The ECM motor used with this product contains two parts: the control module and motor winding section. Do not assume the motor or module
is defective if it will not start. Go through the steps described below before replacing control module, Easy Select Board or entire motor. The
control module is available as a replacement part.

Table 2—CFM Range for FV4B Units

FAN COIL SIZE

SYSTEM SIZES

CFM RANGE

FV4BNF002

024, 030, 036

450-1275

FV4BNF003

024, 030, 036, 042

525-1475

FV4BNF005

036, 042, 048

550-1700

FV4BNB006

042, 048, 060

550-2150

Table 3—FV4B Fan Coil Airflow Delivery (CFM) in Cooling Mode

UNIT

SIZE

OUTDOOR

UNIT

CAPACITY

OPERATING MODE

FAN ONLY

LO/MED/HI

Single-Speed

Application

Two-Speed

Application

High Speed

Low Speed

Nominal

A/C

Cooling

A/C

Cooling

Dehumidity

Nominal

A/C

Cooling

A/C

Cooling

Dehumidity

Nominal

A/C

Cooling

A/C

Cooling

Dehumidity

002

018
024
030
036

525
700
875

1050

420
560
700
840

735

1100

590

880

440

660

350

530

350/350/525
350/440/700
440/550/875

525/660/1050

003

024
030
036
042

700
875

1050
1225

560
700
840
980

735

1100

590

880

440

660

415

530

415/440/700
440/550/875

525/660/1050
610/770/1225

005

030
036
042
048

875

1050
1225
1400

700
840
980

1120

1100

1470

880

1175

660

880

530

705

440/550/875

525/660/1050
610/770/1225
700/880/1400

006

036
042
048
060

1050
1225
1400
1750

840
980

1120
1400

1100

1470
1835

880

1175
1470

660

880

1100

530

705
880

525/660/1050
610/770/1225
700/880/1400

875/1100/1750

NOTE
1. The above airflows result with the AC/HP CFM ADJUST select jumper set on NOM.
2. Airflow can be ad15 percent or -10 percent by selecting HI or LO respectively for all modes except fan only.
3. Dry coil at 230 volts and with 10kw heater and filter installed.
4. Airflows shown are at standard air conditions.

Table 4—FV4B Fan Coil Airflow Delivery (CFM) in Heat Pump Only Heating Mode

UNIT

SIZE

OUTDOOR

UNIT

CAPACITY

OPERATING MODE

FAN ONLY

LO/MED/HI

Single-Speed

Application

Two-Speed

Application

High Speed

Low Speed

Heat Pump

Comfort

Heat Pump

Efficiency

Heat Pump

Comfort

Heat Pump

Efficiency

Heat Pump

Comfort

Heat Pump

Efficiency

002

018
024
030
036

420
560
700
840

525
700
875

1050

660

990

735

1100

395

595

440

660

350/350/470
350/395/630
440/520/785
525/595/945

003

024
030
036
042

560
700
840
980

700
875

1050
1225

660

990

735

1100

415

595

440

660

415/415/630
440/520/785
525/595/945

610/695/1100

005

030
036
042
048

700
840
980

1120

875

1050
1225
1400

990

1320

1100

1470

595

795

660

880

440/520/785
525/595/945

610/695/1100
700/795/1260

006

036
042
048
060

840
980

1120
1400

1050
1225
1400
1750

990

1325
1655

1100

1470
1835

595

795
990

660

880

1100

525/595/945

610/695/1100
700/795/1260
875/990/1575

NOTE
1. The above airflows result with the AC/HP CFM ADJUST select jumper set on NOM.
2. Airflow can be ad15 percent or -10 percent by selecting HI or LO respectively for all modes except fan only.
3. Dry coil at 230 volts and with 10kw heater and filter installed.
4. Airflows shown are at standard air conditions.

—16—

Summary of Contents for FV4B

Page 1: ...work gloves Use quenching cloth for brazing operations Have fire extinguisher available Read these instructions thoroughly and follow all warnings or cautions attached to the unit Consult local buildi...

Page 2: ...orizontal left applications as factory shipped See Fig 2 4 and 8 Units can be installed for horizontal right applications with field modifications Units may be converted for downflow applications usin...

Page 3: ...ide of unit and reinstall on coil support rail on right side of unit Fig 2 Slope Coil Unit in Upflow Application A00091 A COIL UNITS POWER ENTRY OPTIONS LOW VOLT ENTRY OPTIONS FIELD MODIFIED SIDE RETU...

Page 4: ...e sheets f Install hose onto plastic spout 7 Install horizontal pan on right side of coil assembly Fig 4 Slope Coil in Horizontal Left Application Factory Ready A00096 UNIT FIELD SUPPLIED HANGING STRA...

Page 5: ...cal pan fitting to door joint to retain the low air leak performance of the unit Failure to follow this CAUTION could result in personal injury or product and property damage In this application field...

Page 6: ...nect switch remote to the unit is turned off Failure to do so will result in electrical shock causing personal injury or death A Line Voltage Connections If unit contains an electric heater remove and...

Page 7: ...nufactured housing applications the Code of Federal Regulations Title 24 Chapter XX Part 3280 714 requires that supplemental electric heat be locked out at outdoor temperatures above 40 deg F except f...

Page 8: ...n Coil Wiring with 1 Speed Air Conditioner A98477 O W2 Y1 W2 W W1 G R W2 Y1 INDOOR CONTROL FAN COIL 1 SPEED AIR CONDITIONER W1 G C Y C DHUM HUM B S1 S2 Y Y2 R O C DH HEAT STAGE 2 N A HEAT STAGE 1 COOL...

Page 9: ...Wiring with 1 Speed Heat Pump A98475 O W2 W W1 Y1 W2 G R O W2 INDOOR CONTROL FAN COIL 1 SPEED HEAT PUMP W1 G C Y R W2 O C DHUM HUM B S1 S2 Y Y2 R Y1 C DH HEAT STAGE 3 HEAT STAGE 2 HEAT COOL STAGE 1 R...

Page 10: ...condensate flows from the secondary drain or external condensate pan the unit requires servicing or water damage will occur Install traps in the condensate lines as close to the coil as possible See...

Page 11: ...ory setting for air conditioner or heat pump size is the largest unit meant for application with the model of fan coil purchased Installer needs to select air conditioner or heat pump size to ensure t...

Page 12: ...ave a 1 minute off delay and zero on delay programmed into the ECM motor that cannot be overridden Four motor operation delay profiles are provided to customize and enhance system operation See Fig 17...

Page 13: ...AC HP CFM ADJUST Select NOM 5 ON OFF DELAY Select 0 90 profile 6 CONTINUOUS FAN Select desired fan speed when thermostat is set to continuous fan I COMFORT OPTIONS WARMER HEATING AND SUPER DEHUMIDIFY...

Page 14: ...AUX and HUM terminals on the Easy Select Board are tied directly to the G terminal and provide a 24 vac signal whenever the G terminal is energized See Fig 17 and 18 During Super Dehumidify and SuperC...

Page 15: ...iguration instructions If the indoor temperature is below the temperature set point and the humidity is above the humidity set point the Thermidistat closes circuit R to O opens circuits R to DH and R...

Page 16: ...60 1050 610 770 1225 700 880 1400 875 1100 1750 NOTE 1 The above airflows result with the AC HP CFM ADJUST select jumper set on NOM 2 Airflow can be adjusted 15 percent or 10 percent by selecting HI o...

Page 17: ...LO NOM HI 005 30 000 975 975 1040 1100 1100 1100 36 000 980 1085 1250 1100 1100 1250 1250 1250 1250 42 000 1140 1270 1460 1140 1270 1460 1250 1270 1460 48 000 1305 1450 1665 1305 1450 1665 1305 1450 1...

Page 18: ...SELECT BOARD 1 Unplug harness from board 2 Check for appropriate voltages on pins with Easy Select Board screw terminals jumpered See Table 7 for values and see example below If proper signals are no...

Page 19: ...e The disconnect when used on access panel does not disconnect power to the line side of disconnect but does allow safe service to all other parts of unit If unit does not have a disconnect disregard...

Page 20: ...utor for maintenance procedures WARNING As with any mechanical equipment personal injury can result from sharp metal edges etc therefore care should be taken when removing parts Using the Owner s User...

Page 21: ...n as other HFC s is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig Do not install a s...