background image

6

2. Remove old A

coil from plenum and discard coil.

3. Place 

collar

 over furnace flanges inside of plenum (See Fig.

1).

IMPORTANT

: Insure that

 collar 

is level for proper drainage.

4. Remove front and rear 

extension air baffles

 from new

N

coil.

5. Slide new N

coil into plenum.

6. Cut holes for liquid, suction and drain connections in the

existing field

fabricated front access panel of plenum on

fabricated new panel. Use 

header plate 

supplied with coil

as template to locate holes.

7. Slide 

header plate

 and 

grommets 

over tubing and con-

densate pan connections and secure it to the plenum front

access to cover up oversized and additional holes. This will

provide an airtight seal and better installation presentation.

8. Seal all joints to create air tight seal using locally approved

materials.

3D. Upflow and downflow applications using KCAKC N

coil

casing. See Table 1 and 2 for proper kit casing model number

match

up.

1. Remove and keep front access and tubing header panel.

IMPORTANT

: Insure that

 collar 

is level for proper drainage.

2. Slide new N

coil into casing.

3. Cut holes for liquid and suction connections in the existing

header panel. Use 

header plate 

supplied with coil as tem-

plate to locate holes. Align header plate to header panel us-

ing the upper hole as indicated in Fig. 11.

4. Slide header panel over tubing and condensate pan connec-

tions. Secure header panel to casing.

5. Cut bottom portion of 

header plate

, just below the drain

connections. See Fig. 12.

6. Slide 

header plate

 and 

grommets

 over tubing and con-

densate pan connections and secure it to the fitting plate to

cover up oversized and additional holes. This will provide

an airtight seal and better installation presentation.

7. Reinstall and secure front access panel to casing.

3E. Upflow and downflow applications using a new field

fabricated plenum installation.

For uncased N

coil CNPVU/CNRVU width and depth dimensions

See Table 1 and 2. Fabricate plenum accordingly.

1. Mount 

collar

 directly on furnace flanges to support the coil.

2. Remove front and rear extension 

air baffles

 from new

N

coil.

3. Slide new N

coil into plenum opening.

4. Cut holes for liquid, suction connections in field 

fabricated

front plenum panel. Use 

header plate

 supplied as template

to locate holes.

5. Cover plenum opening with field

fabricated front plenum

panel.

6. Slide 

header plate

 and 

grommets

 over tubing and con-

densate pan connections and secure it to the field fabricated

front plenum panel to cover up oversized holes. This will

provide an airtight seal and better installation presentation.

7. Seal all joints to create air tight seal using locally approved

materials.

IMPORTANT

: Locate caution label stapled to installation

instructions. Attach to right side of plenum or accessory casing
(See Fig. 14).

AIR CONDITIONING COIL BEHIND THIS

PANEL. DO NOT DRILL OR CUT PANEL

UNTIL COIL LOCATION HAS BEEN

VERIFIED BY REMOVING ACCESS

COVER.

CAUTION

A06285

Fig. 14 

 

Plenum Caution Label

NOTE

:  The uncased N

coil features an enclosure to direct airflow

through the third coil slab.

NOTE

:  If coil is not being installed in the standard orientation

(front of coil matching front of furnace) then coil must be raised
2

1/4 in. above furnace.

NOTE

:  Installing coils rotated 90

_

 from the front of the furnace,

in upflow or downflow applications, can cause water blow

off or

coil freeze

up due to the concentration of air on one slab of the coil

or lack of air to a slab in the coil. It is recommended that on this
type of application, a field

supplied adapter be placed between the

coil and furnace to allow air to distribute properly between all slabs
of the coil.

Procedure 4 — Refrigerant Line Connections

Use accessory tubing package or field

supplied tubing of

refrigerant grade. Suction tube must be insulated. Do not use

damaged, dirty, or contaminated tubing because it may plug

refrigerant flow

control device. ALWAYS evacuate the coil and

field

supplied tubing before opening outdoor unit service valves.

Procedure 5 — Connect Refrigerant Liquid and

Suction Lines

SUCTION LINE

Suction line is designed for field sweat connection. Line is plugged

to keep out moisture and dirt. Remove these plugs only when

ready to make connection.
See Table 1 and 2 for coil connection tube size.
For matched and mismatched systems, use line sizes recommended

in outdoor unit Installation Instructions.

UNIT OR PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in property damage.
Take precautions to ensure aluminum tubes do not come in

direct contact or allow for condensate run

off with a dissimilar

metal.  Dissimilar metals can cause galvanic corrosion and

possible premature failure.

CAUTION

!

The coil can be connected to outdoor units using field

supplied

tubing of refrigerant grade. Always evacuate tubing and reclaim

refrigerant when making connections or flaring tubing. Leak check

connections before insulating entire suction line.

1. Remove cabinet access door.
2. Remove rubber plugs, suction plug then liquid plug, from

coil stubs using a pulling and twisting motion. Hold coil

stubs steady to avoid bending or distorting.

3. Remove tubing plate with rubber grommets and slide plate

with grommets onto the refrigerant lines (field line

set),

away from braze joints.

Summary of Contents for CNPVU1814ACA

Page 1: ...he potential for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will res...

Page 2: ...ith R 22 refrigerant Use only with outdoor units designed for R 22 NOTE All TXVs have preset superheat settings and are not field adjustable Airflow Airflow amount and distribution are vital to adequa...

Page 3: ...VU37171A C T L A 3 19 1 8 16 3 4 19 3 8 16 1 4 3 8 7 8 KCAKC3201ECC CNPVU4221A C T L A 3 1 2 19 1 8 20 1 4 19 3 8 19 5 8 3 8 7 8 KCAKC2801ECC CNPVU4324A C T L A 3 1 2 19 1 8 23 3 4 19 3 8 23 1 8 3 8 7...

Page 4: ...remature failure CAUTION CUT HAZARD Failure to follow this caution may result in personal injury Sheet metal parts may have sharp edges or burrs Use care and wear appropriate protective clothing and g...

Page 5: ...old N coil from casing and discard coil 3 Slide new N coil into casing 4 Cut holes for liquid suction and drain connections in the existing header panel Use new header plate supplied with coil as tem...

Page 6: ...t seal and better installation presentation 7 Seal all joints to create air tight seal using locally approved materials IMPORTANT Locate caution label stapled to installation instructions Attach to ri...

Page 7: ...fabricated secondary condensate pan under the entire unit CAUTION The coil is designed to dispose of accumulated water through built in condensate drain fittings It is recommended that PVC fittings b...

Page 8: ...removed from their casing and applied dir ectly into the plenum affix this Caution Label to the right side of the plenum enclosure This is needed only in cases where the humidifier is not installed w...

Reviews: