10
Step 2 — Rig the Machine —
The 23XRV machine
can be rigged as an entire assembly. Large interconnecting pip-
ing has flanged connections that allow the compressor, cooler,
and condenser sections to be separated and rigged individually.
In addition, the VFD can be removed and rigged separately.
RIG MACHINE ASSEMBLY — See rigging instructions on
label attached to machine. Also refer to rigging guide (Fig. 13),
physical data in Fig. 13 and 14, and Tables 3-19.
Lift machine
only from the points indicated in rigging guide.
Each lifting ca-
ble or chain must be capable of supporting the entire weight of
the machine.
Contractors are not authorized to disassemble any part of
the chiller without Carrier's supervision. Any request otherwise
must be in writing from the Carrier Service Manager.
NOTE: Carrier suggests that a structural engineer be consulted
if transmission of vibrations from mechanical equipment is of
concern.
7
6
4
2
1
3
5
8
9
19
1
8
17
16
15
14
11
10
12 1
3
20
Fig. 8 — Typical 23XRV Installation — Sensor Locations (Units with R Compressor)
1 — Condenser Pressure
2 — Evaporator Pressure
3 — Compressor Discharge Temperature
4 — Compressor Discharge Pressure
5 — Compressor Discharge High Pressure Switch
6 — Compressor Motor Winding Temperature (Hidden)
7 — Evaporator Refrigerant Liquid Temperature (Hidden)
8 — Condenser Liquid Temperature
9 — Condenser Liquid Flow (Optional)
10 — Inductor Temperature Switch (Inside VFD Enclosure)
11 — VFD Rectifier Temperature (Inside Power Module)
12 — VFD Cold Plate Temperature (Inside VFD Enclosure)
13 — VFD Inverter Temperature (Inside Power Module)
14 — Humidity Sensor (Inside VFD Enclosure)
15 — Oil Pressure Leaving Filter (Hidden)
16 — Oil Sump Pressure (Hidden)
17 — Oil Sump Temperature (Hidden)
18 — Vaporizer Temperature
19 — Evaporator Liquid Temperature
20 — Evaporator Liquid Flow (Optional)
a23-1551
a23-1552
Fig. 9 — VFD Nameplate
a23-1553
WARNING
Lifting machine from points other than those specified may
result in serious damage to the unit and personal injury.
Rigging equipment and procedures must be adequate for
machine weight. See Fig. 13 for machine weights.
NOTE: These weights are broken down into component
sections for use when installing the unit in sections. For the
complete machine weight, add all component sections and
refrigerant charge together. See Tables 8-19 for machine
component weights.
Summary of Contents for EVERGREEN 23XRV
Page 53: ...53 Fig 60 Typical Field Wiring Schematic LF 2 VFD Shown NOTE See Notes for Fig 60 on page 56 ...
Page 54: ...54 Fig 60 Typical Field Wiring Schematic LF 2 VFD Shown cont a23 1585 ...
Page 55: ...55 Fig 60 Typical Field Wiring Schematic LF 2 VFD Shown cont a23 1586 ...
Page 60: ...60 Fig 63 23XRV Controls Schematic LF 2 ...
Page 64: ...64 FROM PREVIOUS PAGE Fig 67 23XRV Controls Schematic Rockwell Standard Tier VFD Shown cont ...