background image

5

Outdoor units may be connected to indoor section using
accessory tubing package or field--supplied refrigerant grade

tubing of correct size and condition. For tubing requirements
beyond 80 ft., substantial capacity and performance losses can

occur. Following the recommendations in the Application

Guideline and Service Manual--Residential Split--System Air
Conditioners and Heat Pumps will reduce these losses. Refer to

Table 1 for accessory requirements. Refer to Table 2 for field
tubing diameters.
There are no buried--line applications greater than 36 in.
If refrigerant tubes or indoor coil are exposed to atmosphere, they
must be evacuated to 500 microns to eliminate contamination and

moisture in the system.

Outdoor Unit Connected to Factory--Approved Indoor Unit

Outdoor unit contains correct system refrigerant charge for
operation with approved ARI rated indoor unit when connected

by 15 ft. of field--supplied or factory--accessory tubing, and
factory supplied filter drier. Check refrigerant charge for

maximum efficiency.

Refrigerant Tubing and Sweat Connections

Connect vapor tube to fitting on outdoor unit vapor service

valves (see Table 2). Connect liquid tubing to adapter tube on
liquid service valve. Use refrigerant grade tubing.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Service valves must be wrapped in a heat--sinking

material such as a wet cloth while brazing.

Remove plastic retainer holding outdoor piston in liquid service
valve, leaving the piston and piston retainer inside the valve.

Connect sweat/flare adapter provided, to valve. (See Fig. 6.)
Connect refrigerant tubing to fittings on outdoor unit vapor and

liquid service valves. Service valves are closed from factory and

ready for brazing. After wrapping service valve with a wet cloth,
tubing set can be brazed to service valve using either silver

bearing or non--silver bearing brazing material. Do not use soft
solder (materials which melt below 800

°

F). Consult local code

requirements. Refrigerant tubing and indoor coil are now ready

for leak testing. This check should include all field and factory
joints.

PISTON  BODY

PISTON

PISTON 

RETAINER

SWEAT/FLARE  ADAPTER

A05226

Fig. 6

---

Liquid Service Valve

Table 1—Accessory Usage

Accessory

REQUIRED FOR LOW---AMBIENT AP-

PLICATIONS
(Below 55

°

F

)

REQUIRED FOR LONG LINE APPLICA-

TIONS* (Over 80 ft.)

Crankcase Heater

Yes

Yes

Evaporator Freeze Thermostat

Yes

No

Winter Start Control

Yes

No

Accumulator

No

No

Compressor Start Assist Capacitor and Relay

Yes

Yes

Support Feet

Recommended

No

Liquid Line Solenoid Valve

No

See Long---Line Application Guideline

* For Tubing Set lengths between 80 and 200 ft. horizontal or 20 ft. vertical differential (250 ft. Total Equivalent Length), refer to the Long Line Guidelines for Air

Conditioners and Heat Pumps using R---22.

Table 2—Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (in.)

UNIT SIZE

LIQUID

VAPOR (up to 80 ft.*)

Connection Diameter

Tube

Diameter

Connection Diameter

Rated Tube Diameter

018, 024

3/8

3/8

5/8

5/8

030, 036

3/8

3/8

3/4

3/4

042, 048

3/8

3/8

7/8

7/8

060

3/8

3/8

7/8

1--1/8

Notes:

1. Tube diameters are for total equivalent lengths up to 80 ft..

2. Do not apply capillary tube or fixed orifice indoor coils to these units.
* For Tubing Set lengths between 80 and 200 ft. horizontal or 20 ft. vertical differential (250 ft.Total Equivalent Length), refer to the Longline Guideline--- Air

Conditioners and Heat Pumps using R---22

25H

C

R

25H

C

R

Summary of Contents for COMFORT SERIES 25HCR

Page 1: ...COMMENDATIONS 2 INSTALLATION 3 10 Step 1 Check Equipment Jobsite 3 Step 2 Install on Solid Pad 3 Step 3 Clearance Requirements 3 Step 4 Operating Ambient 3 Step 5 Install TXV 3 4 Step 6 Check Defrost...

Page 2: ...h a suitable warning label INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from wi...

Page 3: ...in above roof surface STEP 4 Operating Ambient The minimum outdoor operating ambient in cooling mode is 55 F and the maximum outdoor operating ambient in cooling mode is 125 F The maximum outdoor ope...

Page 4: ...r connection to indoor coil Adapter has a 1 4 in male connector for attaching equalizer tube 14 Connect equalizer tube of TXV to 1 4 in equalizer fitting on vapor line adapter Use backup wrench to pre...

Page 5: ...nnect refrigerant tubing to fittings on outdoor unit vapor and liquid service valves Service valves are closed from factory and ready for brazing After wrapping service valve with a wet cloth tubing s...

Page 6: ...r A05227 Fig 7 Liquid Line Filter Drier STEP 8 Make Electrical Connections WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Do not supply power t...

Page 7: ...ries Refer to the individual instructions packaged with kits or accessories when installing STEP 11 Start Up CAUTION PERSONAL INJURY HAZARD Failure to follow this caution may result in personal injury...

Page 8: ...G FIELD SPLICE CONNECTION OUTDOOR THERMOSTAT EMERGENCY HEAT RELAY SUPPLEMENTAL HEAT RELAY SHR EHR ODT A02325 A97413 Fig 9 Generic Wiring Diagrams See Thermostat Installation Instructions for specific...

Page 9: ...he start of defrost cycle and restarting of heating cycle It is selected by placing DIP switch 3 on defrost board see Fig 12 in the ON position When Quiet Shift switch is placed in ON position and a d...

Page 10: ...t match on chart system refrigerant charge may not be correct Do not use chart to adjust refrigerant charge STEP 13 Final Checks IMPORTANT Before leaving job be sure to do the following 1 Ensure that...

Reviews: