background image

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

PC 111

Catalog No. 534-80096

Printed in U.S.A.

Form 48/50HG-19SI

Pg 8

2-02

Replaces: 48/50HG-17SI

Book 1

1

4

4

Tab

1a 1b 6a 6b

Copyright 2002 Carrier Corporation

Standby, Alarm and Sensitivity Tests — 

The cov-

er of the smoke detector must be removed to perform these
tests.
STANDBY AND TROUBLE TEST
Standby 

— Look for presence of flashing green LED.

The LED should flash approximately every
10 seconds.

Trouble — If the detector LED does not flash, then the detec-

tor lacks power (check TB4), the detector board is
missing (replace), the cover has been missing or
not secured properly for more than 20 minutes
(secure cover properly), or the unit is defective
(return for repair).

Test —

The trouble condition can be caused intentionally
to verify correct operation of the system. Remove
the detector board to cause an alarm.

Cover
Tamper — If the cover is removed or not properly secured for

a period longer than 20 minutes, a trouble signal is
generated to indicate the cover is missing.

ALARM TESTS
Magnet Test

1. Place the painted surface of the magnet onto the TEST

locator on the bottom of the housing.

2. The red alarm LED on the detector should switch on.

Verify system control panel alarm status and control
panel execution of all intended auxiliary functions
(i.e., fan shutdown, damper control, etc.).

3. The detector must be reset by the front cover reset button.

SENSITIVITY TEST — After verification of alarm capabili-
ty, use a field-supplied voltmeter to check detector sensitivity.
The housing cover must be removed to perform this test. If
readings indicate that the detector head is outside of the accept-
able range that is printed on the label of the detector, the detec-
tor chamber requires cleaning.

Summary of Contents for CRSMKSUP001A00

Page 1: ...itioning equipment can be hazardous due to system pressure and electrical compo nents Only trained and qualified service personnel should install repair or service air conditioning equipment Untrained personnel can perform the basic maintenance functions of cleaning coils and filters and replacing filters All other operations should be performed by trained service per sonnel When working on air co...

Page 2: ...et 12 Slide sampling tube into bracket making sure that the sampling holes point down Pull the sampling tube so that it is flush with the smoke detector 13 Return to Electrical Compressor section and secure sam pling tube to smoke detector with two no 6 self tapping screws 14 Attach smoke detector to partition using two 8 18 3 4 in pan head screws 15 Return to side panel and insert tube end plug i...

Page 3: ...ING TERMINAL STRIP POWER BOARD COVER MOUNTING SCREWS FILTERS SAMPLING TUBE DETECTOR BOARD DETECTOR COVER PLASTIC SAMPLING TUBE PLASTIC SAMPLING TUBE SELF TAPPING SCREW SMOKE DETECTOR Fig 1 Smoke Detector Fig 2 Return Air Smoke Detector Location ...

Page 4: ...4 Fig 3 Return Air Smoke Detector Wiring SAMPLING TUBE SUPPORT BRACKET Fig 4 Sampling Tube Support Bracket ...

Page 5: ...ring the ComfortLink Controller below 23 Perform Standby Alarm and Sensitivity Tests on page 7 At a minimum the Magnet test should be per formed to verify smoke detector wiring 24 Turn off power to the unit 25 Replace smoke detector cover Do not overtighten screws 26 Reconnect the indoor fan plug and the limit switch wires if applicable 27 Close the indoor fan section door 28 Restore power to the ...

Page 6: ...UTE WIRES AS SHOWN SUPPLY SMOKE DETECTOR SUPPLY FAN VIEW FROM INSIDE UNIT USE 10 SCREWS PROVIDED TO ATTACH WIRE TIES Fig 5 Supply Smoke Detector Location and Wire Routing Fig 6 Supply Smoke Detector Wiring ...

Page 7: ...lace 5 Secure board with the two mounting screws 6 Re connect wiring to terminal block TROUBLESHOOTING Test and maintain unit smoke detectors as recommended in NFPA 72 Before conducting these tests notify the proper authorities that the smoke detection system will be temporarily out of service Disable the system under test to prevent unwant ed alarms Smoke Entry Tests AIRFLOW TEST The smoke detect...

Page 8: ...The trouble condition can be caused intentionally to verify correct operation of the system Remove the detector board to cause an alarm Cover Tamper If the cover is removed or not properly secured for a period longer than 20 minutes a trouble signal is generated to indicate the cover is missing ALARM TESTS Magnet Test 1 Place the painted surface of the magnet onto the TEST locator on the bottom of...

Reviews: