background image

PROCEDURE 8—UNIT START-UP

Refer to outdoor unit Installation Instructions for system start-up instructions and refrigerant charging method details.

PROCEDURE 9—EASY SELECT CONFIGURATION TAPS

EASY SELECT taps are used by the installer to configure a system. ICM2 uses the selected taps to modify its operation to a pre-programmed table
of airflows. Airflows are based on system size or mode of operation and those airflows are modified in response to other inputs such as the need
for de-humidification. (See Fig. 16 and 17.)

The FK4C Fan Coil must be configured to operate properly with system components with which it is installed. To successfully configure a basic
system (see information printed on circuit board label located next to select pins), move the 6 select wires to the pins which match the components
used.

A.

AUX HEAT KW/CFM – Select heater range for size of electric heater installed

Installer must select the auxiliary heat airflow approved for application with kw size heater installed. If no heater is installed, this step can be
skipped. Each select pin is marked with a range of heaters for which airflow, also marked, is approved. The heater installed must fall within the
range selected for safe and continuous operation. Note that airflow marked is the airflow which will be supplied in emergency heat mode and
heating mode on air conditioners when electric heat is the primary heating source. In heat pump heating mode when electric heaters are energized,
the ICM2 will run the higher of heat pump heating airflow and electric heater airflow to ensure safe heater operation. The factory selection is the
largest heater range approved. (See Fig. 16, A as indicated.)

B.

AC/HP SIZE – Select system size installed

The factory setting for air conditioner or heat pump size is the largest unit meant for application with the model of fan coil purchased. Installer
needs to select air conditioner or heat pump size to ensure that airflow delivered falls within proper range for the size unit installed. This applies
to all operational modes with the exception of electric heat modes. (See Fig. 16, B as indicated.)

C.

SYSTEM TYPE – Select system type installed AC or HP

The type of system must be selected:

1. AC — Air conditioner

2. HP-COMFORT — Provides approximately 315 CFM per ton for higher normal heating air delivery temperature. Provides approximately

350 CFM per ton cooling airflow for good humidity removal.

3. HP-EFF — Provides same airflow for heating and cooling modes; approximately 350 CFM per ton.

The factory setting is AC. (See Fig. 16, C as indicated.)

D.

AC/HP CFM ADJUST – Select Medium, Low, or High airflow

To provide airflow at rates described above, the AC/HP ADJUST select is factory set to the nominal (nom) tap. The adjust selections HI/LO will
regulate airflow supplied for all operational modes, except non-heat pump heating modes, +15 percent and -10 percent respectively. The adjust
selection options are provided to adjust airflow supplied to meet individual installation needs for such things as noise, comfort, and humidity
removal. (See Fig. 16, D as indicated.)

E.

ON/OFF DELAY – Select desired time delay profile

Four motor operation delay profiles are provided to customize and enhance system operation. (See Fig. 16, E as indicated)

Selection options are:

1. The standard 90 sec off delay (Factory setting).

2. No delay option used for servicing unit or when a thermostat is utilized to perform delay functions.

Fig. 15—Condensate Trap and Unit

A97560

FILTER
ACCESS
PANEL

PRIMARY TRAP

(FACTORY-SUPPLIED

ON SOME UNITS)

SECONDARY DRAIN
(FIELD-SUPPLIED
TRAP REQUIRED)

—12—

Summary of Contents for FK4C

Page 1: ...ructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most se...

Page 2: ...LEFT APPLICATIONS FRONT VIEW SHOWN WITH A COIL DETAILS CONNECTION LOCATIONS FOR UPFLOW OR HORIZ APPLICATIONS 3 1 16 4 11 16 10 3 4 9 1 2 LIQUID LINE CONNECTION SUCTION LINE CONNECTION ACCESS PANEL CON...

Page 3: ...P 4 PLACES 1 TYP 2 PLACES 2 7 8 2 3 16 TYP 2 PLACES SECONDARY DRAIN PRIMARY DRAIN 5 16 TYP 1 5 16 3 1 4 1 TYP 2 PLACES SECONDARY DRAIN PRIMARY DRAIN HORIZ RIGHT FIELD CONVERTED 1 5 16 1 11 16 2 1 2 TY...

Page 4: ...and width of unit A Upflow Installation If return air is to be ducted install duct flush with floor Set unit on floor over opening Only use return air opening provided All return air must pass throug...

Page 5: ...rommets after brazing E Horizontal Right Conversion of Units With A Coil To convert units for horizontal right installations 1 Remove blower and coil access panels See Fig 8 2 Remove metal clip securi...

Page 6: ...access and fitting panels aligning holes with tubing connections and condensate pan connections Be sure to reinstall metal clip between fitting panel and vertical condensate pan Fig 6 Slope Coil in Ho...

Page 7: ...tested by UL Standard 181 for Class 1 air ducts PROCEDURE 4 ELECTRICAL CONNECTIONS A Line Voltage Connections Units with 15 and 20 kw heaters are factory wired for dual circuit operation When single...

Page 8: ...to 3 stage operation Connect low voltage leads to thermostat and outdoor unit See Fig 9 and 10 C Intelligent Heat Option Intelligent Heat staging of the electric heat package is possible when the FK4C...

Page 9: ...fault should occur The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes Failure to follow this warning could result in an electrical s...

Page 10: ...tat closes circuit R to W W1 or W2 The fan coil delivers the selected electric heat airflow G Heat Pump Heating Mode Single speed or 2 Speed High 1 Thermostat closes circuits R to G and R to Y Y2 The...

Page 11: ...pan should be installed underneath the entire unit and a secondary condensate line with appropriate trap should be run from the unit into the pan Any condensate in this external condensate pan should...

Page 12: ...AC HP SIZE Select system size installed The factory setting for air conditioner or heat pump size is the largest unit meant for application with the model of fan coil purchased Installer needs to sel...

Page 13: ...gnal is present whenever the G thermostat signal is present heat pump heating cooling and continuous blower modes When the FK4C Fan Coil is installed with an electronic air cleaner use EAC relay kit P...

Page 14: ...and wire in a standard humidistat See Fig 21 E Dehumidify and Super Dehumidify Capabilities This model fan coil is capable of responding to a signal from indoor system control thermostat thermidistat...

Page 15: ...ensate drain each cooling season for cleanliness Clean as necessary An inspection port is provided on all A coil delta plates Remove plastic plug to inspect 3 Inspect blower motor and wheel for cleanl...

Page 16: ...ay to increase your knowledge of the equipment discussed in this manual including Unit Familiarization Maintenance Installation Overview Operating Sequence A large selection of product theory and skil...

Reviews: