background image

25

TROUBLESHOOTING

For a list of common operating issues and concerns, see

Table 15.

Power Loss (Outage or Brownout)

All set points and advanced settings are restored after any pow-

er loss or interruption, as all settings are stored in the Econo-

mizer controller’s non-volatile flash memory.
NOTE: If the power goes below 18 vac, the W7220 controller

module assumes a power loss and the 5 minute power up delay

will become functional when power returns above 18 vac.

Alarms

The economizer module provides alarm messages that display

on the 2-line LCD.
NOTE: Upon power up, the module waits several seconds before

checking for alarms. This allows time for all the configured devic-

es (e.g., sensors, actuator) to become operational.

If one or more alarms are present and there has been no keypad

activity for at least 5 minutes, the Alarms menu displays and

cycles through the active alarms.
The Alarms menus can be navigated at any time. See Table 11

for the Alarms menu. 
CLEARING ALARMS
Once the alarm has been identified and the cause has been re-

moved (e.g., replaced faulty sensor), the alarm can be cleared

from the display.
To clear an alarm, perform the following:
1. Navigate to the desired alarm.
2. Press the 

 button.

3. ERASE? displays.

4. Press the 

 button.

5. ALARM ERASED displays.

6. Press the 

 (Menu up/Exit) button to complete the

action and return to the previous menu.

NOTE: If an alarm still exists after it has been cleared, it will re-

display within 5 seconds.

Table 15 — Operating Issues and Concerns

ISSUE OR CONCERN

POSSIBLE CAUSE AND REMEDY

My outdoor temperature reading on the STATUS menu is 

not accurate

Check the sensor wiring:

• Enthalpy sensors are to be wired to the S-Bus terminals.

• Temperature sensors are to be wired to the OAT and MAT terminals.

If my enthalpy sensor drifts in accuracy over time, can I 

recalibrate it?

The sensor is not able to be re-calibrated in the field. However, there is a menu item 

under the ADVANCED menu to input a limited offset in temperature and humidity for 

each sensor that is connected to the economizer.

Can I go back to factory defaults and start over?

Under the SYSTEM SETUP menu, you can change the set points to the factory 

defaults.

Will I be able to see the LCD screen when it is in the unit?

The LCD screen has a backlight that is always illuminated.

What is a good set point for the Mixed Air Temperature 

(MAT)?

The Mixed Air Temperature is the temperature of air to supply to the space. In a 

commercial building, this is between 50°F and 55°F (10°C and 13°C). Mixed air is the 

combination of return air and outdoor air.

I am using enthalpy sensors. Why did the control ask me to 

input a dry bulb changeover temperature?

If the humidity sensor in the enthalpy sensors fails, the backup algorithm in the control is 

to default to the temperature sensor in the enthalpy sensor.

In checkout, the outdoor damper closes when I command it 

to open.

Check the actuator linkage or rotation. In the CHECKOUT mode, the outdoor damper 

should drive open or closed with the return air damper having the opposite effect.

How do I set my minimum position when using a CO

2

 

sensor?

The minimum position is set using the VENTMIN and VENTMAX setup in the 

SETPOINTS menu. VENTMIN is the minimum ventilation required when using an 

occupancy sensor and VENTMAX is the minimum ventilation when not using an 

occupancy sensor for Demand Control Ventilation. The VENTMAX position is set the 

same as with the potentiometer on the analog economizers and is the output voltage to 

the damper actuator. The range is 2 vdc closed OA damper and 10 vdc open OA 

damper.

What if my damper does not go completely closed in the 

checkout operation?

Check the damper linkage or hub to make sure the damper is able to close completely.

How do I set the OCC?

There are two settings for the OCC setting: INPUT and ALWAYS. INPUT is from the 

space thermostat, if it has an occupancy output. ALWAYS is the unit in the occupied 

mode, if the economizer is powered (fan on).

Does the economizer save my program values if the unit 

loses power?

Yes, once the changes are stored in the controller they will be stored until they are 

changed by the operator.

If the unit is left in checkout, how long will the unit stay in 

checkout mode without input?

The unit will remain in checkout for 10 minutes, then return to normal operation.

Summary of Contents for CRECOMZR077A00

Page 1: ...r safety glasses and work gloves Use care in handling and installing the accessory It is important to recognize safety information This is the safety alert symbol When you see this symbol on the unit...

Page 2: ...for applications requiring even greater ex haust capabilities The power exhaust set point is adjustable at the EconoMi er X controller See Table 1 3 for package usage See Table 4 for package con tents...

Page 3: ...Off Panel 1 Horizontal Blank Off Panel 1 Filter Access Door 1 Hardware Bag CRECOMZR081A00 1 EconoMi er Horizontal Damper Assembly with Actuator and HH79ZZ007 OA Sensor 1 Jade HW63AW002 HW W7220 Contr...

Page 4: ...IZER P N A B SHIP WT CRECOMZR077A00 25 1 29 19 95 lb CRECOMZR079A00 25 1 37 25 150 lb CRECOMZR081A00 24 81 53 36 245 lb Outside Air Temperature Sensor Red Shipping Tape Outside Air Damper Wiring Harne...

Page 5: ...nk off panel above hood Screw in place See Fig 8 and 9 Fig 7 EconoMi er X Hood Installation Fig 8 Horizontal Return Opening Blank Off Panel Fig 9 Front Blank Off Panel Installation Panel Fig 10 Top Vi...

Page 6: ...on for more details on enthalpy settings Fig 13 Connect EconoMi er X Harness to Unit PL6 Economizer Harness 17 Remove and save the 12 pin jumper plug from the unit economizer harness located in the up...

Page 7: ...r ness See Fig 17 and 25 Fig 17 Connect 10 pin Plugs Together 22 Connect the 10 pin female plug from the Jade controller harness to ECON on the CTB See Fig 18 and 25 Fig 18 Connect 10 pin Jade Plug to...

Page 8: ...to Harness from Controller 27 Route the 4 wire 48TMHSRSE A20 harness through the divider between the control box and the indoor blower sec tion See Fig 22 NOTE Some control box configurations may diff...

Page 9: ...nnect Pink and Violet Wires in Indoor Blower Section 30 If using differential return sensor or DCV sensor install it now See installation details later in the instructions and the wiring diagram for f...

Page 10: ...GRA ORG YEL BLK BRN RED VIO 1 1 2 2 3 3 4 10 6 4 5 9 1 3 8 2 7 1 2 3 4 5 6 7 8 9 10 4 9 3 8 10 2 6 7 5 1 4 10 Pin Female Plug Disconnected from CTB CO2 Optional Ground W1 on CTB W7220 JADE Controller...

Page 11: ...NOTE The 4 wire 48TMHSRSE A20 harness provided with the economizer will also NOT be used on the 48 50LC 07 12 units see Fig 27 Fig 27 48TMHSRSE A20 Not Used on 48 50LC 07 12 Units 3 The 48 50LC 07 12...

Page 12: ...er See Fig 30 6 The connectors on the left side of Fig 28 on the 48LCHS RADH A00 harness attach to the unit s CSC board Con nect J3 and J5 plugs to the CSC board See Fig 30 7 Screw the green wire with...

Page 13: ...13 NOTE Harness attached to the W7220 controller from the Carrier factory is removed and not used with 48 50LC 07 12 units Fig 30 Typical EconoMi er X Wiring Diagram For 48 50LC 07 12 Units...

Page 14: ...e the HH57AC081 sensor for outside air sensor the dipswitches on the sensor must be set to OFF OFF OFF See Table 8 The 2 gray wires with a plug from the EconoMi er X harness in the return chamber plug...

Page 15: ...y limit value shall be set to the enthalpy value at 75 F and 50 relative humidity As an example at approximately 6 000 foot elevation the fixed enthalpy limit is approximately 30 7 Btu lb Demand Contr...

Page 16: ...ceptable to some codes is an annunci ator light visible by service personnel See Fig 36 for typical wiring to the Jade controller Refer to codes for proper labeling of light Fig 35 Thermostat Wired fo...

Page 17: ...GE STORED displays 9 Press the Enter button to return to the current menu parameter 10 Press the Menu Up Exit button to return to the previ ous menu Menu Structure Table 11 illustrates the complete hi...

Page 18: ...or power exhaust are available by referring to Table 11 options 3 Fan speed options are 1 1 Speed 2 2 Speed 3 2 Speed 1 Heat 1 Cool 4 3 Speed 1 Heat 2 Cool 4 Do not use 3 speed setting for LC units Ta...

Page 19: ...nds invalid value if not connected short or out of range OA TEMP _ _ _ F or C 40 F to 140 F 40 C to 60 C OUTSIDE AIR TEMPERATURE Displays measured value of outdoor air temperature Displays _ _ _ if se...

Page 20: ...unit under FAN TYPE and if DCV is NOT used MIN POS L 6 0V 2 to 10 vdc VENTILATION MINIMUM POSITION AT LOW SPEED Only displays if unit is set for 2 or 3 speed and CO2 is not used IF using 2 speed with...

Page 21: ...t and 1 for cool 3 speed units 1 for heat and 2 for cool These Fan Type speed settings are for future use only Do not use for 3 speed LC units FAN CFM 5000cfm 100 to 15000 cfm increment by 100 UNIT DE...

Page 22: ...PER CLOSE n a n a Positions damper to the fully closed position CONNECT Y1 O n a n a Closes the Y1 O relay Y1 O CONNECT Y2 O n a n a Closes the Y2 O relay Y2 O CONNECT AUX1O n a n a Energizes the AUX1...

Page 23: ...les 12 and 13 to locate the wiring terminals for the economizer module NOTE The four terminal blocks are removable Slide out each terminal block wire it and then slide it back into place Fig 38 W7220...

Page 24: ...d is satisfied thermostat Y1 opens the dampers will return to Minimum Damper position if indoor fan is running or fully closed if fan is off If accessory power exhaust is installed the power exhaust f...

Page 25: ...k to factory defaults and start over Under the SYSTEM SETUP menu you can change the set points to the factory defaults Will I be able to see the LCD screen when it is in the unit The LCD screen has a...

Page 26: ......

Page 27: ......

Page 28: ...o discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480208 01 Printed in U S A Form IIK CRECOMZR77 03 Pg 28 11 18A 11 18 Repl...

Reviews: