Table 2 — Standard Efficiency Packaged Rooftop Units,

Electrical Data and Electric Heater Package Usage

UNIT 50TJ

and 559F

NOMINAL VOLTAGE

(3 Ph, 60 Hz)

ACCESSORY HEATER

PART NO. CRHEATER

IFM

ACCESSORY

ELECTRIC HEAT

POWER SUPPLY

Hp

FLA

kW

MCA

MOCP

15 Tons

208/240

141A00

3.7

72/ 82

26/34

103/116

150/150

142A00

117/135

42/56

155/148

175/150

143A00

156/180

56/75

169/193

175/200

380

137A00

3

32

21.6

55

80

138A00

54

37.2

76

80

480

137A00

3.7

39

32

55

70

138A00

66

55

72

80

139A00

96

80

102

110

18 Tons

208/240

141A00

5

72/ 82

26/34

110/122

110/125

142A00

117/135

42/56

166/155

175/175

143A00

156/180

56/75

176/200

200/225

480

137A00

39

32

59

60

138A00

66

55

76

80

139A00

96

80

106

110

20 Tons

208/240

141A00

7.5

72/ 82

26/34

121/134

150/150

142A00

117/135

42/56

178/166

200/175

143A00

156/180

56/75

187/211

200/225

480

137A00

39

32

65

70

138A00

66

55

82

90

139A00

96

80

112

125

25 Tons

208/240

141A00

10

72/ 82

26/34

137/138

175/175

142A00

117/135

42/56

181/170

200/175

143A00

156/180

56/75

191/215

200/225

380

137A00

32

21.6

80

100

138A00

54

36

93

100

480

137A00

39

32

70

90

138A00

66

55

84

90

139A00

96

80

114

125

LEGEND

FLA

— Full Load Amps

IFM

— Indoor-Fan Motor

MCA

— Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection

NOTE: Control circuit is 24 v.

3

Summary of Contents for CRHEATER136A00

Page 1: ...included in package numbers CRHEATER137A00 and CRHEATER138A00 only and are only used on heat pump units INSTALLATION NOTE A minimum ductwork clearance of 1 in is re quired for the first 24 in of ductw...

Page 2: ...ROL BOX ACCESS PANEL NOTE Typical unit shown with electric heater access panel removed Fig 1 Typical Unit Physical Details 13 to 18 Ton Unit Shown Kit numbers CRHEATER142A00 and CRHEATER143A00 only Fi...

Page 3: ...110 122 110 125 142A00 117 135 42 56 166 155 175 175 143A00 156 180 56 75 176 200 200 225 480 137A00 39 32 59 60 138A00 66 55 76 80 139A00 96 80 106 110 20 Tons 208 240 141A00 7 5 72 82 26 34 121 134...

Page 4: ...75 195 215 225 225 380 137A00 32 21 6 71 90 138A00 54 36 89 90 480 137A00 39 32 66 70 138A00 66 55 83 90 139A00 96 80 113 125 LEGEND FLA Full Load Amps IFM Indoor Fan Motor MCA Minimum Circuit Amps M...

Page 5: ...ower supply wiring in accessory electric heat box and connect it to TB see Fig 8 and label diagram on the unit 5 Route 1 0 wire with pigtails from the accessory electric heat box into base unit contro...

Page 6: ...ASEPAN BAFFLE ELECTRIC HEATER CONTROL BOX SPACER BAFFLE Fig 5 Electric Heater Installation Details LEGEND ASY Assembly TB Terminal Block Fig 6 Accessory Electric Heat Wiring Connection Diagram Package...

Page 7: ...Electric Heat Box NOTE Route heater control wiring outside of accessory electric heat box Secure with field supplied wire ties to base unit control box Con trol wiring must clear hinged door on electr...

Page 8: ...0 26 32 0 52 55 0 78 Heater capacity kW is based on heater voltage of 208 V 240 v 380 v or 480 v Heaters are rated at 240 v and 480 v If distribution voltage to unit power varies from rated heater vol...

Reviews: