background image

4

DEADBAND (Step 5) — The deadband is the difference in

temperature above the cooling set point or below the heating

set point that the thermostat will wait before turning on the first

stage of heating or cooling. For example, if the cooling set

point is 82 F (28 C) and the deadband is 2 degrees, the first

stage of cooling will not be energized until the temperature

reaches 84 F (30 C). The range of values is 1 to 6 degrees. The

default is 2 degrees.
SET POINT MINIMUM DIFFERENCE (Step 6) — The min-

imum difference between heating and cooling set points can be

user-configured. The range is from 0 to 6 degrees. The default

is 2 degrees. The minimum difference is enforced during

Autochangeover and Program On operation.
CYCLES PER HOUR LIMIT (Step 7) — The  number  of

times that heating or cooling can be energized per hour can be

configured. Set the variable to ‘‘d’’ for no limit. Set the variable

to ‘‘d1’’ to disable the 5-minute compressor lockout. The vari-

able can also be set from 2 to 6 cycles per hour. The default is

6 cycles per hour.

BACKLIGHT DISPLAY (Step 8) — The  display  backlight

can be set to ON (always on) or OFF (turn off 8 seconds after

usage). The default is ON.
FAHRENHEIT/CELSIUS OPERATION (Step 9)  —   The

thermostat can be set to operate in Fahrenheit or Celsius de-

grees. Set the variable to ‘‘F’’ for Fahrenheit operation. Set the

variable to ‘‘C’’ for Celsius operation. The default is ‘‘F.’’
SECURITY LEVEL (Steps 10 to 12) — The  Security  Level

limits the actions that the user can perform at the thermostat.

There are 4 security levels. When the security level is set to

‘‘0,’’ no security will be in effect. When the security level is set

to ‘‘1,’’ the set point range is limited by the settings of Steps 11

and 12. When the security level is set to ‘‘2,’’ the set point

range is limited by the settings of Steps 11 and 12 and the Pro-

gram On mode is always in effect. When the security level is

set to ‘‘3,’’ the set point range is limited by the settings of

Steps 11 and 12, the Program On mode is always in effect, and

set point changes are prohibited. The default is 0.
Security Maximum Heat Set Point (Step 11) — If the Securi-

ty Level is not set to 0, the maximum heating set point will be

in effect. The user will not be allowed to set the heating set

point over the specified value. The range of values is 35 to 99 F

(1 to 37 C). The default is 80 F (27 C).
Security Minimum Cool Set Point (Step 12) — If the Securi-

ty Level is not set to 0, the minimum cooling set point will be

in effect. The user will not be allowed to set the cooling set

point below the specified value. The range of values is 35 to

99 F (1 to 37 C). The default is 65 F (18 C).
HEAT PUMP CONFIGURATION (Step 13) — This is used

to set the reversing valve polarity for the heat pump. The vari-

able can be set to either ‘‘B’’ or ‘‘O.’’ Set the reversing valve

polarity to the correct value depending on the application. The

default is ‘‘O.’’

Program  Thermostat  Schedules  — 

 Before pro-

gramming the thermostat, plan the thermostat daily schedule.

The schedule is divided into 7 days (Monday through Sunday).

Each day has from 2 to 4 time periods (Occupied 1, Occupied

2, Occupied 3, Unoccupied) depending on the configuration of

the thermostat. Each occupied time period has a start time, stop

time, heating set point, and cooling set point. The unoccupied

time period has a heating set point and a cooling set point. The

unoccupied time period is active when ever an occupied time

period is not active. Fill in Table 3 as an aid to programming

the daily schedules.
PROGRAMMING MODE — To program the daily sched-

ules, perform the following procedure:

1. Enter Programming mode by pressing the Program but-

ton. The Occupied 1 annunciator will appear on the ther-

mostat display. Use the UP ARROW and DOWN AR-

ROW buttons to set the maximum number of Occupied

periods for each day. The thermostat can be set to 1, 2, or

3. After the number of Occupied periods has been select-

ed, press the Mode button. See Fig. 6.

2. The cooling set point for Occupied 1 will be displayed.

Use the UP ARROW and DOWN ARROW buttons to

raise or lower the cooling set point until the desired tem-

perature is shown. The range of acceptable values is 35 to

99 F (1 to 37 C). Press the Mode button to continue. See

Fig. 6.

3. The heating set point for Occupied 1 will be displayed.

Use the UP ARROW and DOWN ARROW buttons to

raise or lower the heating set point until the desired tem-

perature is shown. The range of acceptable values is 35 to

99 F (1 to 37 C). Press the Mode button to continue. See

Fig. 6.

4. The cooling set point for Unoccupied will be displayed.

Use the UP ARROW and DOWN ARROW buttons to

raise or lower the cooling set point until the desired tem-

perature is shown. The range of acceptable values is 35 to

99 F (1 to 37 C) or ‘‘OF’’ (no unoccupied cooling). Press

the Mode button to continue.

5. The heating set point for Unoccupied will be displayed.

Use the UP ARROW and DOWN ARROW buttons to

raise or lower the heating set point until the desired tem-

perature is shown. The range of acceptable values is 35 to

99 F (1 to 37 C) or ‘‘OF’’ (no unoccupied heating). Press

the Mode button to continue.

6. The day of the week will be shown. Use the UP ARROW

and DOWN ARROW buttons to change the day of the

week until the desired starting day is shown. Possible

choices are M (Monday) through S (Sunday). Press the

Mode button when the desired day is shown.

Damage to compressor could result if 5-minute compressor

lockout is disabled or compressor is allowed unlimited

cycles. Do not set thermostat Advanced Setup Step 7 to

‘‘d’’ or ‘‘dl’’ unless specifically recommended for the

application.

Fig. 6 — Setting Occupied 1 Set Points

Summary of Contents for AQUAZONE 50QE900

Page 1: ...r property damage GENERAL The 7 day commercial programmable thermostats is a wall mounted low voltage thermostat which maintains room temperature by controlling the operation of an HVAC heating cooling and ventilation system Separate heating and cooling set points and auto changeover capability allow occupied and unoccupied programming for energy savings This thermostat allows up to 4 time tempera...

Page 2: ...re length and routing to allow proper closure of the thermostat Strip each wire at the end no more than 1 4 in to prevent adjacent wires from shorting together Match and connect wires to terminals on the thermostat See Fig 2 5 and Table 1 9 Push excess wiring into wall Seal hole in wall to prevent drafts 10 Re attach thermostat cover to back plate by aligning the top two prongs of the back plate i...

Page 3: ...ser to reset the Service Filter counter to zero and remove the SERVICE FILTER icon if displayed on the thermostat screen Press the OVERRIDE button while in Setup Step 3 and the counter is reset to zero Press the arrow buttons to ad just the number of hours the blower will run before the SER VICE FILTER icon is displayed The range is 0 to 1950 hours Set the variable to 0 to disable this function Th...

Page 4: ...arity for the heat pump The vari able can be set to either B or O Set the reversing valve polarity to the correct value depending on the application The default is O Program Thermostat Schedules Before pro gramming the thermostat plan the thermostat daily schedule The schedule is divided into 7 days Monday through Sunday Each day has from 2 to 4 time periods Occupied 1 Occupied 2 Occupied 3 Unoccu...

Page 5: ... been entered press the Program button to exit Programming mode NOTE The thermostat will continue to follow the schedule until a new one is entered If only one occupied schedule is selected the Occupied 2 and 3 schedules are skipped If the start time is set later in the day than the stop time the program will run from midnight of that day to the stop time and then from the start time to mid night ...

Page 6: ...the deadband plus 2 degrees Clock Backup In the event of a power loss the ther mostat will keep time for a minimum of 48 hours without external power or batteries Fan Operation If Fan On is selected the fan will run continuously during occupied schedule except when Mode is switched to OFF The fan will be off during unoccupied schedule except during heating or cooling operation If Fan On is not sel...

Page 7: ...ower operation timer to 0 hours Cooling Will Not Energize Select COOL mode Decrease cooling set point to 10 degrees below room temperature Check for 24 vac at Y1 terminal If present ther mostat is operating correctly and problem is with wiring or equipment If 24 vac is not present replace the thermostat Check for Compres sor Cycle per Hour Limit Cooling may be locked out Heating Will Not Energize ...

Page 8: ...ntinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53500037 01 Printed in U S A Form 50QE 7SI Pg 8 7 07 Replaces 50QE 2SI Book 1 4 Tab 5a 5a Copyright 2007 Carrier Corporation ...

Reviews: