COMMUNICATIONS WIRING
LEGEND
A
—
Alarm
CWP
—
Chilled Water Pump
CWPI
—
Chilled Water Pump Interlock
EMM
—
Energy Management Module
FIOP
—
Factory-Installed Option
LWT
—
Leaving Water Thermistor
OAT
—
Outdoor-Air Thermistor
SPT
—
Space Temperature Thermistor
TB
—
Terminal Block
Field Control Wiring
Fig. 38 — Field Control Wiring
NOTES:
1. Power for control circuit should be supplied from a separate source through a field-
supplied disconnect (see Tables 7A-7E for maximum current protection requirements).
Connect control circuit power to terminals 1 and 2 of TB4. Control circuit conductors for
all units must be copper only.
2. Terminals 13 and 14 of TB5 are for field external connection for remote on-off. The
contacts must be capable of handling a 24-vac load up to 50 mA. For Dual Chiller installa-
tions, remote on-off contacts should be supplied to both modules.
3. Terminals 1 and 2 of TB5 are for Chilled Water Pump Interlock (CWPI) functions. If
added, remove jumper. The contacts must be rated for dry circuit application capable of
handling a 24-vac load up to 50 mA load. Chilled Water Flow Switch (CWFS) is factory
installed.
4. Terminals 10 and 12 of TB5 are for control of chilled water pump starter. The maximum
load allowed for the chilled water pump relay is 75-va sealed, 360-va inrush at 115 or
230 volt depending on control circuit voltage. Field power supply is not required.
5. Terminals 11 and 12 of TB5 are for alarm relay. The maximum load allowed for the alarm
relay is 75-va sealed, 360-va inrush at 115 or 230 volt depending on control circuit volt-
age. Field power supply is not required.
6. Make appropriate connections to TB6 as shown for energy management board options.
The contacts for Demand Limit and Ice Done options must be capable of handling a
24-vac load up to 50 mA.
7. All 30GXN,R duplex chillers have the EMM option mounted in the master chiller (B) only.
All remote chiller control interfaces are required on the master (B) chiller only.
Summary of Contents for ECOLOGIC 30GXN
Page 3: ...3 Fig 1 Dimensions 30GXN R080 090 Cast iron Steel ...
Page 4: ...4 Fig 2 Dimensions 30GXN R083 093 106 108 114 125 135 Cast iron Steel ...
Page 5: ...5 Fig 3 Dimensions 30GXN R118 128 138 150 160 Cast iron Steel ...
Page 6: ...6 Fig 4 Dimensions 30GXN R153 174 Cast iron Steel ...
Page 7: ...7 Fig 5 Dimensions 30GXN R163 178 Cast iron Steel ...
Page 8: ...8 Fig 6 Dimensions 30GXN R204 225 Cast iron Steel ...
Page 9: ...9 Fig 7 Dimensions 30GXN R208 228 Cast iron Steel ...
Page 10: ...10 Fig 8 Dimensions 30GXN R249 264 Cast iron Steel ...
Page 11: ...11 Fig 9 Dimensions 30GXN R253 268 Cast iron Steel ...
Page 12: ...12 Fig 10 Dimensions 30GXN R281 301 325 350 Cast iron Steel ...
Page 13: ...13 Fig 11 Dimensions 30GXN R283 ...
Page 14: ...14 Fig 12 Dimensions 30GXN R303 ...
Page 15: ...15 Fig 13 Dimensions 30GXN R328 ...
Page 16: ...16 Fig 14 Dimensions 30GXN R353 ...
Page 17: ...17 Fig 15 Dimensions 30GXN R370 ...
Page 18: ...18 Fig 16 Dimensions 30GXN R373 ...
Page 19: ...19 Fig 17 Dimensions 30GXN R390 ...
Page 20: ...20 Fig 18 Dimensions 30GXN R393 418 ...
Page 21: ...21 Fig 19 Dimensions 30GXN R415 ...
Page 22: ...22 Fig 20 Dimensions 30GXN R450 ...
Page 23: ...23 Fig 21 Dimensions 30GXN R453 ...
Page 24: ...24 Fig 22 Dimensions 30GXN R475 ...
Page 25: ...25 Fig 23 Dimensions 30GXN R478 ...
Page 26: ...26 Fig 24 Dimensions 30GXN R500 525 ...
Page 27: ...27 Fig 25 Dimensions 30GXN R503 528 ...
Page 73: ......