background image

2

10. Using the scrolling marquee, enable the unit to run using

the following procedure:

a. Push the 

 key unit a blank display screen

is shown.

b. Push the 

 key until the SERVICE TEST LED is

lit.

c. Push the 

 key. The display will show

STOP.

d. Push the 

 key again. The NO/YES display

will flash.

e. Push the 

 or 

 key to toggle the display to NO

and then push 

. The unit will return to

normal operation and exit SERVICE TEST mode.

11. To test the operation of the gas section, use the scrolling

marquee Service Test routine to energize the gas outputs

and to turn on the gas. Refer to the unit Controls, Start-

Up, Operation, Service and Troubleshooting literature for

more information.

12. For normal operation, make sure that units with a conven-

tional thermostat are set to heating control temperature.

On VAV (variable air volume) and constant volume units

with a space temperature sensor, make sure that the set

points are at the normal heat set points.

WARNING

If the main burners fail to light or the blower fails to start,

shut down gas heating section and call your dealer for ser-

vice. Failure to follow these requirements could result in

serious personal injury.

ESCAPE

ENTER

ENTER

ENTER

LIMIT

S

WITCH

NO. 1

S

ECTION 1

S

ECTION 2

LIMIT

S

WITCH

NO. 2

GA

S

 VALVE

GA

S

 VALVE

FLUE
OUTLET

FLUE
OUTLET

GA

S

 VALVE

FLUE
OUTLET

LIMIT

S

WITCH

NO. 1

S

ECTION 1

S

ECTION 2

LIMIT

S

WITCH

NO. 2

FLUE
OUTLET

GA

S

 VALVE

Fig. 1 — Heat Section Details

NOTE: High heat consists of sections 1-3. Low heat consists of
sections 1 and 2 only.

055-100 SIZES LOW HEAT

NOTE: High heat consists of sections 1 and 2. Low heat consists
of section 1 only.

030-050 SIZES

a48-8445a

a48-8445b

GA

S

 VALVE

FLUE
OUTLET

LIMIT

S

WITCH

NO. 1

S

ECTION 1

LIMIT

S

WITCH

NO. 2

S

ECTION 2

FLUE
OUTLET

GA

S

 VALVE

S

ECTION 

3

FLUE
OUTLET

GA

S

 VALVE

Fig. 1 — Heat Section Details (cont)

NOTE: High heat consists of sections 1-3. Low heat consists of
sections 1 and 2 only.

055-100 SIZES HIGH HEAT

a48-8446

Summary of Contents for COMFORTLINK 48P2

Page 1: ...on the electrical supply to the units 9 Open the field installed manual gas valve WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property dama...

Page 2: ...erature sensor make sure that the set points are at the normal heat set points WARNING If the main burners fail to light or the blower fails to start shut down gas heating section and call your dealer...

Page 3: ...Run Status Service Test Temperature Pressures Setpoints Inputs Outputs Configuration Time Clock Operating Modes Alarms Alarm Status ENTER MODE ESCAPE Run Status Service Test Temperature Pressures Setp...

Page 4: ...ged filter access door to replace or inspect the filters All units have filter tracks into which the filters slide Remove the filters by pulling outward from the track See Fig 4 for filter access door...

Page 5: ...erly Checking and or cleaning the heat exchanger involves removing the gas controls assembly and the flue collector box cover and when completed reinstalling the gas controls assembly for proper opera...

Page 6: ...ORS POWER EXHAUST ACCESS DOOR TYP BOTH SIDES GAS BURNERS AIR HOODS FILTER ACCESS DOOR POWER EXHAUST OPTION CONTROL BOX GAS SECTION ACCESS DOOR ACCESS DOORS POWER EXHAUST ACCESS DOOR TYP BOTH SIDES GAS...

Page 7: ...om bustion area and vent system should be visually inspected be fore each heating season The normal accumulation of dirt soot rust and scale can result in loss of efficiency and improp er performance...

Page 8: ...is suspected Check for sufficient airflow Check the air filters for dirt Check for blocked return air or supply air grilles Be sure they are open and unobstructed Be sure heating and cooling set poin...

Reviews: