background image

7

Table 3 — Daily Schedule Planner

NOTE: The cooling temperature set point must be higher than the heating temperature set point. (The temperature difference may be changed in
the advanced setup configuration.)

If YES was selected, the schedule will be copied to the
next day. The schedule copy may be repeated until Sun-
day is reached. The Sunday schedule cannot be copied to
Monday.

12. After all the times and set points for each day have been

entered, press and hold the Mode and UP ARROW but-
tons to exit Programming mode.

NOTE: The thermostat will continue to follow the schedule
until a new one is entered.

If only one occupied schedule is selected, the Occupied 2

and 3 schedules are skipped. If the start time is set later in the
day than the stop time, the program will run from midnight of
that day to the stop time and then from the start time to mid-
night. If the same start and stop times are programmed for an
occupancy schedule, the thermostat will be in Occupied mode
for 24 hours. If one occupied period starts or stops within an-
other occupied period, the lower numbered schedule has priori-
ty. For example, if schedule Occupied 3 is running for 24 hours
and Occupied 2 schedule comes on from 1 to 3 PM, the set
points from Occupied 2 are in effect from 1 to 3 PM.
OVERRIDING THE SCHEDULE — The schedule can be
overridden by pressing the UP or DOWN ARROW buttons to
change the desired temperature. The thermostat will use the
new set point until the next scheduled time period starts.

Factory Defaults —

If the thermostat needs to be reset to

factory default settings, perform the following procedure:

1. Hold down the Mode button and press the DOWN

ARROW button simultaneously for 5 seconds. All of the
icons on the display screen will appear.

2. Press and hold the Override button until Fd (factory de-

faults) appears on the screen.

3. Press the Mode button twice to return to normal display.

NOTE: The occupied and unoccupied schedules will be reset.
The schedule will need to be re-entered.

Calibrate Sensor —

Every thermostat is factory cali-

brated. Under normal circumstances there will never be a need
to re-calibrate the thermostat. If re-calibration must be done,
perform the following procedure:

1. Hold down the Mode and DOWN ARROW buttons for

5 seconds. All of the icons on the display screen will
appear. Release the buttons.

2. Press the Mode button. The current temperature will be

displayed.

3. Use an accurate thermometer to measure room tempera-

ture. Press the UP or DOWN ARROW buttons until the
flashing number equals room temperature.

4. Press the Mode button again to return to normal

operation.

Check Thermostat Operation —

To check thermo-

stat operation, perform the following procedure:

1. Press the Mode button repeatedly until the Heat icon ap-

pears on the display. The thermostat is now in Heating
mode.

2. Press the UP ARROW button until the heating set point is

10 F (6 C) higher than the current room temperature.
Heating and fan should be energized.

3. Press the Mode button repeatedly until the Cool icon ap-

pears on the display. The thermostat is now in Cooling
mode.

4. Press the DOWN ARROW button until the cooling set

point is 10 F lower than the current room temperature.
Cooling and fan should be energized.

5. If heating, cooling, or fan operation do not energize,

check wiring and consult Table 4.

Final Checklist

1. Put away tools and instruments. Clean up debris and

packaging.

2. Review Owner’s Guide with occupant or owner.
3. Leave the manuals with owner.

OPERATION

The Mode button selects the operating mode of the thermo-

stat. If OFF is selected, the thermostat will not enter Heating or
Cooling mode. If HEAT is selected, the thermostat will only
enter Heating mode (if the room temperature is below the heat-
ing set point). If COOL is selected, the thermostat will only en-
ter Cooling mode (if the room temperature is above the cooling
set point). If AUTO is selected, the thermostat will enter Heat-
ing or Cooling mode based on the room temperature and the
heating and cooling set points. If PROGRAM ON is selected,
the stored schedule is enabled and the thermostat will follow
the Occupied and Unoccupied schedules stored in its memory.

Auto-Changeover —

When the thermostat mode is set

to AUTO, the thermostat will provide automatic changeover
from Heating to Cooling mode and Cooling to Heating mode
when required. The thermostat will automatically switch to
maintain the desired temperature setting. The thermostat does
not need to be manually changed from heating to cooling or
cooling to heating operation.

Two-Stage Operation —

The second stage of heat or

cool is turned on when the first stage has been on for a mini-
mum of 2 minutes and the temperature differential from the set
point is equal to or greater than the set point plus the deadband
plus 2 degrees.

Clock Backup —

In the event of a power loss, the ther-

mostat will keep time for a minimum of 48 hours without ex-
ternal power or batteries.

DAY

OF THE

WEEK

SCHEDULE

Occupied 1

Occupied 2

Occupied 3

Unoccupied

Start / Stop / Heat / Cool

Start / Stop / Heat / Cool

Start / Stop / Heat / Cool

Heat / Cool

Monday

/

/

/

/

/

/

/

/

/

/

Tuesday

/

/

/

/

/

/

/

/

/

/

Wednesday

/

/

/

/

/

/

/

/

/

/

Thursday

/

/

/

/

/

/

/

/

/

/

Friday

/

/

/

/

/

/

/

/

/

/

Saturday

/

/

/

/

/

/

/

/

/

/

Sunday

/

/

/

/

/

/

/

/

/

/

Summary of Contents for DEBONAIR 33CS

Page 1: ...most serious hazards which will result in severe personal injury or death WARNING signifies a haz ard which could result in personal injury or death CAUTION is used to identify unsafe practices which would result in minor personal injury or property damage GENERAL The commercial 7 day programmable thermostats are wall mounted low voltage thermostats which maintain room temperature by controlling t...

Page 2: ... is a hazardous waste and must be disposed of properly 3 Install 2 x 4 in junction box field supplied in wall See Fig 1 4 Route thermostat wires through back of junction box Re move outer sheath from wires for added flexibility Standard solid or multi conductor thermostat wire should be used from the thermostat to the unit Size and length considerations are as follows for a maximum distance from u...

Page 3: ...o prevent adjacent wires from shorting together Match and connect wires to terminals on the thermostat See Fig 2 and Table 1 5 Attach thermostat to wall On paneling installations see Fig 4 a Push thermostat into hole in wall Make sure tabs on paneling match up with mounting holes on thermostat b Using two 11 2 in self tapping screws attach thermostat to wall Make sure thermostat cover is flush aga...

Page 4: ...ing UP ARROW or DOWN AR ROW To ensure the schedules are properly followed make sure that AM or PM is correct for the time chosen When the correct time is shown press the Mode button to modify the day of the week The current day will blink on and off Press the UP ARROW and DOWN ARROW buttons until the correct day is shown Press the and hold the Mode and Override buttons at the same time again to ex...

Page 5: ...an application The soft start staggers the start up times of the units in the event of power loss and restart Each unit should be assigned a unit ID number The 30 second delay time is multiplied the unit ID number to get the total soft start delay time for each unit For example if the unit ID number is 10 set the Soft Start function to 10 the start up delay time is 30 seconds x 10 300 seconds 5 mi...

Page 6: ...wer the cooling set point until the desired tem perature is shown The range of acceptable values is 35 to 99 F 1 to 37 C or OF no unoccupied cooling To configure the Unoccupied Cooling set point to OF press the UP ARROW button until 99 F is displayed Press the UP ARROW button again to display OF Press the Mode button to continue 5 The heating set point for Unoccupied will be displayed Use the UP A...

Page 7: ...Press the UP or DOWN ARROW buttons until the flashing number equals room temperature 4 Press the Mode button again to return to normal operation Check Thermostat Operation To check thermo stat operation perform the following procedure 1 Press the Mode button repeatedly until the Heat icon ap pears on the display The thermostat is now in Heating mode 2 Press the UP ARROW button until the heating se...

Page 8: ...ore the remaining config ured days have passed press the Mode and UP ARROW but tons simultaneously to enter into Programming mode Press the Override button to enter into Holiday Programming mode Press the DOWN ARROW to set the number of days to zero Holiday mode will be disabled Remote Temperature Sensor 33CS250 FS Only A remote temperature sensor is available to read the temperature from a space ...

Page 9: ...check the unit wiring diagram See Fig 10 SOFT START When multiple thermostats are controlled by the same external device a Soft Start option can be used to stagger the turn on times of the HVAC equipment This feature may cause a delay in operation after entering Unoccupied mode 10 Watt Resistor A 10 watt 270 ohm resistor is pro vided with the thermostat This resistor should only be used in applica...

Page 10: ...ac is not present replace the thermostat When using 4 wires R G W Y the cooling equipment tries repeatedly to turn on but cannot At times the display dims or disappears There is not enough power available Connect a 270 ohm 10 watt power resistor supplied with thermostat at the air conditioning equipment between terminals W and C non heat pump applications only When using 4 wires R G W Y the heatin...

Page 11: ......

Page 12: ...inue or change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 533 352 Printed in U S A Form 33CS 35SI Pg 12 105 9 00 Replaces New Book 1 4 Tab 11a 13a Copyright 2000 Carrier Corporation ...

Reviews: