ARE ORIFICES IN
NEGATIVE PRESSURE
HOSE CLEAR?
CLEAN OUT BLOCKAGE
AT ORIFICES
CHART 1
OPEN
BLOWER STARTS
PURGE LIGHT ON?
CHECK FOR 120 VAC
BETWEEN TERMINALS 1
AND 3 AT CONNECTOR
CN4 ON IBC
REPLACE IBC
CHECK FOR 120 VAC AT
BLOWER LEADS
ON WIRING HARNESS
REPAIR/REPLACE
WIRING FROM IBC
TO DRAFT INDUCER
REPAIR/REPLACE
BLOWER
CONTACTS OPEN
IBC WAITS UP TO 5
MINUTES FOR NORMALLY
OPEN AIR PRESSURE
SWITCH CONTACTS TO
CLOSE, INDICATING
BLOWER SUCTION
IS PRESENT
ARE VENT PIPE AND
AIR INTAKE PIPE CLEAR
(NO BLOCKAGE)
CLEAN OUT VENT PIPE
AND/OR AIR INTAKE PIPE.
CHECK FOR SAGS OR
LOW SPOTS WHERE
CONDENSATE MAY PUDDLE
AND BLOCK THE VENT
CHECK AIR PRESSURE
SWITCH PER
INSTRUCTIONS ON
FOLLOWING PAGES. ARE
SAMPLING LINES CLEAR
AND CONNECTED
PROPERLY?
CLEAN OUT SAMPLING
LINES OR REPLACE
DEFECTIVE SWITCH
CHECK FLUE PASSAGES
IN BOILER PER
MAINTENANCE AND
CLEANING . ARE FLUE
PASSAGES IN BOILER
CLEAN?
CLEAN BOILER FLUE
PASSAGES PER
MAINTENANCE AND
CLEANING INSTRUCTIONS
CHECK DRAFT INDUCER
MOTOR RPM. IS IT
3400-3600?
CHECK FOR BROKEN OR
LOOSE IMPELLER ON
DRAFT INDUCER AND
REPLACE BLOWER
IF FOUND TO BE
BROKEN OR LOOSE
REPLACE BLOWER
REPLACE IBC
15 SECOND PRE PURGE COMPLETE.
PURGE LIGHT OFF. SIMULTANEOUSLY
IGNITER LIGHT IS ON AS IGNITOR
CIRCUIT IS ENERGIZED
CHART 4
TROUBLESHOOTING
TROUBLE SHOOTING CHART 3
YES
NO
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
YES
YES
YES
YES
NO
NO
NO
A06155
Fig. 29
---
Troubleshooting Chart No. 3