REFRIGERANT PIPING LENGTH LIMITATIONS

Maximum Line Lengths:

The maximum allowable total equivalent length for heat pumps varies depending on the vertical separation. See the tables below for

allowable lengths depending on whether the outdoor unit is on the same level, above or below the outdoor unit.

Maximum Line Lengths for Heat Pump Applications

MAXIMUM ACTUAL LENGTH

ft (m)

MAXIMUM EQUIVALENT LENGTH

{

ft (m)

MAXIMUM VERTICAL

SEPARATION ft (m)

Units on equal level

200 (61)

250 (76.2)

N/A

Outdoor unit ABOVE

indoor unit

200 (61)

250 (76.2)

200 (61)

Outdoor unit BELOW

indoor unit

See Table ’

Maximum Total Equivalent Length: Outdoor Unit BELOW Indoor Unit’

{

Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.

Maximum Total Equivalent Length

{

-- Outdoor Unit BELOW Indoor Unit

Size

Liquid Line

Diameter

w/ TXV

HP with Puron

r

Refrigerant --- Maximum Total Equivalent Length

{

Vertical Separation ft (m) Outdoor unit BELOW indoor unit;

0---20

(0 --- 6.1)

21---30

(6.4 --- 9.1)

31---40

(9.4 --- 12.2)

41---50

(12.5 --- 15.2)

51---60

(15.5 --- 18.3)

61---70

(18.6 --- 21.3)

71---80

(21.6 --- 24.4)

18000

HP with

Puron

3/8

250*

250*

250*

250*

250*

250*

250*

24000

HP with

Puron

3/8

250*

250*

250*

250*

250*

250*

250*

30000

HP with

Puron

3/8

250*

250*

250*

250*

250*

250*

250*

36000

HP with

Puron

3/8

250*

250*

250*

250*

250*

250*

250*

42000

HP with

Puron

3/8

250*

250*

250*

250*

250*

250*

150

48000

HP with

Puron

3/8

250*

250*

250*

250*

230

160

--- ---

60000

HP with

Puron

3/8

250*

225*

190

150

110

--- ---

--- ---

* Maximum actual length not to exceed 200 ft (61 m)

{

Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.

--- --- = outside acceptable range

LONG LINE APPLICATIONS

An application is considered Long Line when the refrigerant level in the system requires the use of accessories to maintain acceptable
refrigerant management for systems reliability. Defining a system as long line depends on the liquid line diameter, actual length of the tubing,

and vertical separation between the indoor and outdoor units.
For Heat Pump systems, the chart below shows when an application is considered Long Line. Beyond these lengths, long line accessories

are required:

HP WITH PURON

r

REFRIGERANT LONG LINE DESCRIPTION ft (m)

Beyond these lengths, long line accessories are required

Liquid Line Size

Units On Same Level

Outdoor Below Indoor

Outdoor Above Indoor

3/8

80 (24.4)

20 (6.1) vertical or 80 (24.4) total

80 (24.4)

Note:

See Long Line Guideline for details

25H

C

D

4

Summary of Contents for Comfort 25HCD4

Page 1: ...ratings information INDUSTRY LEADING FEATURES BENEFITS Efficiency S 14 SEER S Microtube Technologyt refrigeration system S Indoor air quality accessories available Sound S Sound level as low as 69 dB...

Page 2: ...all manufacturing refrigerant charging and air flow instructions Failure to confirm proper charge and air flow may reduce energy efficiency and shorten equipment life Use of the AHRI Certified TM Mark...

Page 3: ...Cooling Capacity Losses Puronr Refrigerant 1 Stage Heat Pump Applications Unit Nominal Size Btuh Maximum Liquid Line Diameters In OD Vapor Line Diameters In OD Cooling Capacity Loss Total Equivalent...

Page 4: ...0 250 250 250 250 24000 HP with Puron 3 8 250 250 250 250 250 250 250 30000 HP with Puron 3 8 250 250 250 250 250 250 250 36000 HP with Puron 3 8 250 250 250 250 250 250 250 42000 HP with Puron 3 8 25...

Page 5: ...X X X X X KSASH2101COP SOUND BLKT KIT X KSASF0101AAA SPRT FEET KIT X X X X X X KAATD0101TDR TIME DELAY KIT X X X X X X KSATX0201PUR TXV KIT X X X KSATX0301PUR TXV KIT X X KSATX0501PUR TXV KIT X x Acce...

Page 6: ...mproves compressor lubrication on restart and minimizes the chance of liquid slugging Usage Guideline Required in low ambient cooling applications Required in long line applications Suggested in all c...

Page 7: ...allow for drainage from unit base Usage Guideline Suggested in the following applications Heat pump installations in heavy snowfall areas Heat pump installations in snow drift locations Heat pump ins...

Page 8: ...TE Control circuit is 24 V on all units and requires external power source Copper wire must be used from service disconnect to unit All motors compressors contain internal overload protection Complies...

Page 9: ...9 DIMENSIONS ENGLISH 25HCD4...

Page 10: ...10 DIMENSIONS SI 25HCD4...

Page 11: ...Y MBTUH 25HCD424A30 FB4CNF030 25HCD442A30 FB4CNF048 25HCD430A30 FB4CNF030 25HCD448A30 FB4CNF060 25HCD436A30 FB4CNF036 25HCD460A30 FX4DNF061 25HCD418A30 FB4CNF018 23 3 17 8 12 2 6 7 1 1 4 4 10 0 15 6 2...

Page 12: ...2 24 609 6 Service 6 152 4 12 304 8 24 609 6 Service 24 609 6 Service 24 609 6 Service Note Numbers in mm 18 457 2 18 457 2 12 304 8 IMPORTANT When installing multiple units in an alcove roof well or...

Page 13: ...TBA TBA TBA 14 0 TBD TBA TBA TBA TBA 25HCD436 31 TBA TBA TBA TBA 14 0 TBD TBA TBA TBA TBA 25HCD442 30 TBA TBA TBA TBA 14 0 TBD TBA TBA TBA TBA 25HCD448 30 TBA TBA TBA TBA 14 0 TBD TBA TBA TBA TBA 25H...

Page 14: ...r fan will be direct drive propeller type discharging air upward Condenser fan motors will be totally enclosed 1 phase type with class B insulation and permanently lubricated bearings Shafts will be c...

Page 15: ...rconnecting refrigerant tube lengths greater than 80 ft 23 4 m and or elevation differences between indoor and outdoor units greater than 20 ft 6 1 m consult Residential Piping and Longline Guideline...

Page 16: ...rp S 7310 W Morris St S Indianapolis IN 46231 Edition Date 02 13 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 25HC...

Reviews: