energizes R to G, R to Y, and R to W. G energizes fan relay

on PCB which completes circuit to indoor blower motor. W energizes

electric heat relay(s) which completes circuit to heater element(s). When

W  is  de-energized,  electric  heat  relay(s)  open,  turning  off  heater

elements. When G is de-energized there is a 90 second delay before fan

relay opens.

ELECTRIC HEAT OR EMERGENCY HEAT MODE

Thermostat  closes  R  to  W.  W  energizes  electric  heat  relay(s)  which

completes  circuit  to  heater  element(s).  Blower  motor  is  energized

through normally closed contacts on fan relay. When W is de-energized,

electric heat relay(s) opens.

A95294

Fig. 18 – Wiring Layout of Humidifier to Heat Pump

A95295

Fig. 19 – Wiring Layout of Humidifier to Fan Coil

with Electric Heat

CAUTION

!

PRODUCT DAMAGE HAZARD

Failure to follow this caution may result in product or property damage.
Use  only  full  size  P-traps  in  the  condensate  line  (

Fig. 15

).  Shallow

running  traps  are  inadequate  and  DO  NOT  allow  proper  condensate

drainage (

Fig. 16

).

FILTER
ACCESS
PANEL

SECONDARY DRAIN WITH
APPROPRIATE TRAP REQUIRED
(USE FACTORY KIT OR
FIELD-SUPPLIED TRAP)

PRIMARY TRAP REQUIRED

(USE FACTORY KIT OR 

FIELD-SUPPLIED TRAP OF 

SUFFICIENT DEPTH. 

STANDARD P-TRAPS ARE 

NOT SUFFICIENT. SEE 

FIGURE OF RECOMMENDED 

CONDENSATE TRAP)

R

G

C

E

L

O

Y

THERMOSTAT

R

R

C

O

Y

G

C

W

2

W

2

W

2

W

3

E

FAN COIL

(CONTROL)

HEAT PUMP

(CONTROL)

RED

GRY

BRN

WHT

WHT

BLU

VIO

HUMIDISTAT

RELAY

FAN HUMIDIFIER

115V

M

R

G

W

Y

THERMOSTAT

R

G

W

2

W

3

E

C

FAN COIL

(CONTROL)

C

Y

AIR COND.

HUMIDISTAT

FAN HUMIDIFIER

115V

RED

GRY

WHT

WHT

BLU

VIO

BRN

M

Summary of Contents for FZ4ANP

Page 1: ...s 5 through 30kW See Product Data literature for all available accessory kits HEATER PACKAGES This unit may or may not be equipped with an electric heater package For units not equipped with factory i...

Page 2: ...mid return air the Water Management Kit KFAHC0125AAA may need to be used to assist in water management A COIL UNITS POWER ENTRY OPTIONS LOW VOLT ENTRY OPTIONS FIELD MODIFIED SIDE RETURN LOCATION FOR S...

Page 3: ...f Units with A Coils 1 Remove blower and coil access panels Fig 5 2 Remove metal clip securing fitting panel to condensate pan Remove fitting panel 3 Remove 2 snap in clips securing A coil in unit 4 S...

Page 4: ...ertical condensate pan 15 Make sure liquid and suction tube grommets are in place to prevent air leaks and cabinet sweating MANUFACTURED HOUSING AND MOBILE HOME APPLICATIONS 1 Fan coil unit must be se...

Page 5: ...ance with the NEC and any local codes or ordinances that may apply Use copper wire only The unit must have a separate branch electric circuit with a field supplied disconnect switch located within sig...

Page 6: ...ay also be accomplished by using grounding lugs provided in control box MINIMUM CFM AND MOTOR SPEED SELECTION The fan speed selection is done at the motor connector Units with or without electric heat...

Page 7: ...line Finally caulk around the lines where they exit the fitting to retain the low leak rating of the unit Units are equipped with primary and secondary 3 4 in FPT drain connections For proper condensa...

Page 8: ...er motor When G is de energized there is a 90 second delay before relay opens COOLING MODE Thermostat energizes R to G R to Y and R to O heat pump only G energizes fan relay on PCB which completes cir...

Page 9: ...placement or cleaning on a monthly basis CAUTION PRODUCT DAMAGE HAZARD Failure to follow this caution may result in poor unit performance and or product damage Never operate unit without a filter Fact...

Page 10: ...cfm ton on 048 061 size could result in condensate blowing off coil or splashing out of drain pan Table 4 Airflow Performance CFM MODEL SIZE BLOWER SPEED 0 10 0 20 0 30 0 40 0 50 0 60 FZ4A 024 Tap 5 9...

Reviews: