background image

FZ4ANP: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

7

To  change  motor  speeds  disconnect  the  BLUE  fan  lead  from  motor

connector  terminal  #2  (factory  default  position)  and  move  to  desired

speed-tap; 1, 2, 3, or 5.
On single stage systems with dehum and two stage systems, use blower

speed taps 2 and 3 for straight match systems and blower speed taps 1

and 2 for up-sized indoor systems..
Speed-taps  1,  2,  and  3  have  a  90  second  blower  off  time  delay

pre-programmed  into  the  motor.  Speed-tap  4  is  used  for  electric  heat

only  (with  0-second  blower  time  delay)  and  the  WHITE  wire  should

remain on tap 4. Speed-tap 5 is used for high static applications, but has

a  0-second  blower  time  delay  pre-programmed  into  the  motor.  See

Airflow Performance tables for actual CFM. Also, see 

Fig. 14

 for motor

speed selection location.

NOTE: 

In low static applications, lower motor speed tap should be used

to reduce possibility of water being blown off coil.

REFRIGERANT TUBING CONNECTION AND 

EVACUATION

Use  accessory  tubing  package  or  field-supplied  tubing  of  refrigerant

grade.  Suction  tube  must  be  insulated.  Do  not  use  damaged,  dirty,  or

contaminated  tubing  because  it  may  plug  refrigerant  flow-control

device. ALWAYS  evacuate  the  coil  and  field-supplied  tubing  to  500

microns before opening outdoor unit service valves.

Units have sweat suction and liquid tube connections. Make suction tube

connection first.

1. Cut tubing to correct length.
2. Insert tube into sweat connection on unit until it bottoms.
3. Braze connection using silver bearing or non-silver bearing brazing

materials. Do not use solder (materials which melt below 800°F /

427°C). Consult local code requirements.

4. Evacuate coil and tubing system to 500 microns using deep vacuum

method.

REFRIGERANT FLOW-CONTROL DEVICE

The  FZ4ANP(024-061)  size  units  come  equipped  with  a  R-410A

refrigerant TXV. 
Always use outdoor units designed to match indoor fan coil applications.

CONDENSATE DRAINS

To connect drains, the cap openings must be removed. Use a knife to

start the opening near the tab and using pliers, pull the tab to remove the

disk.  Clean  the  edge  of  the  opening  if  necessary  and  install  the

condensate line. Finally caulk around the lines where they exit the fitting

to retain the low leak rating of the unit.

Units  are  equipped  with  primary  and  secondary  3/4-in.  FPT  drain

connections. For proper condensate line installations see 

Fig. 1

Fig. 2

,

Fig. 3

, 

Fig. 4

  and 

Fig. 5

.  To  prevent  property  damage  and  achieve

optimum  drainage  performance,  BOTH  primary  and  secondary  drain

lines  should  be  installed  and  include  properly-sized  condensate  traps

(

Fig. 15

 and 

Fig. 17

). Factory-approved condensate traps are available. It

is recommended that PVC fittings be used on the plastic condensate pan.

Finger-tighten plus 1-1/2 turns. Do not over-tighten. Use pipe dope.

NOTE: 

When connecting condensate drain lines, avoid blocking filter

access  panel,  thus  preventing  filter  removal. After  connection,  prime

both primary and secondary condensate traps.

A03002

Fig. 15 – Recommended Condensate Trap

A03013

Fig. 16 – Insufficient Condensate Trap

CAUTION

!

PRODUCT DAMAGE HAZARD

Failure to follow this caution may result in product or property damage.
A brazing shield MUST be used when tubing sets are being brazed to

the  unit  connections  to  prevent  damage  to  the  unit  surface  and

condensate pan fitting caps.

CAUTION

!

PRODUCT DAMAGE HAZARD

Failure to follow this caution may result in product or property damage.
Wrap a wet cloth around rear of fitting to prevent damage to TXV and

factory-made joints.

CAUTION

!

PRODUCT OPERATION HAZARD

Failure to follow this caution may result in improper product operation.
If  using  a  TXV  in  conjunction  with  a  single-phase  reciprocating

compressor,  a  compressor  start  capacitor  and  relay  are  required.

Consult outdoor unit pre-sale literature for start assist kit part number.

CAUTION

!

PRODUCT OR PROPERTY DAMAGE HAZARD

Failure to follow this warning caution may result in product or property

damage. 

The conversion of the fan coil to downflow requires special procedures

for  the  condensate  drains  on  both A-coil  and  Slope-coil  units.  The

vertical  drains  have  an  overflow  hole  between  the  primary  and

secondary drain holes. This hole is plugged for all applications except

downflow, and must be used for downflow. During conversion process,

remove plastic cap covering vertical drains only and discard. Remove

plug  from  overflow  hole  and  discard.  At  completion  of  downflow

installation, caulk around vertical pan fitting to door joint to retain low

air leak performance of the unit.

2” MIN

(51 mm)

UNIT

2” MIN

(51 mm)

DO NOT USE SHALLOW RUNNING TRAPS!

Summary of Contents for FZ4ANP

Page 1: ...s 5 through 30kW See Product Data literature for all available accessory kits HEATER PACKAGES This unit may or may not be equipped with an electric heater package For units not equipped with factory i...

Page 2: ...mid return air the Water Management Kit KFAHC0125AAA may need to be used to assist in water management A COIL UNITS POWER ENTRY OPTIONS LOW VOLT ENTRY OPTIONS FIELD MODIFIED SIDE RETURN LOCATION FOR S...

Page 3: ...f Units with A Coils 1 Remove blower and coil access panels Fig 5 2 Remove metal clip securing fitting panel to condensate pan Remove fitting panel 3 Remove 2 snap in clips securing A coil in unit 4 S...

Page 4: ...ertical condensate pan 15 Make sure liquid and suction tube grommets are in place to prevent air leaks and cabinet sweating MANUFACTURED HOUSING AND MOBILE HOME APPLICATIONS 1 Fan coil unit must be se...

Page 5: ...ance with the NEC and any local codes or ordinances that may apply Use copper wire only The unit must have a separate branch electric circuit with a field supplied disconnect switch located within sig...

Page 6: ...ay also be accomplished by using grounding lugs provided in control box MINIMUM CFM AND MOTOR SPEED SELECTION The fan speed selection is done at the motor connector Units with or without electric heat...

Page 7: ...line Finally caulk around the lines where they exit the fitting to retain the low leak rating of the unit Units are equipped with primary and secondary 3 4 in FPT drain connections For proper condensa...

Page 8: ...er motor When G is de energized there is a 90 second delay before relay opens COOLING MODE Thermostat energizes R to G R to Y and R to O heat pump only G energizes fan relay on PCB which completes cir...

Page 9: ...placement or cleaning on a monthly basis CAUTION PRODUCT DAMAGE HAZARD Failure to follow this caution may result in poor unit performance and or product damage Never operate unit without a filter Fact...

Page 10: ...cfm ton on 048 061 size could result in condensate blowing off coil or splashing out of drain pan Table 4 Airflow Performance CFM MODEL SIZE BLOWER SPEED 0 10 0 20 0 30 0 40 0 50 0 60 FZ4A 024 Tap 5 9...

Reviews: