background image

36

Stage 2. When the call is satisfied at the thermostat the unit

will continue to run in Heating Stage 1 until the call is

removed or satisfied, shutting down the unit.
NOTE: Not all units have two-stage heating functionality.
REHEAT MODE — A call from the humidistat/dehumidis-

tat to the (H) terminal of the Deluxe D control board will

bring the unit on in Reheat mode if there is no call for cool-

ing at the thermostat. When the humidistat/dehumidistat call

is removed or satisfied the unit will shut down.
NOTE: Cooling always overrides Reheat mode. In the

Cooling mode, the unit cools and dehumidifies. If the cool-

ing thermostat is satisfied but there is still a call for dehu-

midification, the unit will continue to operate in Reheat

mode.

SYSTEM TEST

System testing provides the ability to check the control

operation. The control enters a 20-minute Test mode by mo-

mentarily shorting the test pins. All time delays are in-

creased 15 times.

Test Mode — 

To enter Test mode on Complete C or De-

luxe D controls, cycle the power 3 times within 60 seconds.

The LED (light-emitting diode) will flash a code representing

the last fault when entering the Test mode. The alarm relay will

also power on and off during Test mode. See Tables 24-26. To

exit Test mode, short the terminals for 3 seconds or cycle the

power 3 times within 60 seconds.
NOTE: The Deluxe D control has a flashing code and alarm

relay cycling code that will both have the same numerical

label. For example, flashing code 1 will have an alarm relay

cycling code 1. Code 1 indicates the control has not faulted

since the last power off to power on sequence.

Retry Mode — 

In Retry mode, the status LED will start to

flash slowly to signal that the control is trying to recover from

an input fault. The control will stage off the outputs and try to

again satisfy the thermostat used to terminal Y. Once the ther-

mostat input calls are satisfied, the control will continue normal

operation. 
NOTE: If 3 consecutive faults occur without satisfying the

thermostat input call to terminal Y, the control will go into

lockout mode. The last fault causing the lockout is stored in

memory and can be viewed by entering Test mode.

Aquazone™ Deluxe D Control LED Indica-
tors — 

There are 3 LED indicators on the Deluxe D control:

STATUS LED — Status LED indicates the current status or

mode of the Deluxe D control. The Status LED light is green.
TEST LED — Test LED will be activated any time the De-

luxe D control is in Test mode. The Test LED light is yellow.
FAULT LED — Fault LED light is red. The fault LED will

always flash a code representing the last fault in memory. If

there is no fault in memory, the fault LED will flash code 1 on

the and appear as 1 fast flash alternating with a 10-second

pause. See Table 26.

Table 24 — Complete C Control Current LED Status

and Alarm Relay Operations

LEGEND

NOTES:

1. Slow flash is 1 flash every 2 seconds.
2. Fast flash is 2 flashes every 1 second.
3. EXAMPLE: “Flashing Code 2

 is represented by 2 fast flashes

followed by a 10-second pause. This sequence will repeat con-
tinually until the fault is cleared.

LED STATUS

DESCRIPTION OF OPERATION

ALARM RELAY

On

Normal Mode

Open

Normal Mode with

PM Warning

Cycle

(closed 5 sec.,

Open 25 sec.)

Off

Complete C Control is 

non-functional

Open

Slow Flash

Fault Retry

Open

Over/Under Voltage Shutdown

Open

(Closed after

15 minutes)

Fast Flash

Lockout

Closed

Flashing Code 1

Test Mode — No fault in memory

Cycling Code 1

Flashing Code 2

Test Mode — HP Fault in memory

Cycling Code 2

Flashing Code 3

Test Mode — LP Fault in memory

Cycling Code 3

Flashing Code 4

Test Mode — FP1 Fault in memory

Cycling Code 4

Flashing Code 5

Test Mode — FP2 Fault in memory

Cycling Code 5

Flashing Code 6

Test Mode — CO Fault in memory

Cycling Code 6

Flashing Code 7

Test Mode — Over/Under

shutdown in memory

Cycling Code 7

Flashing Code 8

Test Mode — PM in memory

Cycling Code 8

Flashing Code 9

Test Mode — FP1/FP2

Swapped fault in memory

Cycling Code 9

CO

Condensate Overflow

FP

Freeze Protection

HP

High Pressure

LED —

Light-Emitting Diode

LP

Low Pressure

PM

Performance Monitor

Table 25 — Complete C Control LED Code and

Fault Descriptions

LEGEND

LED

CODE

FAULT

DESCRIPTION

1

No fault in memory

There has been no fault since 
the last power-down to power-up 
sequence

2

High-Pressure Switch

HP Open Instantly

3

Low-Pressure Switch

LP open for 30 continuous sec-
onds before or during a call 
(bypassed for first 60 seconds)

4

Freeze Protection Coax
— FP1

FP1 below Temp limit for 30 con-
tinuous seconds (bypassed for 
first 60 seconds of operation)

5

Freeze Protection Air Coil
— FP2

FP2 below Temp limit for 30 con-
tinuous seconds (bypassed for 
first 60 seconds of operation)

6

Condensate overflow

Sense overflow (grounded) for 
30 continuous seconds

(Autoreset)

Over/Under Voltage
Shutdown

"R" power supply is <19VAC or 
>30VAC

8

PM Warning

Performance Monitor Warning 
has occurred.

9

FP1 and FP2 Thermistors 
are swapped

FP1 temperature is higher than 
FP2 in heating/test mode, or FP2 
temperature is higher than FP1 
in cooling/test mode.

CO

Condensate Overflow

FP

Freeze Protection

HP

High Pressure

LED —

Light-Emitting Diode

PM

Performance Monitor

Summary of Contents for AQUAZONE 50HQL072-120

Page 1: ... and Plateframe Heat Exchanger Well Systems 34 OPERATION 35 36 Power Up Mode 35 Units with Aquazone Complete C Control 35 Units with Aquazone Deluxe D Control 35 Units with HWR Option 35 SYSTEM TEST 36 37 Test Mode 36 Retry Mode 36 Aquazone Deluxe D Control LED Indicators 36 SERVICE 37 38 Filters 37 Water Coil 37 Condensate Drain Pans 37 Refrigerant System 37 Condensate Drain Cleaning 37 Air Coil ...

Page 2: ...aser to file all necessary claims with the shipping company 1 Verify unit is correct model for entering water tempera ture of job 2 Be sure that the location chosen for unit installation pro vides ambient temperatures maintained above freezing Well water applications are especially susceptible to freezing 3 Be sure the installation location is isolated from sleeping areas private offices and other...

Page 3: ...20 x 20 2 20 x 25 and 1 20 x 18 FPI Fins per Inch TPI Threads per inch UNIT 50VQL 080 100 120 160 200 240 300 NOMINAL CAPACITY tons 61 2 81 2 10 13 17 20 25 COMPRESSOR S Qty Type 1 Scroll 1 Scroll 1 Scroll 2 Scroll 2 Scroll 2 Scroll 2 Scroll WEIGHTS lb Operating 600 685 735 1120 1265 1350 1465 Shipping 610 695 745 1145 1275 1375 1475 AIR COIL Aluminum Fins Copper Tubes Total Face Area sq ft 9 00 1...

Page 4: ... 2 S 34 1 74 1 PLAN VIEW TOP FRONT FRONT OF UNIT V U Left Return Left View Air Coil Opening 24 Service Access Filter Bracket Shown 24 Service Access 4 2 NOTES 1 All dimensions in inches 2 Flanged filter bracket shipped with unit Leave one end of duct collar open for filter removal 3 All side panels are removable 4 Available in left return straight discharge only 5 Condensate is 3 4 in FPT copper 6...

Page 5: ... should be removed for return duct connection CONNECTIONS Water Outlet 11 4 FPT Water Inlet 11 4 FPT Condensate Drain 3 4 FPT High Voltage Access 7 8 K O Low Voltage Access 7 8 DIA LEGEND BSP Blower Service Panel CAP Control Access Panel CSP Compressor Service Panel 1 2 3 4 5 UNIT 50HQL OVERALL CABINET in DISCHARGE CONNECTIONS in Duct Flange 0 10 in WATER CONNECTIONS in ELECTRICAL KNOCKOUTS in RET...

Page 6: ...l Valve Ball Valve with integral P T plug Stainless steel braid hose with integral J swivel Building Loop Fig 2 Typical Horizontal Installation 50HQL Units T Optional Discharge Supply Air Optional Discharge Access Panel Access Panel Access Panel Access Panel Vibration Pad Control Box Supply Air Supply Water Return Water Balancing Valve Valves Trap Condensate 24 V Remote Mtd Stat Power Supply Disco...

Page 7: ...ions UNIT 50VQL OVERALL CABINET DISCHARGE CONNECTIONS Duct Flange 0 10 in WATER CONNECTIONS ELECTRICAL KNOCKOUTS RETURN AIR CONNECTIONS Using Duct Flange A Width B Depth C Height D Supply Width E Supply Depth F K 1 Water Inlet L 2 Water Outlet M 3 Cond ensate N O P Q R S Return Depth T Return Height U V W 080 100 in 29 0 41 0 71 5 14 7 15 8 11 2 4 0 7 4 14 5 20 5 2 1 20 6 1 0 3 1 34 8 23 4 25 4 3 ...

Page 8: ...HWR Hot Water Reheat NRP Non Removable Panel UNIT 50VQL OVERALL CABINET DISCHARGE CONNECTIONS Duct Flange 0 10 in WATER CONNECTIONS ELECTRICAL KNOCKOUTS RETURN AIR CONNECTIONS Using Duct Flange A Width B Depth C Height D Supply Width E Supply Depth F G K 1 Water Inlet L 2 Water Outlet M 3 Cond ensate N O P Q R S Return Depth T Return Height U V W 160 in 29 0 82 0 71 5 14 7 15 8 19 4 13 8 4 0 7 4 1...

Page 9: ...r Reheat NRP Non Removable Panel Fig 4C 50VQL300 Unit Dimensions UNIT 50VQL OVERALL CABINET DISCHARGE CONNECTIONS Duct Flange 0 10 in WATER CONNECTIONS ELECTRICAL KNOCKOUTS RETURN AIR CONNECTIONS Using Duct Flange A Width B Depth C Height D Supply Width E Supply Depth F G K 1 Water Inlet L 2 Water Outlet M 3 Cond ensate N O P Q R S Return Depth T Return Height U V W 300 in 29 0 82 0 71 5 18 8 16 1...

Page 10: ...or safety See Fig 2 Rod attachments must be able to support the weight of the unit See Table 1 for unit operating weights VERTICAL UNITS 50VQL Vertical units are available in rear or front return air configurations Sound minimization is achieved by enclosing the unit with in a small mechanical room or a closet Additional measures for sound control include the following 1 Mount the unit so that the...

Page 11: ...n there are 3types of WSHP piping systems to choose from water loop ground water and ground loop Refer to the Carrier System Design Manual for additional information All WSHP units utilize low temperature soldered female pipe thread fittings for water connections to prevent annealing and out of round leak problems which are typically associated with high temperature brazed connections Refer to Tab...

Page 12: ...ectrical Data shown in Tables 4 and 5 Make all final electrical connections with a length of flexi ble conduit to minimize vibration and sound transmission to the building POWER CONNECTION Line voltage connection is made by connecting the incoming line voltage wires to the L side of the CC terminal See Tables 4 and 5 for correct wire and maximum overcurrent protection sizing SUPPLY VOLTAGE Operati...

