Installation Instructions

25HCR

COMFORT

t

SERIES R---22 HEAT PUMPS

SIZES 18 TO 60

1---1/2 TO 5 NOMINAL TONS

A05341

Fig. 1

---

25HCR

NOTE

: Read the entire instruction manual before starting the

installation.

TABLE OF CONTENTS

PAGE

SAFETY CONSIDERATIONS

2

. . . . . . . . . . . . . . . . . . . . . . .

INSTALLATION RECOMMENDATIONS

2

. . . . . . . . . . . . .

INSTALLATION

3 -- 10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Step 1 -- Check Equipment & Jobsite

3

. . . . . . . . . . . . . . .

Step 2 -- Install on Solid Pad

3

. . . . . . . . . . . . . . . . . . . . . .

Step 3 -- Clearance Requirements

3

. . . . . . . . . . . . . . . . . .

Step 4 -- Operating Ambient

3

. . . . . . . . . . . . . . . . . . . . . .

Step 5 -- Install TXV

3 -- 4

. . . . . . . . . . . . . . . . . . . . . . . . .

Step 6 -- Check Defrost Thermostat

4

. . . . . . . . . . . . . . . . .

Step 7 -- Make Piping Connections

4 -- 6

. . . . . . . . . . . . . .

Step 8 -- Make Electrical Connections

6 -- 7

. . . . . . . . . . . .

Step 9 -- Compressor Crankcase Heater

7

. . . . . . . . . . . . .

Step 10 -- Install Electrical Accessories

7

. . . . . . . . . . . . . .

Step 11 -- Start--Up

7 -- 9

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Step 12 -- Check Charge

10

. . . . . . . . . . . . . . . . . . . . . . . . .

Step 13 -- Final Checks

10

. . . . . . . . . . . . . . . . . . . . . . . . . .

CARE AND MAINTENANCE

10

. . . . . . . . . . . . . . . . . . . . . .

Summary of Contents for COMFORT SERIES 25HCR

Page 1: ...COMMENDATIONS 2 INSTALLATION 3 10 Step 1 Check Equipment Jobsite 3 Step 2 Install on Solid Pad 3 Step 3 Clearance Requirements 3 Step 4 Operating Ambient 3 Step 5 Install TXV 3 4 Step 6 Check Defrost...

Page 2: ...h a suitable warning label INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from wi...

Page 3: ...in above roof surface STEP 4 Operating Ambient The minimum outdoor operating ambient in cooling mode is 55 F and the maximum outdoor operating ambient in cooling mode is 125 F The maximum outdoor ope...

Page 4: ...r connection to indoor coil Adapter has a 1 4 in male connector for attaching equalizer tube 14 Connect equalizer tube of TXV to 1 4 in equalizer fitting on vapor line adapter Use backup wrench to pre...

Page 5: ...nnect refrigerant tubing to fittings on outdoor unit vapor and liquid service valves Service valves are closed from factory and ready for brazing After wrapping service valve with a wet cloth tubing s...

Page 6: ...r A05227 Fig 7 Liquid Line Filter Drier STEP 8 Make Electrical Connections WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Do not supply power t...

Page 7: ...ries Refer to the individual instructions packaged with kits or accessories when installing STEP 11 Start Up CAUTION PERSONAL INJURY HAZARD Failure to follow this caution may result in personal injury...

Page 8: ...G FIELD SPLICE CONNECTION OUTDOOR THERMOSTAT EMERGENCY HEAT RELAY SUPPLEMENTAL HEAT RELAY SHR EHR ODT A02325 A97413 Fig 9 Generic Wiring Diagrams See Thermostat Installation Instructions for specific...

Page 9: ...he start of defrost cycle and restarting of heating cycle It is selected by placing DIP switch 3 on defrost board see Fig 12 in the ON position When Quiet Shift switch is placed in ON position and a d...

Page 10: ...t match on chart system refrigerant charge may not be correct Do not use chart to adjust refrigerant charge STEP 13 Final Checks IMPORTANT Before leaving job be sure to do the following 1 Ensure that...