Carrier COMFORT SERIES 25HCR Installation Instructions Manual Download Page 9

9

Sequence of Operation
NOTE

: Defrost control board is equipped with 5 minute lockout

timer that is initiated upon any interruption of power.
Turn on power to indoor and outdoor units. Transformer is
energized.

Cooling

On a call for cooling, thermostat makes circuits R--O, R--Y, and

R--G. Circuit R--O energizes reversing valve, switching it to
cooling position. Circuit R--Y sends low voltage through the

safeties and energizes the T1 terminal on the circuit board. If the

compressor
has been off for 5 minutes, or power has not been cycled for 5

minutes, the OF2 relay and T2 terminal will energize. This will
close the contactor, and start the outdoor fan motor and

compressor.
When the cycle is complete, R--Y is turned off, stopping the
compressor and outdoor fan. The 5 minute time guard begins

counting. Compressor will not come on again until this delay
expires. In the event of a power interruption, the time guard will

not allow another cycle for 5 minutes.

NOTE

: If the indoor blower off delay is enabled, it will run up

to an additional 90 seconds to increase system efficiency.

Heating

On a call for heating, thermostat makes circuits R--Y and R--G.
Circuit R--Y sends low voltage through the safeties and energizes

the T1 terminal on the circuit board. T1 energizes the defrost

logic circuit. If the compressor has been off for 5 minutes, or
power

has not been cycled for 5 minutes, the OF2 relay and T2 terminal
will energize. This will close the contactor, start the outdoor fan

motor and compressor.
When the cycle is complete, R--Y is turned off , stopping the

compressor and outdoor fan. The 5 minute time guard begins

counting. Compressor will not come on again until this time
delay expires. In the event of a power interruption, the time guard

will
not allow another cycle for 5 minutes.

Quiet Shift

Quiet shift is a field selectable defrost mode (factory set to OFF),

which will eliminate occasional noise that could be heard at the
start of defrost cycle and restarting of heating cycle. It is selected

by placing DIP switch 3 on defrost board (see Fig. 12) in the ON

position.
When Quiet Shift switch is placed in ON position, and a defrost is

initiated, the following sequence of operation will occur.
Reversing valve will energize, compressor will turn off for 30

seconds, and then turn back on to complete defrost. At the start of

heating after conclusion of defrost, reversing valve will
de--energize, compressor will turn off for another 30 seconds, and

the fan will turn off for 40 seconds, before starting in the heating
mode.

Defrost

The defrost control is a time/temperature control which has field
selectable settings of 30, 60, 90, or 120 minutes, factory set to

90 minutes. These settings represent the amount of time that must
pass after closure of the defrost thermostat before the defrost

sequence begins.
The defrost thermostat senses coil temperature throughout the

heating cycle. When the coil temperature reaches the defrost

thermostat setting of approximately 32 degrees F, it will close,
which energizes the DFT terminal and begins the defrost timing

sequence. When the DFT has been energized for the selected
time, the defrost cycle begins.
Defrost cycle is terminated when defrost thermostat opens, or

automatically after 10 minutes.

Defrost Speedup

To initiate a forced defrost, speedup pins (J1) must be shorted
with a flat head screwdriver for 5 seconds and

RELEASED

. If

the defrost thermostat is open, a short defrost cycle will be

observed (actual length depends on Quiet Shift switch position).
When Quiet Shift is off, only a short 30 second defrost cycle is

observed. With Quiet Shift ON, the speedup sequence is one
minute; 30 second compressor off period followed by 30 seconds

of defrost with compressor operation. When returning to heating
mode, the compressor will turn off for an additional 30 seconds

and the fan for 40 seconds.
If the defrost thermostat is closed, a complete defrost cycle is
initiated. If the Quiet Shift switch is turned on, the compressor

will be turned off for two 30 second intervals as explained
previously.

25H

C

R

Summary of Contents for COMFORT SERIES 25HCR

Page 1: ...COMMENDATIONS 2 INSTALLATION 3 10 Step 1 Check Equipment Jobsite 3 Step 2 Install on Solid Pad 3 Step 3 Clearance Requirements 3 Step 4 Operating Ambient 3 Step 5 Install TXV 3 4 Step 6 Check Defrost...

Page 2: ...h a suitable warning label INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from wi...

Page 3: ...in above roof surface STEP 4 Operating Ambient The minimum outdoor operating ambient in cooling mode is 55 F and the maximum outdoor operating ambient in cooling mode is 125 F The maximum outdoor ope...

Page 4: ...r connection to indoor coil Adapter has a 1 4 in male connector for attaching equalizer tube 14 Connect equalizer tube of TXV to 1 4 in equalizer fitting on vapor line adapter Use backup wrench to pre...

Page 5: ...nnect refrigerant tubing to fittings on outdoor unit vapor and liquid service valves Service valves are closed from factory and ready for brazing After wrapping service valve with a wet cloth tubing s...

Page 6: ...r A05227 Fig 7 Liquid Line Filter Drier STEP 8 Make Electrical Connections WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Do not supply power t...

Page 7: ...ries Refer to the individual instructions packaged with kits or accessories when installing STEP 11 Start Up CAUTION PERSONAL INJURY HAZARD Failure to follow this caution may result in personal injury...

Page 8: ...G FIELD SPLICE CONNECTION OUTDOOR THERMOSTAT EMERGENCY HEAT RELAY SUPPLEMENTAL HEAT RELAY SHR EHR ODT A02325 A97413 Fig 9 Generic Wiring Diagrams See Thermostat Installation Instructions for specific...

Page 9: ...he start of defrost cycle and restarting of heating cycle It is selected by placing DIP switch 3 on defrost board see Fig 12 in the ON position When Quiet Shift switch is placed in ON position and a d...

Page 10: ...t match on chart system refrigerant charge may not be correct Do not use chart to adjust refrigerant charge STEP 13 Final Checks IMPORTANT Before leaving job be sure to do the following 1 Ensure that...

Reviews: