background image

12

Table 6 – LP Gas Conversion*

ELEVATION

(ft)

LP GAS ORIFICE†

Low

Heat

Med.

Heat

High Heat

(6 Cell)

High Heat

(8 Cell)

0-1,999

35

38

35

35

2,000

36

39

36

36

3,000

36

39

36

36

4,000

37

40

37

37

5,000

37

40

37

37

6,000

38

41

38

38

7,000

39

42

39

39

8,000

40

43

40

40

9,000

41

44

41

41

10,000

42

45

42

42

*As the height above sea level increases, there is less oxygen per cubic ft.

of air. Therefore, heat input rate should be reduced at higher altitudes.

Includes a 4% input reduction per each 1000 ft.

Step 10 — Make Electrical Connections

Field Power Supply

(For more details, refer to the Controls, Start--Up, Operation, and
Troubleshooting manual).
Unit is factory wired for voltage shown on unit nameplate. Be sure
to check for correct voltage.
All 208/230-v units are factory wired for 230-v power supply. If

the 208/230-v unit is to be connected to a 208-v power supply,
transformers (TRAN1 and TRAN2) must be rewired by moving

the black wire with the

1

/

4

-in. female quick connect from the

230-volt connection and moving to the 200-volt

1

/

4

-in. male

terminal on the primary side of the transformer.
When installing units, provide disconnect per NEC (National

Electrical Code) of adequate size (MOCP [Maximum Overcurrent

protection] of unit is on the informative plate). (See Table 7 and 8.)
All field wiring must comply with NEC and local codes. Size wire

based on MCA (Minimum Circuit Amps) on the unit informative
plate. See Fig. 14 for power wiring connection to the unit power

terminal block and equipment ground.
Route power and ground lines through control box end panel or
unit basepan (see Fig. 4) to connections as shown on unit wiring

diagram and Fig. 14.

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage.
The correct power phasing is critical to the operation of the

scroll compressors. An incorrect phasing will result in

compressor shutdown on thermal overload and possible

damage to compressor. Should this occur, power phase

correction must be made to the incoming power.

CAUTION

!

LEGEND

EQUIP

 - Equipment

GND

 - Ground

NEC

 - National Electrical Code

TB

 - Terminal Board

NOTE:  The maximum wire size for TB1 is 2/0

C06293

Fig. 14 -- Field Power Wiring Connections

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Unit cabinet must have an uninterrupted, unbroken

electrical ground to minimize the possibility of personal

injury if an electrical fault should occur. This ground may

consist of electrical wire connected to unit ground lug in

control compartment, or conduit approved for electrical

ground when installed in accordance with NEC; ANSI

(American National Standards Institute)/NFPA (National

Fire Protection Association), latest edition, and local

electrical codes.

Do not use gas piping as an electrical

ground.

!

WARNING

Field wiring must conform to temperature limitations for type “T”

wire. All field wiring must comply with NEC and local
requirements.
Operating voltage to compressor must be within voltage range

indicated on unit nameplate. On 3-phase units, voltages between
phases must be balanced within 2%.
Unit failure as a result of operation on improper line voltage or
excessive phase imbalance constitutes abuse and may cause

damage to electrical components.

Field Control Wiring (Units Without Optional

Humidi--MiZer

t

Adaptive Dehumidification System)

Unit can be controlled with either a Carrier-approved accessory
thermostat or a Carrier-approved space temperature sensor. Install

thermostat according to the installation instructionsincluded with

accessory. Locate thermostat assembly or space temperature sensor
on a solid interior wall in the conditioned space to sense average

temperature.

48PM20

--

28

Summary of Contents for COMFORTLink PURON 48PM20

Page 1: ...ilters All other operations should be performed by trained service personnel When working on air conditioning equipment observe precautions in the literature tags and labels attached to the unit and o...

Page 2: ...ng sides of unit with a minimum of 3 equally spaced 4 in x 4 in pads on each side Slab Mount Horizontal Units Only Provide a level concrete slab that extends a minimum of 6 in beyond unit cabinet Inst...

Page 3: ...3 C07327 Fig 1 Roof Curb Details 48PM20 28...

Page 4: ...ST BE IN PLACE WHEN RIGGING NOTICE TO RIGGERS Rig by inserting hooks into unit base rails as shown Maintain a distance of 120 inches 3048 MM from top of unit to eyehook Leave coil cover attached to un...

Page 5: ...5 50TG505861 Rev 2 0 C07328 Fig 4 Base Unit Dimensions 48PM20 28...

Page 6: ...N Manifold Pressure in wg Natural Gas Vertical Horizontal 3 00 2 95 3 00 2 95 3 00 2 95 Liquid Propane Vertical Horizontal 3 00 2 8 3 00 2 8 3 00 2 8 Thermostat Heat Anticipator Setting amps First Sta...

Page 7: ...43 43 43 34 34 Moveable pulley maximum full turns 6 6 6 6 6 6 Factory Speed setting RPM 1078 1078 1078 1078 906 906 MID HIGH RANGE Motor HP 7 5 7 5 7 5 7 5 7 5 7 5 Motor Nominal RPM 1750 1750 1750 17...

Page 8: ...s 6 6 6 6 6 6 Factory Speed setting RPM 1062 991 1062 991 906 906 MID HIGH RANGE Motor HP 5 5 5 5 7 5 7 5 Motor Nominal RPM 1750 1750 1750 1750 1750 1750 Maximum Continuous BHP 5 37 5 75 5 75 5 37 5 7...

Page 9: ...sed with a night set back thermostat To operate at lower return air temperatures a field supplied outdoor air temperature control must be used to initiate both stages of heat when the temperature is b...

Page 10: ...h the unit Attach the cover of the observation hole on the intake hood and then replace the heat panel onto the unit to complete the installation NOTE When properly installed the flue hood will line u...

Page 11: ...ration using natural gas at an elevation from sea level to 2000 ft This unit uses orifice type LH32RFnnn where nnn indicates the orifice size based on drill size diameter in thousands of an inch High...

Page 12: ...phasing is critical to the operation of the scroll compressors An incorrect phasing will result in compressor shutdown on thermal overload and possible damage to compressor Should this occur power pha...

Page 13: ...anticipator settings as follows VOLTAGE STAGE 1 W1 ON STAGE 1 AND 2 W1 AND W2 ON All 0 15 0 30 Settings may be changed slightly to provide a greater degree of comfort for a particular installation Hu...

Page 14: ...ROOFTOP UNIT TB2 THERMIDISTAT C06295 Fig 17 Field Control Thermidistat Wiring C07354 Fig 18 Humidi MiZert Low Voltage Terminal Strip Humidity Sensor Humidistat Wiring 48PM C Humidi MiZer RTU C07346 F...

Page 15: ...07 106 2 1 5 9 115 114 150 150 115 115 150 150 121 119 5 16 7 15 2 109 108 125 125 109 109 125 125 114 112 2 1 5 9 121 120 150 150 121 121 150 150 128 126 7 5 24 2 22 117 115 150 150 117 117 150 150 1...

Page 16: ...12 2 1 5 9 120 119 150 150 120 120 150 150 126 125 5 16 7 15 2 114 113 150 150 114 114 150 150 120 118 2 1 5 9 126 125 150 150 126 126 150 150 133 132 7 5 24 2 22 122 120 150 150 122 122 150 150 128 1...

Page 17: ...ge is greater than 2 Use the following formula to determine the percent age of voltage imbalance Voltage Imbalance 100 x max voltage deviation from average voltage average voltage Example Supply volta...

Page 18: ...ge of both hood sides where hood side connects to the unit back panel See Fig 21 6 Apply seal strip provided to top flange of both hood sides where hood sides connect to the hood top panels See Fig 21...

Page 19: ...ssembly rests against the inside wall of unit 3 Secure each damper assembly to unit with 6 screws across top 3 screws provided and bottom 3 screws from item 1 of damper 4 With screws saved from item 1...

Page 20: ...ket and Hood Positioning Copyright 2007 Carrier Corp D 7310 W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 11 07 Manufacturer reserves the right to change at any time specifications...

Reviews: