background image

FZ4ANP: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

6

A160010A

Fig. 10 – Wiring Layout 2-Stage Air Conditioning Unit

A160011A

Fig. 11 – Wiring Layout 2-Stage Heat Pump Unit

A03088

Fig. 12 – Wiring Layout Heat Pump Unit 

(Cooling and 2-Stage Heat for Manufactured Housing)

MANUFACTURED HOUSING

In manufactured housing applications, the Code of Federal Regulations,

Title 24, Chapter XX, Part 3280.714 requires that supplemental electric

heat be locked out at outdoor temperatures above 40°F (4°C), except for

a heat pump defrost cycle. Refer to 

Fig. 12

for typical low voltage wiring

with outdoor thermostat.

TRANSFORMER INFORMATION

Transformer  is  factory  wired  for  230V  operation.  For  208V

applications,  disconnect  the  black  wire  from  the  230V  terminal  on

transformer and connect it to the 208V terminal (

Fig. 13

).

A05182

Fig. 13 – Transformer Connections

HEATER STAGING

If electric heat staging is required, a multi-stage heating room thermostat

is required. Consult your equipment supplier for a suitable thermostat.

GROUND CONNECTIONS

NOTE: 

Use UL  listed  conduit  and conduit connectors for  connecting

supply wire(s) to unit to obtain proper grounding. Grounding may also

be accomplished by using grounding lugs provided in control box. 

MINIMUM CFM AND MOTOR SPEED SELECTION

The fan  speed selection is done at the motor connector. Units with or

without  electric  heaters  require  a  minimum  CFM.  Refer  to  the  unit

wiring label to ensure that the fan speed selected is not lower than the

minimum fan speed indicated. 

A11048

Fig. 14 – Motor Speed Selection

† electric heat airflow is same CFM as Tap 3, except 0 sec off delay 

‡ high static applications, see airflow tables for max airflow

O

W

HI or Y2

HI or Y2

R

E

W

2

R

C

THERMOSTAT

FAN COIL

(CONTROL)

HEAT PUMP

(CONTROL)

G

C

W

2

E

L

G

C

R

O

Y

ODTS

O

Y

W

3

W

2

230

C

208

BRN

RED

YEL

BLK

SECONDARY

PRIMARY

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to establish  uninterrupted or unbroken ground could result in

personal injury and/or death.

According to NEC, NFPA 70, and local codes, the cabinet must have an

uninterrupted  or  unbroken  ground  to  minimize  personal  injury  if  an

electrical fault should occur. The ground may consist of electrical wire

or metal conduit when installed in accordance with existing electrical

codes. If conduit connection uses reducing washers, a separate ground

wire must be used.

Table 1 – Motor Speed Selection

Tap 1

Low 

90 sec off delay

Tap 2

Medium 

90 sec off delay

Tap 3

High 

90 sec off delay

Tap 4

Electric heat †

0 sec off delay

Tap 5

Max ‡

0 sec off delay

1   2   3   4   5

Speed Taps may be located on motor,
or on plug close to motor.

CL

G

N

1   2   3   4   5

Summary of Contents for FZ4ANP

Page 1: ...s 5 through 30kW See Product Data literature for all available accessory kits HEATER PACKAGES This unit may or may not be equipped with an electric heater package For units not equipped with factory i...

Page 2: ...mid return air the Water Management Kit KFAHC0125AAA may need to be used to assist in water management A COIL UNITS POWER ENTRY OPTIONS LOW VOLT ENTRY OPTIONS FIELD MODIFIED SIDE RETURN LOCATION FOR S...

Page 3: ...f Units with A Coils 1 Remove blower and coil access panels Fig 5 2 Remove metal clip securing fitting panel to condensate pan Remove fitting panel 3 Remove 2 snap in clips securing A coil in unit 4 S...

Page 4: ...ertical condensate pan 15 Make sure liquid and suction tube grommets are in place to prevent air leaks and cabinet sweating MANUFACTURED HOUSING AND MOBILE HOME APPLICATIONS 1 Fan coil unit must be se...

Page 5: ...ance with the NEC and any local codes or ordinances that may apply Use copper wire only The unit must have a separate branch electric circuit with a field supplied disconnect switch located within sig...

Page 6: ...ay also be accomplished by using grounding lugs provided in control box MINIMUM CFM AND MOTOR SPEED SELECTION The fan speed selection is done at the motor connector Units with or without electric heat...

Page 7: ...line Finally caulk around the lines where they exit the fitting to retain the low leak rating of the unit Units are equipped with primary and secondary 3 4 in FPT drain connections For proper condensa...

Page 8: ...er motor When G is de energized there is a 90 second delay before relay opens COOLING MODE Thermostat energizes R to G R to Y and R to O heat pump only G energizes fan relay on PCB which completes cir...

Page 9: ...placement or cleaning on a monthly basis CAUTION PRODUCT DAMAGE HAZARD Failure to follow this caution may result in poor unit performance and or product damage Never operate unit without a filter Fact...

Page 10: ...cfm ton on 048 061 size could result in condensate blowing off coil or splashing out of drain pan Table 4 Airflow Performance CFM MODEL SIZE BLOWER SPEED 0 10 0 20 0 30 0 40 0 50 0 60 FZ4A 024 Tap 5 9...

Reviews: