background image

7

4. Fit refrigerant lines into coil stubs. Wrap a heat sinking

material such as a wet cloth behind braze joints.

5. Wrap TXV and nearby tubing with a heat

sinking material

such as a wet cloth.

6. Use 1/2 psig Nitrogen purge in the suction and out the

liquid line.

7. Braze using a Sil

Fos or Phos

copper alloy. Do not use soft

solder.

8. After brazing, allow joints to cool. Carefully remove TXV

bulb insulation and verify that the TXV bulb is securely

fastened with hose clamp. Tighten screw a half

turn past

hand tight with TXV bulb placed in the indentation with

full contact with the vapor line tube. Re

wrap TXV bulb

with insulation.

9. Leak check connections before insulating entire suction

line.

10. Slide tubing plate with rubber grommets over joints.

Position tubing at center of each grommet to ensure an air

seal around the tube. Reinstall cabinet door.

PRODUCT DAMAGE HAZARD

Failure to follow this caution may result in product or property

damage.
To avoid damage to the refrigerant control device while

brazing, wrap tubing or fittings with a heat

sinking material

such as a wet cloth.

CAUTION

!

PERSONAL INJURY HAZARD

Failure to follow this warning could result in personal injury.
Wear eye protection.
Coil is factory charged with 15 psi nitrogen.  The coil is under

pressure and TXV screen is in place behind liquid line plug.

DO NOT removed liquid line plug first; always remove the

suction line plug first to depressurize the coil.

!

WARNING

REFRIGERANT METERING DEVICE

CNPVU Models:
These coils have a factory

installed hard

shutoff TXV designed

only for use with Puron refrigerant (R

410A). Use only with

outdoor units designed for R

410A.

CNRVU Models:
These coils have a factory

installed hard

shutoff TXV designed

only for use with R

22 refrigerant. Use only with outdoor units

designed for R

22.

NOTE

:  ALL TXVs HAVE PRESET SUPERHEAT SETTINGS

AND ARE FIELD 

NON

ADJUSTABLE

.

Procedure 6 — Condensate Drain Line

Connection

PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in property damage.
When installing over a finished ceiling and/or living area,

install a field

fabricated secondary condensate pan under the

entire unit.

CAUTION

!

The coil is designed to dispose of accumulated water through

built

in condensate drain fittings. It is recommended that PVC

fittings be used on the condensate pan. Do not over

tighten. Finger

tighten plus 1

1/2 turns. Be sure to install plastic plug in unused

condensate drain fitting. Two 3/4

in. female threaded pipe

connections are provided in each coil condensate pan.
A trap is not necessary on the condensate line. Consult local codes

for additional restrictions or precautions. If local codes require a

trap then the following guidelines are suggested to assure proper

drainage. Install a trap in condensate line of coil as close to the coil

as possible. Make trap at least 3 in. (76 mm) deep and no higher

than the bottom of unit condensate drain opening (See Fig. 15).

Pitch condensate line 1 in. (25.4 mm) for every 10 ft. of length to

an open drain or sump. Make sure that the outlet of each trap is

below its connection to condensate pan to prevent condensate from

overflowing the drain pan. Prime all traps, test for leaks, and

insulate traps and lines if located above a living area.

3” / 76mm

A08067

Fig. 15 

 

Condensate Trap

NOTE

:  If unit is located in or above a living space, where damage

may result from condensate overflow, a field

supplied, external

condensate pan should be installed underneath the entire unit, and a
secondary condensate line (with appropriate trap) should be run
from the unit into the pan. Any condensate in this external
condensate pan should be drained to a noticeable place. As an
alternative to using an external condensate pan, some localities
may allow the running of a separate 3/4

in. (19 mm) condensate

line (with appropriate trap) per local code to a place where the
condensate will be noticeable. The owner of the structure must be
informed that when condensate flows from secondary drain or
external condensate pan, the unit requires servicing or water
damage will occur. To further protect against water damage, install
a float switch to shut the unit off if the water in the secondary pan
gets too high.

NOTE

:  To avoid drainage problems, test the primary drain line by

slowly pouring water into the pan. Check piping for leaks and
proper condensate drainage. Using the secondary drain as

Summary of Contents for CNPVU1814ACA

Page 1: ...he potential for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will res...

Page 2: ...ith R 22 refrigerant Use only with outdoor units designed for R 22 NOTE All TXVs have preset superheat settings and are not field adjustable Airflow Airflow amount and distribution are vital to adequa...

Page 3: ...VU37171A C T L A 3 19 1 8 16 3 4 19 3 8 16 1 4 3 8 7 8 KCAKC3201ECC CNPVU4221A C T L A 3 1 2 19 1 8 20 1 4 19 3 8 19 5 8 3 8 7 8 KCAKC2801ECC CNPVU4324A C T L A 3 1 2 19 1 8 23 3 4 19 3 8 23 1 8 3 8 7...

Page 4: ...remature failure CAUTION CUT HAZARD Failure to follow this caution may result in personal injury Sheet metal parts may have sharp edges or burrs Use care and wear appropriate protective clothing and g...

Page 5: ...old N coil from casing and discard coil 3 Slide new N coil into casing 4 Cut holes for liquid suction and drain connections in the existing header panel Use new header plate supplied with coil as tem...

Page 6: ...t seal and better installation presentation 7 Seal all joints to create air tight seal using locally approved materials IMPORTANT Locate caution label stapled to installation instructions Attach to ri...

Page 7: ...fabricated secondary condensate pan under the entire unit CAUTION The coil is designed to dispose of accumulated water through built in condensate drain fittings It is recommended that PVC fittings b...

Page 8: ...removed from their casing and applied dir ectly into the plenum affix this Caution Label to the right side of the plenum enclosure This is needed only in cases where the humidifier is not installed w...

Reviews: