1

50VT---A

Performance

t

14 SEER Single---Packaged Heat Pump

System with Puron

®

(R---410A) Refrigerant

Single and Three Phase

2---5 Nominal Tons (Sizes 24---60)

Installation Instructions

NOTE

:

Read the entire instruction manual before starting the

installation.

NOTE

:

Installer: Make sure the Owner’s Manual and Service

Instructions are left with the unit after installation.

TABLE OF CONTENTS

PAGE

SAFETY CONSIDERATIONS

1

. . . . . . . . . . . . . . . . . . . . . . . . .

INTRODUCTION

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

RECEIVING AND INSTALLATION

2--9

. . . . . . . . . . . . . . . . . .

Check Equipment

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Identify Unit

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Inspect Shipment

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Provide Unit Support

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Roof Curb

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Slab Mount

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Provide Clearances

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Rig and Place Unit

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Inspection

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Rigging/Lifting of Unit

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Select and Install Ductwork

7

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Converting Horizontal Discharge Units to Downflow

(Vertical) Discharge Units

7

. . . . . . . . . . . . . . . . . . . . . . . . . .

Provide for Condensate Disposal

8

. . . . . . . . . . . . . . . . . . . . . .

Install Electrical Connections

8

. . . . . . . . . . . . . . . . . . . . . . . . .

High--Voltage Connections

8

. . . . . . . . . . . . . . . . . . . . . . . . .

Special Procedures for 208--V Operation

9

. . . . . . . . . . . . . . .

Control Voltage Connections

9

. . . . . . . . . . . . . . . . . . . . . . . .

Standard Connections

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Transformer Protection

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Accessory Electric heaters Installation

9

. . . . . . . . . . . . . . . . .

Sequence of Operation

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

PRE--START--UP

17

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

START--UP

17--20

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Checking Cooling & Heating Control Operation

17

. . . . . . . .

Check for Refrigerant Leaks

17

. . . . . . . . . . . . . . . . . . . . . . . . .

Start--Up Adjustments

17

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Checking & Adjusting Refrigerant Charge

18

. . . . . . . . . . . .

Indoor Airflow & Airflow Adjustments

18

. . . . . . . . . . . . . .

Continuous Fan Operation

19

. . . . . . . . . . . . . . . . . . . . . . . .

Defrost Control

20

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Quiet Shift

20

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Defrost

20

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

MAINTENANCE

23--28

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Air Filter

23

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Indoor Blower and Motor

23

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Outdoor Coil, Indoor Coil, & Condensate Drain Pan

26

. . . . . .

Outdoor Fan

26

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Electrical Controls and Wiring

26

. . . . . . . . . . . . . . . . . . . . . . .

Refrigerant Circuit

26

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Indoor Airflow

26

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Metering Devices-- TXV & Piston

26

. . . . . . . . . . . . . . . . . . . .

Pressure Switches

27

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Loss of Charge Switch

27

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

High Pressure Switch

27

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A09033

Fig. 1 -- Unit 50VT--A

Copeland Scroll compressor (Puron Refrigerant)

27

. . . . . . . . .

Refrigerant System

27

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Refrigerant

27

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Compressor Oil

27

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Servicing Systems on Roofs with Synthetic Materials

27

. . . .

Liquid Line Filter Drier

27

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Puron

R

(R--410A) Refrigerant Charging

28

. . . . . . . . . . . . .

System Information

28

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Loss of Charge Switch

28

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Check Defrost Thermostat

28

. . . . . . . . . . . . . . . . . . . . . . . . .

TROUBLESHOOTING

28

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

START--UP CHECKLIST

28

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

SAFETY CONSIDERATIONS

Installation and servicing of this equipment can be hazardous due

to mechanical and electrical components. Only trained and
qualified personnel should install, repair, or service this equipment.
Untrained personnel can perform basic maintenance functions such
as cleaning and replacing air filters. All other operations must be

performed by trained service personnel. When working on this

equipment, observe precautions in the literature, on tags, and on
labels attached to or shipped with the unit and other safety

precautions that may apply.
Follow all safety codes. Wear safety glasses, protective clothing,

and work gloves. Use quenching cloth for brazing operations.
Have a fire extinguisher available. Read these instructions

thoroughly and follow all warnings or cautions included in

literature and attached to the unit. Consult local building codes, the
current editions of the National Electrical Code (NEC) NFPA 70.
In Canada refer to the current editions of the Canadian Electrical
Code CSA C22.1.

Summary of Contents for COMFORT 50VT-A

Page 1: ...ndensate Drain Pan 26 Outdoor Fan 26 Electrical Controls and Wiring 26 Refrigerant Circuit 26 Indoor Airflow 26 Metering Devices TXV Piston 26 Pressure Switches 27 Loss of Charge Switch 27 High Pressu...

Page 2: ...tructions shipped with curb See Fig 4 Install insulation cant strips roofing and flashing Ductwork must be attached to curb IMPORTANT The gasketing of the unit to the roof curb is critical for a water...

Page 3: ...3 A09410 Fig 2 50VT A24 30 Unit Dimensions 50VT A...

Page 4: ...4 A09411 Fig 3 50VT A36 60 Unit Dimensions 50VT A...

Page 5: ...mm B small common base IN mm B large base IN mm C IN mm D IN mm E IN mm F IN mm G IN mm H IN mm Small or Large CPRFCURB010A00 11 279 10 254 14 356 16 406 47 8 1214 32 4 822 2 7 69 30 6 778 46 1 1170 C...

Page 6: ...adapt to various sizes or kinds of loads 2 Instruction in any special operation or precaution 3 Condition of the load as it relates to operation of the lifting kit such as balance temperature etc Foll...

Page 7: ...commended 4 Seal insulate and weatherproof all external ductwork Seal insulate and cover with a vapor barrier all ductwork passing through conditioned spaces Follow latest Sheet Metal and Air Conditio...

Page 8: ...be using a minimum of field supplied 3 4 in PVC or field supplied 3 4 in copper pipe at outlet end of the 2 in 51 mm trap See Fig 9 Do not undersize the tube Pitch the drain tube downward at a slope o...

Page 9: ...o that they do not interfere with operation of unit A gray wire is standard on 3 phase units for connection to an economizer If an accessory electric heater is installed low voltage leads from heater...

Page 10: ...1000 10 x 10 254 x 254 1 2 1200 11 x 10 279 x 254 3 4 1400 11 x 10 279 x 254 3 4 1600 11 x 10 279 x 254 1 1750 11 x 10 279 x 254 1 High Pressure Switch psig Cutout Reset Auto 650 15 420 25 Loss of Cha...

Page 11: ...11 A11002 Fig 12 Connection Wiring Schematics 208 230 1 60 50VT A...

Page 12: ...12 A11001 Fig 12 Cont Ladder Wiring Schematics 208 230 1 60 50VT A...

Page 13: ...13 A11006 Fig 13 Connection Wiring Schematics 208 230 3 60 50VT A...

Page 14: ...14 A11005 Fig 13 Cont Ladder Wiring Schematics 208 230 3 60 50VT A...

Page 15: ...15 A10195 Fig 14 Connection Wiring Diagram 460 3 60 50VT A...

Page 16: ...16 A10195 Fig 14 Cont Ladder Wiring Diagram 460 3 60 50VT A...

Page 17: ...P Checking Cooling and Heating Control Operation Start and check the unit for proper control operation as follows 1 Place room thermostat SYSTEM switch or MODE control in OFF position Observe that blo...

Page 18: ...uctions and adjusted properly ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Disconnect electrical power to the unit and install lockout tag before cha...

Page 19: ...ressure 3 Select speed tap from Table 4 that will achieve required airflow from Table 2 4 Remove the vinyl cap off of the desired speed tap wire Refer to Table 3 for color coding 5 Connect the desired...

Page 20: ...he Heating mode Defrost The defrost control is a time temperature control which includes a field selectable time period DIP switch 1 and 2 on the board between defrost cycles of 30 60 90 or 120 minute...

Page 21: ...ack cfm 2461 2409 2339 2286 2192 2140 2062 1968 1874 50VT A60 Low Blue cfm 1445 1389 1341 1281 1236 1189 1139 1072 1027 Med Low Pink cfm 1678 1635 1602 1558 1513 1474 1438 1404 1349 Medium 1 Red cfm 1...

Page 22: ...0 10 0 12 0 13 0 15 0 17 0 18 0 20 0 23 Table 9 Electric Heat Pressure Drop Table in W C Small Cabinet 24 36 STATIC STANDARD CFM SCFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 5kw 0 00 0...

Page 23: ...air filter s at least once each month and replace throwaway type or clean cleanable type at least twice during each cooling season and twice during the heating season or whenever the filter becomes cl...

Page 24: ...24 A09412 Fig 18 Cooling Charging Table Subcooling 50VT A...

Page 25: ...OF2 OF1 ON QUIET SHIFT 120 30 60 60 30 90 INTERVAL TIMER OFF P3 DFT O R W 2 Y C T2 C C O DFT T1 Y P1 J1 SPEEDUP Speedup Pins Defrost interval DIP switches Quiet Shift A08020 Fig 19 Defrost Control 50V...

Page 26: ...trical Controls and Wiring Inspect and check the electrical controls and wiring annually Be sure to turn off the electrical power to the unit Remove access panels see Fig 22 to locate all the electric...

Page 27: ...gerant System This step covers the refrigerant system of the 50VT A including the compressor oil needed servicing systems on roofs containing synthetic materials the filter drier and refrigerant charg...

Page 28: ...ch must be removed remove and recover all system charge so that pressure gauges read 0 psig Never open system without breaking vacuum with dry nitrogen Check Defrost Thermostat The defrost thermostat...

Page 29: ...ils S Vacuum pumps will not remove moisture from oil S Do not use liquid line filter driers with rated working pressures less than 600 psig S Do not leave Puron suction line filter driers in line long...

Page 30: ...efective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace thermostat Faulty condenser fan motor or capacitor Replace Restriction in refrigerant syst...

Page 31: ...D IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE COMPRESSOR AMPS INDOOR EVA...

Page 32: ...S 7310 W Morris St S Indianapolis IN 46231 Edition Date 01 11 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 50VT 0...