Page 13: ... Saturation Index All N A 0 5 to 0 5 If 0 5 minimize steel pipe use Based upon 150 F HWG and direct well 85 F indirect well HX Iron Fouling Iron Fe2 Ferrous Bacterial Iron Potential All N A 0 2 ppm Ferrous If Fe2 ferrous 0 2 ppm with pH 6 8 O2 5 ppm check for iron bacteria Iron Fouling All N A 0 5 ppm of Oxygen Above this level deposition will occur Corrosion Prevention pH All 6 8 5 Monitor treat ...

Page 14: ...conditions need to be considered The valve takes approximately 60 sec onds to open very little water will flow before 45 seconds and it activates the compressor only after the valve is completely opened by closing its end switch When wired as shown the valve will have the following operating characteristics 1 Remain open during a lockout 2 Draw approximately 25 to 35 VA through the Y signal of the...

Page 15: ...ing shown Refer to thermostat installation instructions for wir ing to the unit Thermostat wiring must be Class 1 and voltage rating equal to or greater than unit supply voltage 6 24 v Alarm Signal shown For Dry Alarm Contact cut JW1 jumper and dry contact will be avail able between AL1 and AL2 7 Transformer secondary ground via board standoffs and screws to Control Box Ground avail able from top ...

Page 16: ...late open end of VIO lead 4 FP1 thermistor provides freeze protection for WATER When using ANTIFREEZE solution cut JW3 jumper 5 Typical heat pump thermostat wiring shown Refer to thermostat installation instructions for wir ing to the unit Thermostat wiring must be Class 1 and voltage rating equal to or greater than unit supply voltage 6 24 v Alarm Signal shown For Dry Alarm Contact cut AL2 DRY JW...

Page 17: ...ith insulating tape 4 FP1 jumper provides freeze protection for WATER When using ANTIFREEZE solutions cut FP1 jumper 5 Typical thermostat wiring shown Refer to thermostat installation instructions for wiring to the unit Thermostat wiring must be Class 1 and voltage rating equal to or greater than unit supply voltage 6 24 v Alarm Signal shown For Dry Alarm Contact cut JW1 jumper and Dry Contact wil...

Page 18: ... thermistor provides freeze protection for WATER When using ANTIFREEZE solutions cut JW3 jumper 5 Typical heat pump thermostat wiring shown Refer to thermostat installation instructions for wir ing to the unit Thermostat wiring must be Class 1 and voltage rating equal to or greater than unit supply voltage 6 24 v Alarm Signal shown For Dry Alarm Contact cut AL2 DRY JW4 jumper and dry contact will ...

Page 19: ...freeze protection for WATER When using ANTIFREEZE solution cut FP1 jumper 5 Typical thermostat wiring shown Refer to thermostat installation instructions for wiring to the unit Thermostat wiring must be Class 1 and voltage rating equal to or greater than unit supply voltage 6 24 v Alarm Signal shown For Dry Alarm Contact cut JW1 jumper and Dry Contact will be avail able between AL1 and AL2 7 Trans...

Page 20: ... When using ANTIFREEZE solutions cut JW3 jumper 5 Typical heat pump thermostat wiring shown Refer to thermostat installation instructions for wir ing to the unit Thermostat wiring must be Class 1 and voltage rating equal to or greater than unit supply voltage 6 24 v Alarm Signal shown For Dry Alarm Contact cut AL2 DRY JW4 Jumper and Dry Contact will be available between AL1 and AL2 7 Transformer s...

Page 21: ...lead 4 FP1 thermister provides freeze protection for water When using antifreeze solutions cut JW3 jumper 5 Typical thermostat wiring shown Refer to thermostat installation instructions for wiring to the unit Thermostat wiring must be Class 1 and voltage rating equal to or greater than unit supply voltage 6 Factory cut JW1 jumper Dry contact will be available between AL1 and AL2 7 Transformer seco...

Page 22: ...lead 4 FP1 thermister provides freeze protection for water When using antifreeze solutions cut JW3 jumper 5 Typical thermostat wiring shown Refer to thermostat installation instructions for wiring to the unit Thermostat wiring must be Class 1 and voltage rating equal to or greater than unit supply voltage 6 Factory cut JW4 jumper Dry contact will be available between AL1 and AL2 7 Transformer seco...

Page 23: ... 32 1 195 1 1 5 5 8 2 0 39 1 47 1 70 37 9 45 9 70 Large 1 32 1 195 1 2 0 6 2 2 0 40 3 48 3 80 38 3 46 3 70 460 414 506 Standard 1 16 4 95 1 1 5 2 4 1 0 19 8 23 9 40 18 8 22 9 35 Large 1 16 4 95 1 2 0 3 1 1 0 20 5 24 6 40 19 5 23 6 40 575 518 633 Standard 1 12 0 80 1 1 5 1 9 0 8 14 7 17 7 25 13 9 16 9 25 Large 1 12 0 80 1 2 0 2 3 0 8 15 1 18 1 30 14 3 17 3 25 120 208 230 197 253 Standard 1 33 6 225...

Page 24: ... capability higher rpm To adjust sheave position follow the procedure outlined below 1 Loosen belt tension and remove belt 2 Loosen set screw on fan motor 3 Open sheave to desired position 4 Retighten set screw and replace belt NOTE Set belt tension as outlined below BELT TENSION ADJUSTMENT An overly loose belt will upon starting motor produce a slippage squeal and cause premature belt failure and...

Page 25: ...4 1 30 1 37 1 44 1 51 1 57 RPM 667 705 742 779 814 849 884 917 950 983 1015 1046 1078 1108 1138 1168 Turns Open 1 5 1 0 4 5 4 0 3 0 2 5 2 0 1 0 0 5 0 0 3 5 3 0 2 5 2 5 2 0 1 5 2800 BHP 0 81 0 87 0 93 1 00 1 06 1 12 1 19 1 25 1 32 1 39 1 46 1 52 1 60 1 67 1 74 1 81 RPM 729 764 799 833 866 899 931 962 993 1024 1054 1084 1114 1143 1171 1199 Turns Open 5 0 4 0 3 5 3 0 2 0 1 5 1 0 0 5 0 0 3 5 3 0 2 5 2...

Page 26: ...5 3 0 2 5 2 0 1 5 1 0 0 5 0 0 0 0 3 5 3 0 3 0 2 5 4200 BHP 1 84 1 91 1 98 2 04 2 10 2 16 2 22 2 28 2 34 2 40 2 47 2 53 2 59 2 65 2 71 2 77 RPM 1164 1191 1217 1241 1266 1291 1314 1337 1360 1383 1406 1427 1449 1470 1492 1513 Turns Open 4 0 3 5 3 0 2 5 2 5 2 0 1 5 1 0 0 5 0 0 3 5 3 5 3 0 2 5 2 5 2 0 4400 BHP 2 07 2 13 2 20 2 27 2 33 2 40 2 46 2 53 2 60 2 66 2 73 2 79 2 86 2 93 2 99 RPM 1202 1227 1251...

Page 27: ...en 4 5 3 5 3 2 1 4 5 4 3 5 2 5 2 1 5 3 2 5 2 2 3700 BHP 0 78 0 85 0 92 0 99 1 07 1 15 1 23 1 31 1 40 1 48 1 55 1 63 1 70 1 78 RPM 566 600 633 665 696 726 755 783 811 838 864 889 914 939 Turns Open 4 3 5 2 5 1 5 1 4 3 5 3 2 5 4 3 5 3 2 5 2 3900 BHP 0 82 0 89 0 96 1 03 1 10 1 18 1 26 1 35 1 43 1 52 1 62 1 71 1 81 RPM 550 584 616 648 679 709 738 766 794 821 847 873 898 Turns Open 4 5 3 5 3 2 1 5 4 5 ...

Page 28: ...84 1 93 2 03 2 13 2 23 2 33 2 43 2 53 RPM 670 705 740 774 807 840 872 903 934 964 993 1022 1051 1079 1107 1134 Turns Open 1 5 1 4 5 4 3 5 2 5 2 1 5 1 0 5 3 2 5 2 2 1 5 1 5200 BHP 1 36 1 45 1 55 1 64 1 74 1 84 1 94 2 04 2 14 2 24 2 34 2 45 2 55 2 66 2 77 2 87 RPM 708 741 773 805 837 867 898 927 957 985 1013 1041 1069 1096 1122 1149 Turns Open 0 5 4 5 4 3 5 2 5 2 1 5 1 0 5 0 3 2 5 2 1 5 1 0 5 5600 B...

Page 29: ...4 1 53 1 63 1 69 1 74 1 80 RPM 557 592 625 658 689 720 750 778 806 833 860 886 911 935 959 Turns Open 4 5 3 5 2 5 2 1 4 5 4 3 2 5 2 1 5 1 0 5 0 2 7600 BHP 0 83 0 90 0 97 1 05 1 12 1 20 1 29 1 37 1 46 1 55 1 65 1 75 1 85 1 95 2 06 RPM 575 608 640 672 702 732 760 788 816 842 868 894 918 943 966 Turns Open 4 3 2 5 1 5 4 5 4 3 5 3 2 5 2 1 5 1 0 5 2 1 5 8000 BHP 0 87 0 94 1 01 1 09 1 16 1 24 1 33 1 41 ...

Page 30: ...elay terminal AL2 to 24 vac R or to remain as a dry contact no connection To connect AL2 to R do not clip the jumper To set as dry contact clip the jumper LOW PRESSURE SETTING The Deluxe D Control can be configured for Low Pressure Setting LP Select jumper 1 JW1 LP Norm Open for choosing between low pressure in put normally opened or closed To configure for normally closed operation do not clip th...

Page 31: ...IP Switch Block S2 Accessory 2 Relay Options LEGEND NOTE All other switch combinations are invalid Units with Modulating Hot Water Reheat HWR Option A heat pump equipped with Hot Water Reheat HWR can operate in three modes cooling cooling with reheat and heating The cooling heating modes are like any other Aquazone water source heat pump The reversing valve O signal is energized in cooling along w...

Page 32: ...this configura tion the relay will be ON if the NSB input is connected to ground C NOTE If there are no relays configured for digital NSB then the NSB and override OVR inputs are automatically config ured for mechanical operation MECHANICAL NIGHT SET BACK When NSB input is connected to ground C all thermostat inputs are ignored A thermostat set back heating call will then be connected to the OVR i...

Page 33: ...internal overload protection will open thus activating the unit lockout This requires a manual reset To reset turn the thermostat on and then off NOTE There is a 5 minute time delay before the compressor will start Unit Start Up Cooling Mode 1 Adjust the unit thermostat to the warmest position Slowly reduce the thermostat position until the compres sor activates 2 Check for cool air delivery at un...

Page 34: ...d to ensure the motor housing has been flood ed Be sure the loop flow center provides adequate flow through the unit by checking pressure drop across the heat exchanger Antifreeze In areas where entering loop temperatures drop below 40 F or where piping will be routed through ar eas subject to freezing antifreeze is needed Alcohols and glycols are commonly used as antifreeze agents Freeze protecti...

Page 35: ...g Heat Stage 3 demand EH2 will turn on after 10 minutes EH1 and EH2 are turned off immediately when the Heating Stage 3 demand is removed The control reverts to Heating Stage 2 mode Output EH2 will be off if FP1 is greater than 45 F AND FP2 when shorted is greater than 110 F during Heating Stage 3 mode This condition will have a 30 second recognition time Also during Heating Stage 3 mode EH1 EH2 F...

Page 36: ...t mode The Test LED light is yellow FAULT LED Fault LED light is red The fault LED will always flash a code representing the last fault in memory If there is no fault in memory the fault LED will flash code 1 on the and appear as 1 fast flash alternating with a 10 second pause See Table 26 Table 24 Complete C Control Current LED Status and Alarm Relay Operations LEGEND NOTES 1 Slow flash is 1 flas...

Page 37: ... from this unit must be recovered without exception Technicians must fol low industry accepted guidelines and all local state and fed eral statutes for the recovery and disposal of refrigerants IMPORTANT To avoid the release of refrigerant into the atmosphere the refrigerant circuit of this unit must only be serviced by technicians which meet local state and federal proficiency requirements IMPORT...

Page 38: ...pressure gage to discharge line near compressor 3 After unit conditions have stabilized read head pressure on discharge line gage NOTE Operate unit a minimum of 15 minutes before checking charge 4 From standard field supplied Pressure Temperature chart for R 22 find equivalent saturated condensing temperature 5 Read liquid line temperature on thermometer then subtract from saturated condensing tem...

Page 39: ... protection Be sure FP1 is located in the discharge fluid and FP2 is located in the air discharge See Fig 19 0 0 10 0 20 0 30 0 40 0 50 0 60 0 70 0 80 0 90 0 0 0 20 0 40 0 60 0 80 0 100 0 120 0 140 0 Temperature degF Resistance kOhm Fig 18 Thermistor Nominal Resistance a50 8163 SUCTION COMPRESSOR DISCHARGE COAX EXPANSION VALVE FP2 FP1 LIQUID LINE WATER IN WATER OUT CONDENSATE OVERFLOW CO AIR COIL ...

Page 40: ... high external static Check Tables 6 16 X Air temperature out of range Too much cold vent air Bring entering air temperature within design parameters X Improper freeze protect set ting 30 F vs 10 F Normal airside applications will require 30 F only X X Bad thermistor Check temperature and impedance correlation Condensate Fault Code 6 X X Blocked drain Check for blockage and clean drain X X Imprope...

Page 41: ...ump capacity X X Scaling in water heat exchanger Perform Scaling check and clean if necessary X X Inlet water too hot or cold Check load loop sizing loop backfill ground moisture High Head Pressure X Reduced or no airflow in heating Check for dirty air filter and clean or replace Check fan motor operation and airflow restrictions Too high external static Check blower Tables 6 16 X Reduced or no wa...

Page 42: ...inue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53500034 01 Printed in U S A Form 50H V 10SI Pg 42 7 07 Replaces 50H V 9SI Book 1 4 Tab 5a 5a Copyright 2007 Carrier Corporation ...

Page 43: ...NS BEEN MADE AND IS FLUID AVAILABLE AT HEAT EXCHANGER Y N HAS PUMP BEEN TURNED ON AND ARE ISOLATION VALVES OPEN Y N HAS CONDENSATE CONNECTION BEEN MADE AND IS A TRAP INSTALLED Y N IS AN AIR FILTER INSTALLED Y N II START UP IS FAN OPERATING WHEN COMPRESSOR OPERATES Y N IF 3 PHASE SCROLL COMPRESSOR IS PRESENT VERIFY PROPER ROTATION PER INSTRUCTIONS Y N UNIT VOLTAGE COOLING OPERATION PHASE AB VOLTS P...

Page 44: ...NALYSIS COOLING CYCLE ANALYSIS HEAT OF EXTRACTION ABSORPTION OR HEAT OF REJECTION FLOW RATE GPM x TEMP DIFF DEG F x FLUID FACTOR Btu hr SUPERHEAT SUCTION TEMPERATURE SUCTION SATURATION TEMPERATURE DEG F SUBCOOLING DISCHARGE SATURATION TEMPERATURE LIQUID LINE TEMPERATURE DEG F Use 500 for water 485 for antifreeze SUCTION COMPRESSOR DISCHARGE COAX EXPANSION VALVE F F AIR COIL F PSI WATER OUT WATER I...

Reviews: