background image

5

FAN CONFIGURATION (Step 3) — The fan configuration
can be set to On or Auto. When the configuration is set to On,
the fan will run continuously during the occupied schedule and
all other modes except OFF. The fan will be off during the un-
occupied schedule except during heating or cooling operation.

If Auto is selected, the fan will run only during heating or

cooling operation. The default is Auto.
HEAT PUMP CONFIGURATION (Steps 4 and 5) — To set
the thermostat for heat pump operation, Advanced Setup
Step 4 must be configured to ON. Use the UP and DOWN AR-
ROW buttons to configure the step. The default is OFF. Press
the mode button to continue to Step 5. Step 5 is used to set the
reversing valve polarity for the heat pump. The variable can be
set to either ‘‘B’’ or ‘‘O.’’ Set the reversing valve polarity to the
correct value depending on the application. The default is ‘‘O.’’
NOTE: Step 5 will appear only if Step 4 is set to ON. Step 6
will appear only if Step 4 is set to OFF.
NOTE: On some commercial heat pump units, the Heat Pump
Configuration option must be set to OFF. Refer to the installa-
tion instructions for the heat pump unit to determine how the
thermostat should be configured.
ELECTRIC HEAT CONFIGURATION (Step 6) — Step

6

is used to configure the thermostat for electric heat. The vari-
able can be configured ON or OFF. The default is OFF.
NOTE: Step 6 will appear only if Step 4 is set to OFF.
DEADBAND (Step 7) — The deadband is the difference in
temperature above the cooling set point or below the heating
set point that the thermostat will wait before turning on the first
stage of heating or cooling. For example, if the cooling set
point is 82 F (28 C) and the deadband is 2 degrees, the first
stage of cooling will not be energized until the temperature
reaches 84 F (30 C). The range of values is 1 to 6 degrees. The
default is 2 degrees.
SET POINT MINIMUM DIFFERENCE (Step 8) — The min-
imum difference between heating and cooling set points can be
user-configured. The range is from 0 to 6 degrees. The default
is 2 degrees. The minimum difference is enforced during
Auto-changeover and Program On operation.
CYCLES PER HOUR LIMIT (Step 9) — The number of
times that heating or cooling can be energized per hour can be
configured. Set the variable to ‘‘d’’ for no limit. Set the variable
to ‘‘d1’’ to disable the 5-minute compressor lockout. The vari-
able can also be set from 2 to 6 cycles per hour. The default is 6
cycles per hour.

PRE-OCCUPANCY

PURGE

TIMER

(Step

10

33CS250-FS Only) — The preoccupancy purge allows fresh
outside air to be brought into the space before the Occupied 1
time period. The timer limits the amount of time that the purge
can operate. The timer can be set from 0 to 3 hours with
15-minute intervals. The default is 0 hours (disabled).
BACKLIGHT DISPLAY (Step 11) — The display backlight
can be set to ON (always on) or OFF (turn off 8 seconds after
usage). The default is ON.
SERVICE FILTER (Steps 12 and 13) — Step 12 allows the
user to reset the Service Filter counter to zero and remove the
‘‘SERVICE FILTER’’ icon (if displayed on the thermostat
screen). Press the Override button while in Setup Step 12 and
the counter is reset to zero. Press the Mode button to adjust the
number of hours the blower will run before the ‘‘SERVICE

FILTER’’ icon is displayed. The range is 0 to 1950 hours. Set
the variable to 0 to disable this function. The default is
500 hours.
SOFT START (Step 14 — 33CS250-FS Only) — The

soft

start is used when multiple units are used in an application. The
soft start staggers the start-up times of the units in the event of
power loss and restart. Each unit should be assigned a unit ID
number. The 30-second delay time is multiplied the unit ID
number to get the total soft start delay time for each unit. For
example, if the unit ID number is 10, set the Soft Start function
to 10, the start-up delay time is 30 seconds x 10 = 300 seconds
(5 minutes). The range is 0 to 99 (ID numbers). A value of 0
disables the function. The default is 0 (ID number).
FAHRENHEIT/CELSIUS OPERATION (Step 15) — The
thermostat can be set to operate in Fahrenheit or Celsius de-
grees. Set the variable to ‘‘F’’ for Fahrenheit operation. Set the
variable to ‘‘C’’ for Celsius operation.
SENSOR TYPE CONFIGURATION (Step 16 — 33CS250-
FS Only) — The sensor type configuration can be set to YES
or NO. If it is set to NO, any sensor wired to the RS and RS+5
terminals will be automatically detected and used as a remote
temperature sensor (thermostat controls to sensor temperature
reading). If the sensor type configuration is set to YES, any
sensor wired to the RS and RS+5 terminals will be used as an
outside or duct sensor (thermostat will not control to sensor
temperature reading). The default is NO.
SECURITY LEVEL (Steps 17 to 19) — The Security Level
limits the actions that the user can perform at the thermostat.
There are 4 security levels. When the security level is set to
‘‘0,’’ no security will be in effect. When the security level is set
to ‘‘1,’’ the set point range is limited by the settings of Steps 18
and 19. When the security level is set to ‘‘2,’’ the set point
range is limited by the settings of Steps 18 and 19 and the Pro-
gram On thermostat operation mode is always in effect. When
the security level is set to ‘‘3,’’ the set point range is limited by
the settings of Steps 18 and 19, the Program On mode is always
in effect, and set point changes are prohibited. The default is 0.
NOTE: The Fan button is ignored when Security levels 2 or 3
are in effect.
Security Maximum Heat Set Point (Step 18) — If the Secu-
rity Level is not set to 0, the maximum heating set point will be
in effect. The user will not be allowed to set the heating set
point over the specified value. The range of values is 35 to 99 F
(1 to 37 C). The default is 80 F (27 C).
Security Minimum Cool Set Point (Step 19) — If the Securi-
ty Level is not set to 0, the minimum cooling set point will be
in effect. The user will not be allowed to set the cooling set
point below the specified value. The range of values is 35 to
99 F (1 to 37 C). The default is 65 F (18 C).

Install Accessories —

The following accessories can

be used with this thermostat:
• remote temperature sensor with override (33CSSEN-WB)
• remote temperature sensor (33CSSEN-01)
• Add-a-Wire™ accessory (33CSACC-AW)
• duct temperature sensor (33CSSEN-DS)
• Add-a-Subzone™ accessory (33CSACC-AZ)
• wireless remote sensor (33CSRFS-RC/RE)

Refer to the accessory installation instructions for each

accessory for more information.
REMOTE

TEMPERATURE

SENSOR

(33CS250-FS

Only) — A remote temperature sensor may be provided to
read the temperature from a space. If a remote temperature sen-
sor is connected, the thermostat will ignore the reading of its
internal sensor. When the thermostat is using a reading from a
remote sensor, the degree symbol above the temperature read-
ing will blink.

When installing a remote sensor, do not run the wires in the

same conduit as the HVAC equipment control wires, fire alarm

Damage to compressor could result if 5-minute compressor
lockout is disabled or compressor is allowed unlimited
cycles. Do not set thermostat Advanced Setup Step 9 to
‘‘d’’ or ‘‘dl’’ unless specifically recommended for the
application.

105

Summary of Contents for DEBONAIR 33CS

Page 1: ...most serious hazards which will result in severe personal injury or death WARNING signifies a haz ard which could result in personal injury or death CAUTION is used to identify unsafe practices which would result in minor personal injury or property damage GENERAL The commercial 7 day programmable thermostats are wall mounted low voltage thermostats which maintain room temperature by controlling t...

Page 2: ... is a hazardous waste and must be disposed of properly 3 Install 2 x 4 in junction box field supplied in wall See Fig 1 4 Route thermostat wires through back of junction box Re move outer sheath from wires for added flexibility Standard solid or multi conductor thermostat wire should be used from the thermostat to the unit Size and length considerations are as follows for a maximum distance from u...

Page 3: ...o prevent adjacent wires from shorting together Match and connect wires to terminals on the thermostat See Fig 2 and Table 1 5 Attach thermostat to wall On paneling installations see Fig 4 a Push thermostat into hole in wall Make sure tabs on paneling match up with mounting holes on thermostat b Using two 11 2 in self tapping screws attach thermostat to wall Make sure thermostat cover is flush aga...

Page 4: ...ing UP ARROW or DOWN AR ROW To ensure the schedules are properly followed make sure that AM or PM is correct for the time chosen When the correct time is shown press the Mode button to modify the day of the week The current day will blink on and off Press the UP ARROW and DOWN ARROW buttons until the correct day is shown Press the and hold the Mode and Override buttons at the same time again to ex...

Page 5: ...an application The soft start staggers the start up times of the units in the event of power loss and restart Each unit should be assigned a unit ID number The 30 second delay time is multiplied the unit ID number to get the total soft start delay time for each unit For example if the unit ID number is 10 set the Soft Start function to 10 the start up delay time is 30 seconds x 10 300 seconds 5 mi...

Page 6: ...wer the cooling set point until the desired tem perature is shown The range of acceptable values is 35 to 99 F 1 to 37 C or OF no unoccupied cooling To configure the Unoccupied Cooling set point to OF press the UP ARROW button until 99 F is displayed Press the UP ARROW button again to display OF Press the Mode button to continue 5 The heating set point for Unoccupied will be displayed Use the UP A...

Page 7: ...Press the UP or DOWN ARROW buttons until the flashing number equals room temperature 4 Press the Mode button again to return to normal operation Check Thermostat Operation To check thermo stat operation perform the following procedure 1 Press the Mode button repeatedly until the Heat icon ap pears on the display The thermostat is now in Heating mode 2 Press the UP ARROW button until the heating se...

Page 8: ...ore the remaining config ured days have passed press the Mode and UP ARROW but tons simultaneously to enter into Programming mode Press the Override button to enter into Holiday Programming mode Press the DOWN ARROW to set the number of days to zero Holiday mode will be disabled Remote Temperature Sensor 33CS250 FS Only A remote temperature sensor is available to read the temperature from a space ...

Page 9: ...check the unit wiring diagram See Fig 10 SOFT START When multiple thermostats are controlled by the same external device a Soft Start option can be used to stagger the turn on times of the HVAC equipment This feature may cause a delay in operation after entering Unoccupied mode 10 Watt Resistor A 10 watt 270 ohm resistor is pro vided with the thermostat This resistor should only be used in applica...

Page 10: ...ac is not present replace the thermostat When using 4 wires R G W Y the cooling equipment tries repeatedly to turn on but cannot At times the display dims or disappears There is not enough power available Connect a 270 ohm 10 watt power resistor supplied with thermostat at the air conditioning equipment between terminals W and C non heat pump applications only When using 4 wires R G W Y the heatin...

Page 11: ......

Page 12: ...inue or change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 533 352 Printed in U S A Form 33CS 35SI Pg 12 105 9 00 Replaces New Book 1 4 Tab 11a 13a Copyright 2000 Carrier Corporation ...

Reviews: