54
Table 7A — Electrical Data Reduced Ambient 115 F Data
LEGEND
*Wye-delta start is standard. Across-the-line start is not available.
NOTES:
1. Main power must be supplied from a field-supplied fused electrical service with a
(factory or field-installed) disconnect located in sight from the unit.
2. Cooler heater, oil heater, and control circuit power must be supplied from a separate
source through a field-supplied disconnect. The control circuit power transformer acces-
sory may be applied to power from the main unit power supply.
3. Maximum incoming wire size for each terminal block is 500 kcmil.
4. Maximum allowable supply voltage phase imbalance is voltage 2%.
5. Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percent voltage imbalance.
Percent Voltage Imbalance
Example: Supply voltage is 240-3-60.
AB = 243 v
BC = 236 v
AC = 238 v
Determine maximum deviation from average voltage:
(AB) 243 – 239 = 4 v
(BC) 239 – 236 = 3 v
(AC) 239 – 238 = 1 v
Maximum deviation is 4 v. Determine percent voltage imbalance:
This amount of phase imbalance is satisfactory as it is below the maximum allow-
able 2%.
UNIT
30GXN,R
UNIT VOLTAGE
POWER
SUPPLY
QTY. REQD
STANDARD CONDENSER FAN
CONTROL CIRCUIT
V-Hz
(3 Ph)
Supplied
# Power Supply
Conductors
MCA
MOCP
ICF
Rec Fuse Size
V-Hz
(Single Ph)
MCA and MOCP
Min
Max
XL
WD
XL
WD
080
208/230-60
187
253
1
3
356.5
500
*
527.9
*
400
115-60
30
230-60
207
253
1
3
324.5
450
*
515.1
*
400
115-60
30
460-60
414
506
1
3
160.9
225
652.6
255.6
200
200
115-60
30
575-60
518
633
1
3
129.0
175
542.4
205.4
150
150
115-60
30
380-60
342
418
1
3
195.6
250
729.3
291.3
225
225
230-60
15
083
208/230-60
187
253
1
3
353.7
500
*
534.5
*
400
115-60
30
230-60
207
253
1
3
324.4
450
*
522.9
*
400
115-60
30
460-60
414
506
1
3
160.1
225
655.8
258.8
200
200
115-60
30
575-60
518
633
1
3
128.0
175
544.6
207.6
150
150
115-60
30
380-60
342
418
1
3
193.7
250
732.7
294.7
225
225
230-60
15
090
208/230-60
187
253
1
6
406.1
600
*
593.9
*
500
115-60
30
230-60
207
253
1
3
369.3
500
*
581.1
*
450
115-60
30
460-60
414
506
1
3
183.2
250
757.6
288.6
225
225
115-60
30
575-60
518
633
1
3
148.1
200
606.4
231.4
175
175
115-60
30
380-60
342
418
1
3
222.9
300
845.3
327.3
250
250
230-60
15
093
208/230-60
187
253
1
6
389.1
500
*
600.5
*
450
115-60
30
230-60
207
253
1
3
356.4
500
*
588.9
*
400
115-60
30
460-60
414
506
1
3
176.1
250
760.8
291.8
200
200
115-60
30
575-60
518
633
1
3
140.8
200
608.6
233.6
175
175
115-60
30
380-60
342
418
1
3
213.0
300
848.7
330.7
250
250
230-60
15
106
208/230-60
187
253
1
6
482.0
700
*
693.9
*
600
115-60
30
230-60
207
253
1
6
438.9
600
*
681.1
*
500
115-60
30
460-60
414
506
1
3
217.3
300
899.4
338.4
250
250
115-60
30
575-60
518
633
1
3
174.4
250
719.8
270.8
200
200
115-60
30
380-60
342
418
1
3
264.9
350
1002.5
382.5
300
300
230-60
15
108
208/230-60
187
253
1
6
445.8
600
*
705.2
*
500
115-60
30
230-60
207
253
1
6
407.7
500
*
691.7
*
500
115-60
30
460-60
414
506
1
3
201.7
250
904.7
343.7
250
250
115-60
30
575-60
518
633
1
3
161.4
225
723.8
274.8
200
200
115-60
30
380-60
342
418
1
3
244.1
350
1008.5
388.5
300
300
230-60
15
114
208/230-60
187
253
1
6
507.7
700
*
719.6
*
600
115-60
30
230-60
207
253
1
6
462.0
600
*
704.2
*
600
115-60
30
460-60
414
506
1
3
228.9
300
911.0
350.0
300
300
115-60
30
575-60
518
633
1
3
183.4
250
728.8
279.8
225
225
115-60
30
380-60
342
418
1
3
279.0
400
1016.6
396.6
350
350
230-60
15
118
208/230-60
187
253
1
6
486.0
600
*
745.5
*
600
115-60
30
230-60
207
253
1
6
445.6
600
*
729.6
*
500
115-60
30
460-60
414
506
1
3
219.9
300
922.9
361.9
250
250
115-60
30
575-60
518
633
1
3
175.9
250
738.3
289.3
200
200
115-60
30
380-60
342
418
1
3
266.1
350
1030.5
410.5
300
300
230-60
15
125
208/230-60
187
253
1
6
576.6
800
*
814.6
*
700
115-60
30
230-60
207
253
1
6
525.4
700
*
795.4
*
600
115-60
30
460-60
414
506
1
3
260.6
350
1025.1
396.1
300
300
115-60
30
575-60
518
633
1
3
207.8
300
820.3
317.3
250
250
115-60
30
380-60
342
418
1
3
316.1
450
1145.6
449.6
400
400
230-60
15
ICF
—
Maximum Instantaneous Current Flow
MCA
—
Minimum Circuit Ampacity (for wire sizing)
MOCP
—
Maximum Overcurrent Protection
Rec Fuse Size —
Recommended Dual-Element Fuse Amps (150% of largest
compressor rated load amps [RLA] plus 100% of remaining
compressor RLAs and sum of condenser fan full load amps
[FLAs]. Choose next largest standard fuse size.)
WD
—
Wye-Delta Start
XL
—
Across-the-Line Start
= 100 x
max voltage deviation from average voltage
average voltage
Average voltage =
243 + 236 + 238
3
=
239 v
% Voltage Imbalance
= 100 x
4
239
= 1.7%
IMPORTANT: Contact your local electric utility company immediately if the supply
voltage phase imbalance is more than 2%.
Summary of Contents for ECOLOGIC 30GXN
Page 3: ...3 Fig 1 Dimensions 30GXN R080 090 Cast iron Steel ...
Page 4: ...4 Fig 2 Dimensions 30GXN R083 093 106 108 114 125 135 Cast iron Steel ...
Page 5: ...5 Fig 3 Dimensions 30GXN R118 128 138 150 160 Cast iron Steel ...
Page 6: ...6 Fig 4 Dimensions 30GXN R153 174 Cast iron Steel ...
Page 7: ...7 Fig 5 Dimensions 30GXN R163 178 Cast iron Steel ...
Page 8: ...8 Fig 6 Dimensions 30GXN R204 225 Cast iron Steel ...
Page 9: ...9 Fig 7 Dimensions 30GXN R208 228 Cast iron Steel ...
Page 10: ...10 Fig 8 Dimensions 30GXN R249 264 Cast iron Steel ...
Page 11: ...11 Fig 9 Dimensions 30GXN R253 268 Cast iron Steel ...
Page 12: ...12 Fig 10 Dimensions 30GXN R281 301 325 350 Cast iron Steel ...
Page 13: ...13 Fig 11 Dimensions 30GXN R283 ...
Page 14: ...14 Fig 12 Dimensions 30GXN R303 ...
Page 15: ...15 Fig 13 Dimensions 30GXN R328 ...
Page 16: ...16 Fig 14 Dimensions 30GXN R353 ...
Page 17: ...17 Fig 15 Dimensions 30GXN R370 ...
Page 18: ...18 Fig 16 Dimensions 30GXN R373 ...
Page 19: ...19 Fig 17 Dimensions 30GXN R390 ...
Page 20: ...20 Fig 18 Dimensions 30GXN R393 418 ...
Page 21: ...21 Fig 19 Dimensions 30GXN R415 ...
Page 22: ...22 Fig 20 Dimensions 30GXN R450 ...
Page 23: ...23 Fig 21 Dimensions 30GXN R453 ...
Page 24: ...24 Fig 22 Dimensions 30GXN R475 ...
Page 25: ...25 Fig 23 Dimensions 30GXN R478 ...
Page 26: ...26 Fig 24 Dimensions 30GXN R500 525 ...
Page 27: ...27 Fig 25 Dimensions 30GXN R503 528 ...
Page 73: ......