Puron (R--410A) Refrigerant Charging

Refer to unit information plate and charging chart. Some R--410A

refrigerant cylinders contain a dip tube to allow liquid refrigerant to
flow from cylinder in upright position. For cylinders equipped

with a dip tube, charge Puron units with cylinder in upright
position and a commercial metering device in manifold hose.

Charge refrigerant into suction--line.

Step 13 — System Information

Loss of Charge Switch

The loss of charge switch is a protective device wired into control
circuit (low voltage). It shuts off the compressor if abnormally low

pressures are present in the refrigeration circuit.

NOTE

:

Because these switches are attached to refrigeration

system under pressure, it is not advisable to remove this device for
troubleshooting unless you are reasonably certain that a problem
exists. If switch must be removed, remove and recover all system
charge so that pressure gauges read 0 psig. Never open system
without breaking vacuum with dry nitrogen.

Check Defrost Thermostat

The defrost thermostat is usually located on the lowest liquid
leaving circuit of the left condenser coil (see Fig. 22). The

thermostat closes at 32

_

F (0

_

C) and opens at 65

_

F (18

_

C).

The defrost thermostat signals heat pump that conditions are right
for defrost or that conditions have changed to terminate defrost. It

is a thermally actuated switch clamped to outdoor coil to sense its
temperature. Normal temperature range is closed at 32

_

3

_

F (0

1.7

_

C) and open at 65

_

5

_

F (18

2.8

_

C).

NOTE

: The defrost thermostat must be located on the liquid side

of the outdoor coil on the bottom circuit and as close to the coil as
possible.

FEEDER TUBE

STUB TUBE

DEFROST

THERMOSTAT

C99029

Fig. 22 -- Defrost Thermostat

TROUBLESHOOTING

Refer to the Cooling and Heating Troubleshooting Chart (Table

10) for troubleshooting information.

START--UP CHECKLIST

Use the Start--Up Checklist.

50V

T

--

A

Summary of Contents for COMFORT 50VT-A

Page 1: ...ndensate Drain Pan 26 Outdoor Fan 26 Electrical Controls and Wiring 26 Refrigerant Circuit 26 Indoor Airflow 26 Metering Devices TXV Piston 26 Pressure Switches 27 Loss of Charge Switch 27 High Pressu...

Page 2: ...tructions shipped with curb See Fig 4 Install insulation cant strips roofing and flashing Ductwork must be attached to curb IMPORTANT The gasketing of the unit to the roof curb is critical for a water...

Page 3: ...3 A09410 Fig 2 50VT A24 30 Unit Dimensions 50VT A...

Page 4: ...4 A09411 Fig 3 50VT A36 60 Unit Dimensions 50VT A...

Page 5: ...mm B small common base IN mm B large base IN mm C IN mm D IN mm E IN mm F IN mm G IN mm H IN mm Small or Large CPRFCURB010A00 11 279 10 254 14 356 16 406 47 8 1214 32 4 822 2 7 69 30 6 778 46 1 1170 C...

Page 6: ...adapt to various sizes or kinds of loads 2 Instruction in any special operation or precaution 3 Condition of the load as it relates to operation of the lifting kit such as balance temperature etc Foll...

Page 7: ...commended 4 Seal insulate and weatherproof all external ductwork Seal insulate and cover with a vapor barrier all ductwork passing through conditioned spaces Follow latest Sheet Metal and Air Conditio...

Page 8: ...be using a minimum of field supplied 3 4 in PVC or field supplied 3 4 in copper pipe at outlet end of the 2 in 51 mm trap See Fig 9 Do not undersize the tube Pitch the drain tube downward at a slope o...

Page 9: ...o that they do not interfere with operation of unit A gray wire is standard on 3 phase units for connection to an economizer If an accessory electric heater is installed low voltage leads from heater...

Page 10: ...1000 10 x 10 254 x 254 1 2 1200 11 x 10 279 x 254 3 4 1400 11 x 10 279 x 254 3 4 1600 11 x 10 279 x 254 1 1750 11 x 10 279 x 254 1 High Pressure Switch psig Cutout Reset Auto 650 15 420 25 Loss of Cha...

Page 11: ...11 A11002 Fig 12 Connection Wiring Schematics 208 230 1 60 50VT A...

Page 12: ...12 A11001 Fig 12 Cont Ladder Wiring Schematics 208 230 1 60 50VT A...

Page 13: ...13 A11006 Fig 13 Connection Wiring Schematics 208 230 3 60 50VT A...

Page 14: ...14 A11005 Fig 13 Cont Ladder Wiring Schematics 208 230 3 60 50VT A...

Page 15: ...15 A10195 Fig 14 Connection Wiring Diagram 460 3 60 50VT A...

Page 16: ...16 A10195 Fig 14 Cont Ladder Wiring Diagram 460 3 60 50VT A...

Page 17: ...P Checking Cooling and Heating Control Operation Start and check the unit for proper control operation as follows 1 Place room thermostat SYSTEM switch or MODE control in OFF position Observe that blo...

Page 18: ...uctions and adjusted properly ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Disconnect electrical power to the unit and install lockout tag before cha...

Page 19: ...ressure 3 Select speed tap from Table 4 that will achieve required airflow from Table 2 4 Remove the vinyl cap off of the desired speed tap wire Refer to Table 3 for color coding 5 Connect the desired...

Page 20: ...he Heating mode Defrost The defrost control is a time temperature control which includes a field selectable time period DIP switch 1 and 2 on the board between defrost cycles of 30 60 90 or 120 minute...

Page 21: ...ack cfm 2461 2409 2339 2286 2192 2140 2062 1968 1874 50VT A60 Low Blue cfm 1445 1389 1341 1281 1236 1189 1139 1072 1027 Med Low Pink cfm 1678 1635 1602 1558 1513 1474 1438 1404 1349 Medium 1 Red cfm 1...

Page 22: ...0 10 0 12 0 13 0 15 0 17 0 18 0 20 0 23 Table 9 Electric Heat Pressure Drop Table in W C Small Cabinet 24 36 STATIC STANDARD CFM SCFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 5kw 0 00 0...

Page 23: ...air filter s at least once each month and replace throwaway type or clean cleanable type at least twice during each cooling season and twice during the heating season or whenever the filter becomes cl...

Page 24: ...24 A09412 Fig 18 Cooling Charging Table Subcooling 50VT A...

Page 25: ...OF2 OF1 ON QUIET SHIFT 120 30 60 60 30 90 INTERVAL TIMER OFF P3 DFT O R W 2 Y C T2 C C O DFT T1 Y P1 J1 SPEEDUP Speedup Pins Defrost interval DIP switches Quiet Shift A08020 Fig 19 Defrost Control 50V...

Page 26: ...trical Controls and Wiring Inspect and check the electrical controls and wiring annually Be sure to turn off the electrical power to the unit Remove access panels see Fig 22 to locate all the electric...

Page 27: ...gerant System This step covers the refrigerant system of the 50VT A including the compressor oil needed servicing systems on roofs containing synthetic materials the filter drier and refrigerant charg...

Page 28: ...ch must be removed remove and recover all system charge so that pressure gauges read 0 psig Never open system without breaking vacuum with dry nitrogen Check Defrost Thermostat The defrost thermostat...

Page 29: ...ils S Vacuum pumps will not remove moisture from oil S Do not use liquid line filter driers with rated working pressures less than 600 psig S Do not leave Puron suction line filter driers in line long...

Page 30: ...efective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace thermostat Faulty condenser fan motor or capacitor Replace Restriction in refrigerant syst...

Page 31: ...D IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE COMPRESSOR AMPS INDOOR EVA...

Page 32: ...S 7310 W Morris St S Indianapolis IN 46231 Edition Date 01 11 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 50VT 0...

Reviews: