D.

Dehumidify Capability with Standard Humidistat Connection

Latent capacities for systems using the FK4C Fan Coil are better than average systems. If increased latent capacity is an application requirement,
the field wiring terminal block provides connection terminals for use of standard humidistat. The FK4C Fan Coil will detect humidistat contacts
opening on increasing humidity and reduce its airflow to approximately 80 percent of nominal cooling mode airflow. This reduction will increase
system latent capacity until humidity falls to a level which causes humidistat to close its contacts. When contacts close, airflow will return to 100
percent of selected cooling airflow. To activate this mode, remove Jumper J1 and wire in a standard humidistat. (See Fig. 21.)

E.

Dehumidify and Super Dehumidify Capabilities

This model fan coil is capable of responding to a signal from indoor system control (thermostat, thermidistat, zoning control) to operate in comfort
control modes such as Super Dehumidify Mode. Consult literature provided with indoor system control to determine if these operating modes are
available, and to see control set up instructions. No special setup or wiring of fan coil is required.

Fig. 17—PCB Wiring Arrangement

A95276

EASY SELECT

D

H

R

W

1

W

2

Y

1

Y/Y

2

G

O

C

HEATER/MOTOR

CEBD430226-01B   CESS430226-01B

AUX HEAT KW/CFM

0-30

1075

SEC1

SEC2

J1

J2

AC/HP SIZE

036

030

024

018

AC

HP-COMFORT

HP-EFF

NOM

HI

ENH

LO

SYSTEM TYPE

AC/HP CFM ADJUST

ON/OFF DELAY

CONTINUOUS FAN

MED

HI

YEL

LO

AUX1

HUM1

AUX2

24VAC

GRY

HUM2

YEL

WHT

BLK

ORN

BLU

VIO

0-20

875

0-10

725

0

90

30
90

0
0

0-5

625

TM

12-PIN MATE-N-LOCK

ELECTRIC HEAT CONNECTOR

—14—

Summary of Contents for FK4C

Page 1: ...ructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most se...

Page 2: ...LEFT APPLICATIONS FRONT VIEW SHOWN WITH A COIL DETAILS CONNECTION LOCATIONS FOR UPFLOW OR HORIZ APPLICATIONS 3 1 16 4 11 16 10 3 4 9 1 2 LIQUID LINE CONNECTION SUCTION LINE CONNECTION ACCESS PANEL CON...

Page 3: ...P 4 PLACES 1 TYP 2 PLACES 2 7 8 2 3 16 TYP 2 PLACES SECONDARY DRAIN PRIMARY DRAIN 5 16 TYP 1 5 16 3 1 4 1 TYP 2 PLACES SECONDARY DRAIN PRIMARY DRAIN HORIZ RIGHT FIELD CONVERTED 1 5 16 1 11 16 2 1 2 TY...

Page 4: ...and width of unit A Upflow Installation If return air is to be ducted install duct flush with floor Set unit on floor over opening Only use return air opening provided All return air must pass throug...

Page 5: ...rommets after brazing E Horizontal Right Conversion of Units With A Coil To convert units for horizontal right installations 1 Remove blower and coil access panels See Fig 8 2 Remove metal clip securi...

Page 6: ...access and fitting panels aligning holes with tubing connections and condensate pan connections Be sure to reinstall metal clip between fitting panel and vertical condensate pan Fig 6 Slope Coil in Ho...

Page 7: ...tested by UL Standard 181 for Class 1 air ducts PROCEDURE 4 ELECTRICAL CONNECTIONS A Line Voltage Connections Units with 15 and 20 kw heaters are factory wired for dual circuit operation When single...

Page 8: ...to 3 stage operation Connect low voltage leads to thermostat and outdoor unit See Fig 9 and 10 C Intelligent Heat Option Intelligent Heat staging of the electric heat package is possible when the FK4C...

Page 9: ...fault should occur The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes Failure to follow this warning could result in an electrical s...

Page 10: ...tat closes circuit R to W W1 or W2 The fan coil delivers the selected electric heat airflow G Heat Pump Heating Mode Single speed or 2 Speed High 1 Thermostat closes circuits R to G and R to Y Y2 The...

Page 11: ...pan should be installed underneath the entire unit and a secondary condensate line with appropriate trap should be run from the unit into the pan Any condensate in this external condensate pan should...

Page 12: ...AC HP SIZE Select system size installed The factory setting for air conditioner or heat pump size is the largest unit meant for application with the model of fan coil purchased Installer needs to sel...

Page 13: ...gnal is present whenever the G thermostat signal is present heat pump heating cooling and continuous blower modes When the FK4C Fan Coil is installed with an electronic air cleaner use EAC relay kit P...

Page 14: ...and wire in a standard humidistat See Fig 21 E Dehumidify and Super Dehumidify Capabilities This model fan coil is capable of responding to a signal from indoor system control thermostat thermidistat...

Page 15: ...ensate drain each cooling season for cleanliness Clean as necessary An inspection port is provided on all A coil delta plates Remove plastic plug to inspect 3 Inspect blower motor and wheel for cleanl...

Page 16: ...ay to increase your knowledge of the equipment discussed in this manual including Unit Familiarization Maintenance Installation Overview Operating Sequence A large selection of product theory and skil...

Reviews: