2

INSTALLATION

Check Package Contents — 

Remove accessory pack-

aging and inspect shipment for damage. If any damage is
found, file a claim with the shipping agent immediately. If any
item is missing or any part does not assemble properly, notify
your Carrier distributor. 

Tables 1A and B list the accessory package contents.

Figure 1 shows the smoke detector.

Table 1A — Accessory Package Contents — 

Return Air Smoke Detector (CRSMKDET001C00)

Table 1B — Accessory Package Contents — 

Supply Air Smoke Detector (CRSMKSUP001A00)

Return  Air  Smoke  Detector  Installation —

The return air smoke detector is to be installed in the predrilled
holes located above compressor B1 in the electrical/
compressor section (Fig. 2).

NOTE: For horizontal applications it is easiest to install the
smoke detector prior to making duct connections.

1. Open the hinged electrical/compressor access door and

secure.

2. Find the 2 plugs located above compressor B1, remove

and discard. Cut holes in the insulation located behind the
partition.

3. Remove cover from smoke detector. The screws will

remain captured in the cover.

4. Place foam gaskets over each sampling tube on smoke

detector. (See Fig. 1.)

5. Remove one knockout from top of smoke detector.
6. Insert stripped ends of wire harness through knockout and

wire to smoke detector as shown in Fig. 3.

7. Provide strain relief for wires by attaching wire tie to

ground screw located next to the knockout in the smoke
detector. Tighten the wire tie.

8. Slide smoke detector into holes in partition with the

terminal block to the right. Do not secure at this time.

9. Slide sampling tube into left-hand hole of smoke detector.

It might be necessary to tilt the smoke detector upwards
in order properly align the sampling tube.

10. Remove the unit side panel at the return end of the unit.

Save screws for use later.

11. Mount the sampling tube support bracket to the cross

member with two 

1

/

4

AB-14 

5

/

8

-in. screws as shown

in Fig. 4. Insert large snap bushing into hole in bracket.

12. Slide sampling tube into bracket, making sure that the

sampling holes point down. Pull the sampling tube so that
it is flush with the smoke detector.

13. Return to Electrical/Compressor section and secure sam-

pling tube to smoke detector with two no. 6 self-tapping
screws.

14. Attach smoke detector to partition using two, 8-18 

3

/

4

-in.

pan head screws.

15. Return to side panel and insert tube end plug into

sampling tube.

16. Replace the unit side panel.
17. Return to Electrical/Compressor section and insert

sampling tube filters into both sampling tube holders.
(See Fig. 1.)

18. Install the snap bushing in the center knockout under-

neath the control terminal strips located in the bottom
right-hand corner of the control box.

19. Feed wires through snap bushing and connect to appro-

priate terminals as shown in Fig. 3.

20. Restore power to the unit.
21. Configure  ComfortLink™ controller as specified in

Configuring the ComfortLink Controller on page 5.

22. Perform Standby, Alarm, and Sensitivity Tests on page 7.

At a minimum, the Magnet test should be performed to
verify smoke detector wiring.

23. Replace smoke detector cover.
24. Check for alarms. Correct any problems.

When installing the smoke detector in the unit, follow all
local codes. Damage to unit may result.

ITEM

QUANTITY

Smoke Detector with Cover

1

Sampling Tube (long)

1

Sampling Tube Filters

2

Test Magnet

1

Foam Gaskets

2

Screw, no. 6 Self Tapping

2

Tube End Plug (large)

1

Sampling Tube Support Bracket

1

Screw, 8-18 

3

/

4

-in. Pan Head

2

Screw, 

1

/

4

AB-14 

5

/

8

-in.

2

Small Snap Bushing

1

Large Snap Bushing

1

Harness Assembly (4-Wires, short)

1

Wire Tie, Screw Mounted

1

ITEM

QUANTITY

Smoke Detector with Cover

1

Sampling Tube (short)

1

Sampling Tube Filters

2

Test Magnet

1

Foam Gaskets

2

Tube End Plug (small)

1

Screw, 8-18 

3

/

4

-in. Pan Head

2

Small Snap Bushing

1

Harness Assembly (4-Wires, long)

1

Wire Tie, Screw Mounted

5

Wire Tie

1

Screw, no. 8 Self Tapping

1

Screw, no. 10

2

Prior to installation of this accessory, make sure all power
is disconnected to the unit and locked out. Failure to dis-
connect power supply prior to servicing may result in seri-
ous injury.

Do not overtighten the screws. Damage to smoke detector
may result.

Summary of Contents for CRSMKSUP001A00

Page 1: ...itioning equipment can be hazardous due to system pressure and electrical compo nents Only trained and qualified service personnel should install repair or service air conditioning equipment Untrained personnel can perform the basic maintenance functions of cleaning coils and filters and replacing filters All other operations should be performed by trained service per sonnel When working on air co...

Page 2: ...et 12 Slide sampling tube into bracket making sure that the sampling holes point down Pull the sampling tube so that it is flush with the smoke detector 13 Return to Electrical Compressor section and secure sam pling tube to smoke detector with two no 6 self tapping screws 14 Attach smoke detector to partition using two 8 18 3 4 in pan head screws 15 Return to side panel and insert tube end plug i...

Page 3: ...ING TERMINAL STRIP POWER BOARD COVER MOUNTING SCREWS FILTERS SAMPLING TUBE DETECTOR BOARD DETECTOR COVER PLASTIC SAMPLING TUBE PLASTIC SAMPLING TUBE SELF TAPPING SCREW SMOKE DETECTOR Fig 1 Smoke Detector Fig 2 Return Air Smoke Detector Location ...

Page 4: ...4 Fig 3 Return Air Smoke Detector Wiring SAMPLING TUBE SUPPORT BRACKET Fig 4 Sampling Tube Support Bracket ...

Page 5: ...ring the ComfortLink Controller below 23 Perform Standby Alarm and Sensitivity Tests on page 7 At a minimum the Magnet test should be per formed to verify smoke detector wiring 24 Turn off power to the unit 25 Replace smoke detector cover Do not overtighten screws 26 Reconnect the indoor fan plug and the limit switch wires if applicable 27 Close the indoor fan section door 28 Restore power to the ...

Page 6: ...UTE WIRES AS SHOWN SUPPLY SMOKE DETECTOR SUPPLY FAN VIEW FROM INSIDE UNIT USE 10 SCREWS PROVIDED TO ATTACH WIRE TIES Fig 5 Supply Smoke Detector Location and Wire Routing Fig 6 Supply Smoke Detector Wiring ...

Page 7: ...lace 5 Secure board with the two mounting screws 6 Re connect wiring to terminal block TROUBLESHOOTING Test and maintain unit smoke detectors as recommended in NFPA 72 Before conducting these tests notify the proper authorities that the smoke detection system will be temporarily out of service Disable the system under test to prevent unwant ed alarms Smoke Entry Tests AIRFLOW TEST The smoke detect...

Page 8: ...The trouble condition can be caused intentionally to verify correct operation of the system Remove the detector board to cause an alarm Cover Tamper If the cover is removed or not properly secured for a period longer than 20 minutes a trouble signal is generated to indicate the cover is missing ALARM TESTS Magnet Test 1 Place the painted surface of the magnet onto the TEST locator on the bottom of...