background image

11

C06282

Fig. 11 -- Condensate Drain Details

NOTE:  Trap should be deep enough to offset maximum unit static difference

A 4-in. trap is recommended.

C06291

Fig. 12 -- Condensate Drain Piping Details

C06236

Fig. 13 -- Field Gas Piping

Step 8 — Install Gas Piping

Unit is equipped for use with natural gas. Refer to local building

codes, or in the absence of local codes, to ANSI Z223.1-latest year
and addendum Z223.1A-latest year entitled NFGC. In Canada,

installation must be in accordance with the CAN1.B149.1 and
CAN1.B149.2 installation codes for gas burning appliances.
Support gas piping. For example, a

3

/

4

-in. gas pipe must have one

field-fabricated support beam every 8 ft. Therefore, an 18-ft long
gas pipe would have a minimum of 3 support beams.
Install field-supplied manual gas shutoff valve with a

1

/

8

-in. NPT

pressure tap for test gauge connection at unit. The pressure tap is

located on the gas manifold, adjacent to the gas valve. Field gas
piping must include sediment trap and union. (See Fig. 13.)

FIRE, EXPLOSION HAZARD

Failure to follow this warning could result in personal

injury or death.
Do not pressure test gas supply while connected to unit.

Always disconnect union before servicing. High pressures

can cause gas valve damage resulting in a hazardous

condition.

!

WARNING

IMPORTANT

: Natural gas pressure at unit gas connection must

not be less than 5.5--in. wg or greater than 13.0--in. wg.
Size gas-supply piping for 0.5-in. wg maximum pressure drop. Do
not use supply pipe smaller than unit gas connection.

Step 9 — Orifice Change

This unit is factory assembled for heating operation using natural
gas at an elevation from sea level to 2000 ft. This unit uses orifice

type LH32RFnnn, where “nnn” indicates the orifice size based on

drill size diameter in thousands of an inch.

High Elevation (Above 2000 ft)

Use accessory high altitude kit when installing this unit at an

elevation of 2000 to 7000 ft. For elevations above 7000 ft, refer to

Table 4 to identify the correct orifice size for the elevation. See
Table 5 for the number of orifices required for each unit size.

Purchase these orifices from your local Carrier dealer. Follow
instructions in accessory Installation Instructions to install the

correct orifices.

Table 4 – Altitude Compensation*

ELEVATION

(ft)

NATURAL GAS ORIFICE†

Low

Heat

Med.

Heat

High Heat

(6 Cell)

High Heat

(8 Cell)

0-1,999

29

30

29

29

2,000

29

30

29

29

3,000

30

31

30

30

4,000

30

31

30

30

5,000

30

31

30

30

6,000

30

31

30

30

7,000

31

32

31

31

8,000

31

32

31

31

9,000

31

32

31

31

10,000

32

33

32

32

*As the height above sea level increases, there is less oxygen per cubic ft.

of air. Therefore, heat input rate should be reduced at higher altitudes.

Includes a 4% input reduction per each 1000 ft.Orifices available through

your Carrier dealer.

Table 5 – Orifice Quantity

UNIT

ORIFICE

QUANTITY

Low Heat (48PMD/L)

5

Medium Heat (48PME/M)

8

High Heat (48PMF/N)

8

Conversion to LP (Liquid Propane) Gas

Use accessory LP gas conversion kit when converting this unit for

use with LP fuel usage for elevations up to 7000 ft. For elevations
above 7000 ft, refer to Table 6 to identify the correct orifice size for

the elevation. See Table 5 for the number of orifices required for
each unit size. Purchase these orifices from your local Carrier

dealer. Follow instructions in accessory Installation Instructions to
install the correct orifices.

48PM20

--

28

Summary of Contents for COMFORTLink PURON 48PM20

Page 1: ...ilters All other operations should be performed by trained service personnel When working on air conditioning equipment observe precautions in the literature tags and labels attached to the unit and o...

Page 2: ...ng sides of unit with a minimum of 3 equally spaced 4 in x 4 in pads on each side Slab Mount Horizontal Units Only Provide a level concrete slab that extends a minimum of 6 in beyond unit cabinet Inst...

Page 3: ...3 C07327 Fig 1 Roof Curb Details 48PM20 28...

Page 4: ...ST BE IN PLACE WHEN RIGGING NOTICE TO RIGGERS Rig by inserting hooks into unit base rails as shown Maintain a distance of 120 inches 3048 MM from top of unit to eyehook Leave coil cover attached to un...

Page 5: ...5 50TG505861 Rev 2 0 C07328 Fig 4 Base Unit Dimensions 48PM20 28...

Page 6: ...N Manifold Pressure in wg Natural Gas Vertical Horizontal 3 00 2 95 3 00 2 95 3 00 2 95 Liquid Propane Vertical Horizontal 3 00 2 8 3 00 2 8 3 00 2 8 Thermostat Heat Anticipator Setting amps First Sta...

Page 7: ...43 43 43 34 34 Moveable pulley maximum full turns 6 6 6 6 6 6 Factory Speed setting RPM 1078 1078 1078 1078 906 906 MID HIGH RANGE Motor HP 7 5 7 5 7 5 7 5 7 5 7 5 Motor Nominal RPM 1750 1750 1750 17...

Page 8: ...s 6 6 6 6 6 6 Factory Speed setting RPM 1062 991 1062 991 906 906 MID HIGH RANGE Motor HP 5 5 5 5 7 5 7 5 Motor Nominal RPM 1750 1750 1750 1750 1750 1750 Maximum Continuous BHP 5 37 5 75 5 75 5 37 5 7...

Page 9: ...sed with a night set back thermostat To operate at lower return air temperatures a field supplied outdoor air temperature control must be used to initiate both stages of heat when the temperature is b...

Page 10: ...h the unit Attach the cover of the observation hole on the intake hood and then replace the heat panel onto the unit to complete the installation NOTE When properly installed the flue hood will line u...

Page 11: ...ration using natural gas at an elevation from sea level to 2000 ft This unit uses orifice type LH32RFnnn where nnn indicates the orifice size based on drill size diameter in thousands of an inch High...

Page 12: ...phasing is critical to the operation of the scroll compressors An incorrect phasing will result in compressor shutdown on thermal overload and possible damage to compressor Should this occur power pha...

Page 13: ...anticipator settings as follows VOLTAGE STAGE 1 W1 ON STAGE 1 AND 2 W1 AND W2 ON All 0 15 0 30 Settings may be changed slightly to provide a greater degree of comfort for a particular installation Hu...

Page 14: ...ROOFTOP UNIT TB2 THERMIDISTAT C06295 Fig 17 Field Control Thermidistat Wiring C07354 Fig 18 Humidi MiZert Low Voltage Terminal Strip Humidity Sensor Humidistat Wiring 48PM C Humidi MiZer RTU C07346 F...

Page 15: ...07 106 2 1 5 9 115 114 150 150 115 115 150 150 121 119 5 16 7 15 2 109 108 125 125 109 109 125 125 114 112 2 1 5 9 121 120 150 150 121 121 150 150 128 126 7 5 24 2 22 117 115 150 150 117 117 150 150 1...

Page 16: ...12 2 1 5 9 120 119 150 150 120 120 150 150 126 125 5 16 7 15 2 114 113 150 150 114 114 150 150 120 118 2 1 5 9 126 125 150 150 126 126 150 150 133 132 7 5 24 2 22 122 120 150 150 122 122 150 150 128 1...

Page 17: ...ge is greater than 2 Use the following formula to determine the percent age of voltage imbalance Voltage Imbalance 100 x max voltage deviation from average voltage average voltage Example Supply volta...

Page 18: ...ge of both hood sides where hood side connects to the unit back panel See Fig 21 6 Apply seal strip provided to top flange of both hood sides where hood sides connect to the hood top panels See Fig 21...

Page 19: ...ssembly rests against the inside wall of unit 3 Secure each damper assembly to unit with 6 screws across top 3 screws provided and bottom 3 screws from item 1 of damper 4 With screws saved from item 1...

Page 20: ...ket and Hood Positioning Copyright 2007 Carrier Corp D 7310 W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 11 07 Manufacturer reserves the right to change at any time specifications...

Reviews: