Table 1 — Thermostat Wiring Terminations

*Terminals W2 and Y2 may not be used in all applications.

Set Clock — 

The Set Clock button allows the user to

change the time and day displayed on the thermostat. Press the

Set Clock button. The current time will blink on and off. Press

the UP ARROW and DOWN ARROW buttons until the cor-

rect time is shown. Hold down the buttons to quickly move

through the time display. The AM and PM annunciators will

automatically change. Hold down the Fan button while press-

ing UP ARROW or DOWN ARROW to change the time by

hours instead of minutes. To ensure the schedules are properly

followed, make sure that AM or PM is correct for the time cho-

sen. When the correct time is shown, press the Mode button to

modify the day of the week. The current day will blink on and

off. Press the UP ARROW and DOWN ARROW buttons until

the correct day is shown. Press the Set Clock button again to

exit the Set Time mode.

Heat Pump Configuration — 

To configure the ther-

mostat for proper heat pump operation, Advanced Setup Step

13 (Reversing Valve Polarity) must be configured correctly.

See the Configure Advanced Setup section for information on

configuring these options.

Configure  Advanced  Setup  — 

 To enter the ad-

vanced setup screens of the thermostat, press the Mode and

Program buttons at the same time. The Advanced Setup Step

number is shown in the top right corner of the thermostat

screen. Use the Mode button to advance through the steps.

There are 13 Advanced Setup Steps. See Table 2. Press the Pro-

gram button at any time to exit the Advanced Setup mode.
NOTE: Advanced Setup Steps 1 and 2 are configured with the

Set Clock button, and are not accessed through the advanced

setup screens.
SERVICE FILTER (Steps 3 and 4) — Step 3 allows the user

to reset the Service Filter counter to zero and remove the

‘‘SERVICE FILTER’’ icon (if displayed on the thermostat

screen). Press the OVERRIDE button while in Setup Step 3

and the counter is reset to zero. Press the arrow buttons to ad-

just the number of hours the blower will run before the ‘‘SER-

VICE FILTER’’ icon is displayed. The range is 0 to 1950

hours. Set the variable to 0 to disable this function. The default

is 500 hours.

Table 2 — Advanced Setup Configuration

*Accessed and configured through the Set Clock button.

EXISTING

WIRE

DESIGNATION

FUNCTION

TERMINAL

CONNECTION

G or F

Fan

G

Y1, Y, or C

Cooling

Y1

W1, W, or H

Heating

W1/O/B

Rh, R, M, Vr, or A

Power (24 v)

R

C

Common

C

O/B

Reversing Valve

W1/O/B

Y2

Second Stage Cooling

Y2*

W2

Second Stage Heating

W2*

STEP

DESCRIPTION

RANGE

DEFAULT

1*

Time of Day

12:00 AM -

11:59 PM

12:00 AM

2*

Day of the Week

Sunday through

Saturday

Monday

3

Reset Service

Filter Icon

4

Service Filter

Run Time

0-1950 hrs

500 hrs

5

Deadband

1 - 6 degrees

2

6

Forced Minimum

Temperature Difference

0 - 6 degrees

2

7

Cycles per Hour

d, d1, 2 - 6

6

8

Thermoglow™ Backlight

Off/On

On

9

Temperature Units

F/C

F

10

Security Level

0 - 3

0

11

Maximum Allowable Heat 

Set Point

35-99

80

12

Minimum Allowable Cool 

Set Point

35-99

65

13

Reversing Valve Polarity

O/B

O

Thermostat

R

C

G

Y

W

O

R

C

G

Y1

Y2

W1

W2

O

24 vac common

24 vac return

Fan

Compressor

Cooling

COMPLETE C

B

Thermostat

R

R

C

C

G

G

Y

Y

W

W

O

O

R

C

G

Y1

Y2

W1

W2

O

24 vac common

24 vac return

Fan

Compressor

Compressor 2

Cooling

COMPLETE C1 COMPLETE C2

B

Thermostat

R

C

G

Y1

Y2

W1

O/W2

R

C

G

Y1

Y2

W1

W2

O

24 vac common

24 vac return

Fan

Compressor 1

Compressor 2

Cooling

DELUXE D

B

Fig. 3 — Water Source Heat Pumps Equipped

with One Complete C Control Board for

Single-Stage Operation

Fig. 4 — Water Source Heat Pumps Equipped

with Two Complete C Control Boards

for Two-Stage Operation

Fig. 5 — Water Source Heat Pumps Equipped

with Deluxe D Control Board(s)

for Single or Two-Stage Operation

Summary of Contents for AQUAZONE 50QE900

Page 1: ...r property damage GENERAL The 7 day commercial programmable thermostats is a wall mounted low voltage thermostat which maintains room temperature by controlling the operation of an HVAC heating cooling and ventilation system Separate heating and cooling set points and auto changeover capability allow occupied and unoccupied programming for energy savings This thermostat allows up to 4 time tempera...

Page 2: ...re length and routing to allow proper closure of the thermostat Strip each wire at the end no more than 1 4 in to prevent adjacent wires from shorting together Match and connect wires to terminals on the thermostat See Fig 2 5 and Table 1 9 Push excess wiring into wall Seal hole in wall to prevent drafts 10 Re attach thermostat cover to back plate by aligning the top two prongs of the back plate i...

Page 3: ...ser to reset the Service Filter counter to zero and remove the SERVICE FILTER icon if displayed on the thermostat screen Press the OVERRIDE button while in Setup Step 3 and the counter is reset to zero Press the arrow buttons to ad just the number of hours the blower will run before the SER VICE FILTER icon is displayed The range is 0 to 1950 hours Set the variable to 0 to disable this function Th...

Page 4: ...arity for the heat pump The vari able can be set to either B or O Set the reversing valve polarity to the correct value depending on the application The default is O Program Thermostat Schedules Before pro gramming the thermostat plan the thermostat daily schedule The schedule is divided into 7 days Monday through Sunday Each day has from 2 to 4 time periods Occupied 1 Occupied 2 Occupied 3 Unoccu...

Page 5: ... been entered press the Program button to exit Programming mode NOTE The thermostat will continue to follow the schedule until a new one is entered If only one occupied schedule is selected the Occupied 2 and 3 schedules are skipped If the start time is set later in the day than the stop time the program will run from midnight of that day to the stop time and then from the start time to mid night ...

Page 6: ...the deadband plus 2 degrees Clock Backup In the event of a power loss the ther mostat will keep time for a minimum of 48 hours without external power or batteries Fan Operation If Fan On is selected the fan will run continuously during occupied schedule except when Mode is switched to OFF The fan will be off during unoccupied schedule except during heating or cooling operation If Fan On is not sel...

Page 7: ...ower operation timer to 0 hours Cooling Will Not Energize Select COOL mode Decrease cooling set point to 10 degrees below room temperature Check for 24 vac at Y1 terminal If present ther mostat is operating correctly and problem is with wiring or equipment If 24 vac is not present replace the thermostat Check for Compres sor Cycle per Hour Limit Cooling may be locked out Heating Will Not Energize ...

Page 8: ...ntinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53500037 01 Printed in U S A Form 50QE 7SI Pg 8 7 07 Replaces 50QE 2SI Book 1 4 Tab 5a 5a Copyright 2007 Carrier Corporation ...

Reviews: