background image

26

Step 3 — Defrost Control

Quiet Shift

Quiet Shift is a field--selectable defrost mode, which will eliminate

occasional noise that could be heard at the start of defrost cycle and
restarting of heating cycle. It is selected by placing DIP switch 3

(on defrost board) in ON position.
When Quiet Shift switch is placed in ON position, and a defrost is

initiated, the following sequence of operation will occur. Reversing
valve will energize, outdoor fan will turn off, compressor will turn

off for 30 sec and then turn back on to complete defrost. At the

start of heating after conclusion of defrost reversing valve will
de--energize, compressor will turn off for another 30 sec, and the

outdoor fan will stay off for 40 sec, before starting in the Heating
mode.

Defrost

The defrost control is a time/temperature control which includes a

field--selectable time period (DIP switch 1 and 2 on the board)
between defrost cycles of 30, 60, 90, or 120 minutes (factory set at

60 minutes). To initiate a forced defrost, two options are available

depending on the status of the defrost thermostat.
If defrost thermostat is closed, speed--up pins (J1) must be shorted

by placing a flat head screw driver in between for 5 sec and
releasing, to observe a complete defrost cycle. When the Quiet

Shift switch is selected, compressor will be turned off for two 30
sec intervals during this complete defrost cycle, as explained

previously. When Quiet Shift switch is in factory default OFF

position, a normal and complete defrost cycle will be observed.
If defrost thermostat is in open position, and speedup pins are

shorted (with a flat head screw driver) for 5 sec and released, a
short defrost cycle will be observed (actual length is dependent

upon the selected Quiet Shift position). When Quiet Shift switch is

in ON position, the length of defrost is 1 minute (30 sec
compressor off period followed by 30 sec of defrost with

compressor operation). On return to heating operation, compressor
will again turn off for an additional 30 sec and the outdoor fan for

40 sec. When the Quiet Shift is in OFF position, only a brief 30

sec. cycle will be observed.

NOTE

:

Unit will remain in defrost until defrost thermostat

reopens at approximately 65

_

F (18

_

C) coil temperature at liquid

line or remainder of defrost cycle time.

MAINTENANCE

To ensure continuing high performance, and to minimize the

possibility of premature equipment failure, periodic maintenance
must be performed on this equipment. This heat pump unit should

be inspected at least once each year by a qualified service person.
To troubleshoot unit, refer to Table 10.

NOTE

: TO EQUIPMENT OWNER: Consult your local dealer

about the availability of a maintenance contract.

PERSONAL INJURY AND UNIT DAMAGE HAZARD

Failure to follow this warning could result in personal injury

or death and unit component damage.
The ability to properly perform maintenance on this

equipment requires certain expertise, mechanical skills, tools

and equipment. If you do not possess these, do not attempt to

perform any maintenance on this equipment, other than those

procedures recommended in the Owner’s Manual.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow these warnings could result in personal

injury or death:

1. Turn off electrical power to the unit and install a lockout

tag before performing any maintenance or service on this
unit.

2. Use extreme caution when removing panels and parts.
3. Never place anything combustible either on or in contact

with the unit.

!

WARNING

CUT HAZARD

Failure to follow this caution may result in personal injury.
When removing access panels (see Fig. 19.) or performing

maintenance functions inside your unit, be aware of sharp

sheet metal parts and screws. Although special care is taken

to reduce sharp edges to a minimum, be extremely careful

when handling parts or reaching into the unit.

CAUTION

!

UNIT OPERATION HAZARD

Failure to follow this caution may result in improper

operation.
Errors made when reconnecting wires may cause improper

and dangerous operation. Label all wires prior to

disconnecting when servicing.

CAUTION

!

The minimum maintenance requirements for this equipment are as
follows:

1. Inspect air filter(s) each month. Clean or replace when

necessary.

2. Inspect indoor coil, drain pan, and condensate drain each

cooling season for cleanliness. Clean when necessary.

3. Inspect blower motor and wheel for cleanliness each

cooling season. Clean when necessary.

4. Check electrical connections for tightness and controls for

proper operation each cooling season. Service when
necessary.

Step 1 — Air Filter

IMPORTANT

: Never operate the unit without a suitable air filter

in the return--air duct system. Always replace the filter with the
same dimensional size and type as originally installed. See Table 1
for recommended filter sizes.
Inspect air filter(s) at least once each month and replace

(throwaway--type) or clean (cleanable--type) at least twice during
each cooling season and twice during the heating season, or

whenever the filter becomes clogged with dust and lint.

Indoor Blower and Motor

NOTE

: All motors are pre--lubricated. Do not attempt to lubricate

these motors.

NOTE

: 460 volt units have a stepdown autotransformer that

supplies approximately 230 volts to a nominal 230 volt indoor
blower motor.
For longer life, operating economy, and continuing efficiency,

clean accumulated dirt and grease from the blower wheel and
motor annually.

50E

Z

--

A

Summary of Contents for COMFORT 50EZ-A30

Page 1: ...or 28 Outdoor Coil Indoor Coil Condensate Drain Pan 29 Outdoor Fan 29 Electrical Controls and Wiring 31 Refrigerant Circuit 31 Indoor Airflow 32 A09034 Fig 1 Unit 50EZ A Metering Devices TXV Piston 32...

Page 2: ...e and into the unit base rails When installing large base units onto the common curb the screws must be installed before allowing the full weight of the unit to rest on the curb A minimum of six screw...

Page 3: ...lifter to the load and adjustment of the lifts to adapt to various sizes or kinds of loads 2 Instruction in any special operation or precaution 3 Condition of the load as it relates to operation of th...

Page 4: ...4 A150587 Fig 2 50EZ A30 36 Unit Dimensions 50EZ A...

Page 5: ...5 A150588 Fig 3 50EZ A42 60 Unit Dimensions 50EZ A...

Page 6: ...B large base IN mm C IN mm D IN mm E IN mm F IN mm G IN mm H IN mm Small or Large CPRFCURB010A00 11 279 10 254 14 356 16 406 47 8 1214 32 4 822 2 7 69 30 6 778 46 1 1170 CPRFCURB011A00 14 356 Large C...

Page 7: ...l supporting unit WARNING Lifting holes are provided in base rails as shown in Fig 2 and 3 1 Leave top shipping skid on the unit for use as a spreader bar to prevent the rigging straps from damaging t...

Page 8: ...Association SMACNA and Air Conditioning Contractors Association ACCA minimum installation standards for residential heating and air conditioning systems 5 Secure all ducts to building structure Flash...

Page 9: ...oltage and or phase imbalance 4 Do not damage internal components when drilling through any panel to mount electrical hardware conduit etc CAUTION ELECTRICAL SHOCK HAZARD Failure to follow this warnin...

Page 10: ...do not have a matching receptacle cut the 24V wires from the electric heater plug strip the ends and wire nut together to match the schematic connections If the electric heater 24V wires do not have a...

Page 11: ...e in mm Motor HP 1000 10x10 254x254 1 2 1200 11x10 279x254 3 4 1400 11x10 279x254 3 4 1600 11x10 279x254 1 0 1800 11x10 279x254 1 0 HIGH PRESSURE SWITCH psig Cutout Reset Auto 650 15 420 25 LOSS OF CH...

Page 12: ...12 A11006 Fig 11 Connection Wiring Schematics 208 230 3 60 50EZ A...

Page 13: ...13 A11005 Fig 11 Cont Ladder Wiring Schematics 208 230 3 60 50EZ A...

Page 14: ...14 A10195 Fig 12 Connection Wiring Diagram 460 3 60 50EZ A...

Page 15: ...15 A10195 Fig 12 Cont Ladder Wiring Diagram 460 3 60 50EZ A...

Page 16: ...ontrol in OFF position Observe that blower motor starts when FAN mode is placed in FAN ON position and shuts down when FAN MODE switch is placed in AUTO position 2 Thermostat When the room temperature...

Page 17: ...minimum of 15 minutes before checking or adjusting refrigerant charge IMPORTANT When evaluating the refrigerant charge an indicated adjustment to the specified factory charge must always be very mini...

Page 18: ...f of the desired speed tap wire Refer to Table 3 for color coding for the normal cooling fan speed and place desired speed tap wire on HIGH on the interface board 5 Refer to airflow tables Table 4 to...

Page 19: ...AL2 DCR QCR QC1 C RL 01 G1 G2 Z1 A7 R9 AB A15 C4 C9 C0 QIL Z2 06 04 U1 C3 R4 RL4 JWZ C7 D5 D3 R3 R5 R6 R2 JW5 QCB Y R W2 Y C W3 W3 W2 W2 C JW4 P2 JW3 P4 P1 W2 W3 Y2 Y1 Y DH G C R SSTZ 8 P3 SDL 24VAC...

Page 20: ...1449 1411 1362 1313 1278 1231 1188 High Black CFM 1705 1643 1607 1568 1518 1483 1448 1404 1360 50EZ A48 Low Blue CFM 1402 1351 1311 1263 1224 1172 1136 1080 1041 Med Low Pink CFM 1457 1404 1367 1318...

Page 21: ...274 284 295 302 315 327 331 BHP 0 27 0 29 0 29 0 30 0 32 0 32 0 34 0 35 0 35 50EZ A36 Low Blue CFM 1277 1215 1147 1094 1045 992 932 874 826 757 WATTS 285 289 299 305 314 319 328 335 347 352 BHP 0 31 0...

Page 22: ...1 0 42 0 44 High Black CFM 1775 1736 1696 1660 1622 1588 1557 1516 1472 1426 WATTS 371 386 401 410 424 439 453 468 483 497 BHP 0 40 0 41 0 43 0 44 0 45 0 47 0 49 0 50 0 52 0 53 50EZ A48 Low Blue CFM 1...

Page 23: ...S 569 579 597 607 623 639 648 665 674 663 BHP 0 61 0 62 0 64 0 65 0 67 0 69 0 69 0 71 0 72 0 71 MedHigh Orange CFM 2178 2148 2105 2073 2036 2002 1967 1919 1845 1751 WATTS 674 691 703 717 733 743 758 7...

Page 24: ...FM 12x20x1 12x20x1 305x508x25 305x508x25 2 5 3 0 0 09 0 14 0 16 0 18 0 25 0 28 0 3 1200 1800 CFM 16x24x1 14x24x1 406x610x25 356x610x25 3 5 4 0 0 10 0 11 0 12 0 13 0 14 0 16 0 16 1500 2200 CFM 16x24x1...

Page 25: ...0 00 0 02 0 04 0 06 0 08 0 09 0 11 0 13 0 15 0 17 0 19 Electric Heat Pressure Drop Table IN W C Large Cabinet 42 60 STANDARD CFM SCFM 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2...

Page 26: ...O EQUIPMENT OWNER Consult your local dealer about the availability of a maintenance contract PERSONAL INJURY AND UNIT DAMAGE HAZARD Failure to follow this warning could result in personal injury or de...

Page 27: ...cycles Step 2 Outdoor Coil Indoor Coil and Condensate Drain Pan Inspect the condenser coil evaporator coil and condensate drain pan at least once each year The coils are easily cleaned when dry theref...

Page 28: ...28 B A150586 Fig 16 Cooling Charging Table Subcooling 50EZ A...

Page 29: ...trols and wiring replace all the panels Start the unit and observe at least one complete cooling cycle to ensure proper operation If discrepancies are observed in operating cycle or if a suspected mal...

Page 30: ...h Step 11 Copeland Scroll Compressor Puron Refrigerant The compressor used in this product is specifically designed to operate with Puron R 410A refrigerant and cannot be interchanged EXPLOSION HAZARD...

Page 31: ...n a dip tube to allow liquid refrigerant to flow from cylinder in upright position For cylinders equipped with a dip tube charge Puron units with cylinder in upright position and a commercial metering...

Page 32: ...ctive run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace thermostat Faulty condenser fan motor or capacitor Replace Restriction in refrigerant system...

Page 33: ...ls S Vacuum pumps will not remove moisture from oil S Do not use liquid line filter driers with rated working pressures less than 600 psig S Do not leave Puron suction line filter driers in line longe...

Page 34: ...TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE COMPRESSOR AMPS INDOOR EVAPORATOR FAN AMPS TEMPERATURES OUTDOOR CONDENSER AIR TEMPERATURE DB RETURN AIR TEMPERATURE DB WB COOLING SUPPLY AIR DB WB HEA...

Reviews: