INSTALLATION

These units can be installed in either upflow or downflow

configurations. Before installation, there are several performance

requirements that must be considered because poor installation can

negatively alter performance. This section will briefly discuss those

factors.

TXV

A thermal expansion valve is utilized in this coil design to optimize

performance and comfort throughout the entire operating range of

the system. Special attention needs to be taken to the TXV when

installing the coil

S

Do not overheat valve. Temperatures that exceed 212

_

F (100

_

C)

can harm valve performance. Use a wet cloth or heat sink when
brazing.

S

Place filter dryer near ID unit to reduce the risk of debris
clogging the valve.

S

Make sure TXV bulb is securely fastened and wrapped in the
indentation on heater tube.

CNPVU Models:
These coils have a factory

installed hard

shutoff TXV designed

only for use with R

410A refrigerant. Use only with outdoor units

designed for R

410A.

CNRVU Models:
These coils have a factory

installed hard

shutoff TXV designed

only for use with R

22 refrigerant. Use only with outdoor units

designed for R

22.

NOTE

:  All TXVs have preset superheat settings and are not

field

adjustable.

Airflow

Airflow amount and distribution are vital to adequate system

performance. Problems that can be experienced with incorrect

airflow include:

S

low system performance

S

restricted TXV

S

frosted coil

S

poor humidity control

S

water blow

off

When attaching the coil and building the plenum, pay special

attention to the effect these details will have on airflow. After

system start

up, check the cfm to insure that it is correct.

(Generally, the cfm should be 350 to 400 cfm/ton during normal

cooling operation.)

Condensate Management

With proper installation, these coils will manage the condensate

without blow

off into the duct work. See detailed instructions for

more info.

Procedure 1 — Inspect Equipment

File claim with shipper if equipment is damaged.
The following parts are included with this coil (See Fig. 1),

depending on your application different components will be

required.

COMPONENT

QUANTITY

Support Rails

2

Collar

1

Header Plate

1

Grommets

2

Extension Air Baffles

2

Uncased N-coil

Support Rails
2 pcs.

Collar
1 pc.

Header Plate
1 pc.

Extension Air Baffles
2 pcs. (Attached to coil)

A06362

Fig. 1 

 

Uncased N

Coil Components

Summary of Contents for CNPVU1814ACA

Page 1: ...he potential for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will res...

Page 2: ...ith R 22 refrigerant Use only with outdoor units designed for R 22 NOTE All TXVs have preset superheat settings and are not field adjustable Airflow Airflow amount and distribution are vital to adequa...

Page 3: ...VU37171A C T L A 3 19 1 8 16 3 4 19 3 8 16 1 4 3 8 7 8 KCAKC3201ECC CNPVU4221A C T L A 3 1 2 19 1 8 20 1 4 19 3 8 19 5 8 3 8 7 8 KCAKC2801ECC CNPVU4324A C T L A 3 1 2 19 1 8 23 3 4 19 3 8 23 1 8 3 8 7...

Page 4: ...remature failure CAUTION CUT HAZARD Failure to follow this caution may result in personal injury Sheet metal parts may have sharp edges or burrs Use care and wear appropriate protective clothing and g...

Page 5: ...old N coil from casing and discard coil 3 Slide new N coil into casing 4 Cut holes for liquid suction and drain connections in the existing header panel Use new header plate supplied with coil as tem...

Page 6: ...t seal and better installation presentation 7 Seal all joints to create air tight seal using locally approved materials IMPORTANT Locate caution label stapled to installation instructions Attach to ri...

Page 7: ...fabricated secondary condensate pan under the entire unit CAUTION The coil is designed to dispose of accumulated water through built in condensate drain fittings It is recommended that PVC fittings b...