background image

CAUTION: The conversion of the fan coil to downflow requires special procedures for the condensate drains on both

A coil and Slope units. The vertical drains have an overflow hole between the primary and secondary drain holes. This hole
is plugged for all applications except downflow, but must be used for downflow. During the conversion process, remove the
plastic cap covering the vertical drains only and discard. Remove the plug from the overflow hole and discard. At completion
of the downflow installation, caulk around the vertical pan fitting to door joint to retain the low air leak performance of the
unit. Failure to follow this CAUTION could result in minor personal injury or product and property damage.

Units are equipped with primary and secondary 3/4-in. FPT drain connections. For proper condensate line installation see Fig. 2, 4, 5, 6, and 8.
To prevent property damage and achieve optimum drainage performance, BOTH primary and secondary drain lines should be installed and include
properly-sized condensate traps. (See Fig. 14 and 16.) Factory-approved condensate traps are available. Be sure to install plastic push-in plugs in
unused condensate drain fittings. It is recommended that PVC fittings be used on the plastic condensate pan. Do not over-tighten. Finger-tighten
plus 1-1/2 turns. Use pipe dope.

CAUTION: Shallow running traps are inadequate and DO NOT allow proper condensate drainage. (See Fig. 15.) Failure

to follow this CAUTION could result in minor personal injury or product and property damage.

NOTE:

When connecting condensate drain lines avoid blocking filter access panel. Prime both primary and secondary condensate traps after

connecting to drain pan.

NOTE:

If unit is located in or above a living space where damage may result from condensate overflow, a field-supplied external condensate pan

should be installed underneath the entire unit, and a secondary condensate line (with appropriate trap) should be run from the unit into the pan.
Any condensate in this external condensate pan should be drained to a noticeable place. As an alternative to using an external condensate pan, some
localities may allow the use of a separate 3/4-in. condensate line (with appropriate trap) to a place where the condensate will be noticeable. The
owner of the structure must be informed that when condensate flows from the secondary drain or external condensate pan, the unit requires
servicing, or water damage will occur.
Install traps in the condensate lines as close to the coil as possible. (See Fig. 16.) Make sure that the outlet of each trap is below its connection
to the condensate pan to prevent condensate from overflowing the drain pan. Prime all traps, test for leaks, and insulate traps if located above a
living area.
Condensate drain lines should be pitched downward at a minimum of 1 in. for every 10 ft. of length. Consult local codes for additional restrictions
or precautions.

CAUTION: Never operate unit without a filter or with filter access door removed. Damage to blower motor or coil can

result. Failure to follow this CAUTION could result in minor personal injury or product and property damage.

IMPORTANT:

Factory authorized filters must be used when locating the filter inside the unit. (See Table 1.) For those applications where access

to an internal filter is impractical, a field-supplied filter must be installed in the return duct system.

PROCEDURE 7—UNIT START-UP

Refer to outdoor unit Installation Instructions for system start-up instructions and refrigerant charging method details.

PROCEDURE 8—EASY SELECT CONFIGURATION TAPS

Easy Select™ taps are used by the installer to configure a system. The ECM motor uses the selected taps to modify its operation to a
pre-programmed table of airflows. (See Table 3 and 4.) Airflows are based on system size or mode of operation and those airflows are modified
in response to other inputs such as the need for de-humidification. (See Fig. 17 and 18.)
The FV4B Fan Coil must be configured to operate properly with system components with which it is installed. To successfully configure a basic
system (see information printed on circuit board label located next to select pins), move the 6 select wires to the pins which match the components
used.

A.

AUX HEAT KW/CFM - Select heater range for size of electric heater installed

Installer must select the auxiliary heat airflow approved for application with kw size heater installed. If no heater is installed, this step can be
skipped. Each select pin is marked with a range of heaters for which airflow, also marked, is approved. For increased comfort select the narrowest
kw range matching the heater size, for example, 0-10 for 10-kw heater. This airflow must be greater than the minimum CFM for electric heater

230

C

208

BRN
RED

YEL
BLK

SECONDARY

PRIMARY

Fig. 13 - Transformer Connections

A94067

—10—

Summary of Contents for FV4B

Page 1: ...work gloves Use quenching cloth for brazing operations Have fire extinguisher available Read these instructions thoroughly and follow all warnings or cautions attached to the unit Consult local buildi...

Page 2: ...orizontal left applications as factory shipped See Fig 2 4 and 8 Units can be installed for horizontal right applications with field modifications Units may be converted for downflow applications usin...

Page 3: ...ide of unit and reinstall on coil support rail on right side of unit Fig 2 Slope Coil Unit in Upflow Application A00091 A COIL UNITS POWER ENTRY OPTIONS LOW VOLT ENTRY OPTIONS FIELD MODIFIED SIDE RETU...

Page 4: ...e sheets f Install hose onto plastic spout 7 Install horizontal pan on right side of coil assembly Fig 4 Slope Coil in Horizontal Left Application Factory Ready A00096 UNIT FIELD SUPPLIED HANGING STRA...

Page 5: ...cal pan fitting to door joint to retain the low air leak performance of the unit Failure to follow this CAUTION could result in personal injury or product and property damage In this application field...

Page 6: ...nect switch remote to the unit is turned off Failure to do so will result in electrical shock causing personal injury or death A Line Voltage Connections If unit contains an electric heater remove and...

Page 7: ...nufactured housing applications the Code of Federal Regulations Title 24 Chapter XX Part 3280 714 requires that supplemental electric heat be locked out at outdoor temperatures above 40 deg F except f...

Page 8: ...n Coil Wiring with 1 Speed Air Conditioner A98477 O W2 Y1 W2 W W1 G R W2 Y1 INDOOR CONTROL FAN COIL 1 SPEED AIR CONDITIONER W1 G C Y C DHUM HUM B S1 S2 Y Y2 R O C DH HEAT STAGE 2 N A HEAT STAGE 1 COOL...

Page 9: ...Wiring with 1 Speed Heat Pump A98475 O W2 W W1 Y1 W2 G R O W2 INDOOR CONTROL FAN COIL 1 SPEED HEAT PUMP W1 G C Y R W2 O C DHUM HUM B S1 S2 Y Y2 R Y1 C DH HEAT STAGE 3 HEAT STAGE 2 HEAT COOL STAGE 1 R...

Page 10: ...condensate flows from the secondary drain or external condensate pan the unit requires servicing or water damage will occur Install traps in the condensate lines as close to the coil as possible See...

Page 11: ...ory setting for air conditioner or heat pump size is the largest unit meant for application with the model of fan coil purchased Installer needs to select air conditioner or heat pump size to ensure t...

Page 12: ...ave a 1 minute off delay and zero on delay programmed into the ECM motor that cannot be overridden Four motor operation delay profiles are provided to customize and enhance system operation See Fig 17...

Page 13: ...AC HP CFM ADJUST Select NOM 5 ON OFF DELAY Select 0 90 profile 6 CONTINUOUS FAN Select desired fan speed when thermostat is set to continuous fan I COMFORT OPTIONS WARMER HEATING AND SUPER DEHUMIDIFY...

Page 14: ...AUX and HUM terminals on the Easy Select Board are tied directly to the G terminal and provide a 24 vac signal whenever the G terminal is energized See Fig 17 and 18 During Super Dehumidify and SuperC...

Page 15: ...iguration instructions If the indoor temperature is below the temperature set point and the humidity is above the humidity set point the Thermidistat closes circuit R to O opens circuits R to DH and R...

Page 16: ...60 1050 610 770 1225 700 880 1400 875 1100 1750 NOTE 1 The above airflows result with the AC HP CFM ADJUST select jumper set on NOM 2 Airflow can be adjusted 15 percent or 10 percent by selecting HI o...

Page 17: ...LO NOM HI 005 30 000 975 975 1040 1100 1100 1100 36 000 980 1085 1250 1100 1100 1250 1250 1250 1250 42 000 1140 1270 1460 1140 1270 1460 1250 1270 1460 48 000 1305 1450 1665 1305 1450 1665 1305 1450 1...

Page 18: ...SELECT BOARD 1 Unplug harness from board 2 Check for appropriate voltages on pins with Easy Select Board screw terminals jumpered See Table 7 for values and see example below If proper signals are no...

Page 19: ...e The disconnect when used on access panel does not disconnect power to the line side of disconnect but does allow safe service to all other parts of unit If unit does not have a disconnect disregard...

Page 20: ...utor for maintenance procedures WARNING As with any mechanical equipment personal injury can result from sharp metal edges etc therefore care should be taken when removing parts Using the Owner s User...

Page 21: ...n as other HFC s is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig Do not install a s...

Page 22: ...22...

Page 23: ...23...

Page 24: ...2003 CAC BDP 7310 W Morris St Indianapolis IN 46231 imfv4B02 24 Book Tab 1 4 3d 2e Catalog No 63FV 4B1...

Reviews: