![Carrier AQUAZONE 50HQL072-120 Installation, Start-Up And Service Instructions Manual Download Page 28](http://html.mh-extra.com/html/carrier/aquazone-50hql072-120/aquazone-50hql072-120_installation-start-up-and-service-instructions-manual_2563393028.webp)
28
Table 12 — 50VQL160 Blower Performance Data
LEGEND
NOTES:
1. Due to alternate sheaves, ‘Turns Open’ may vary within ±0.5 turn from
the position shown above.
2. Units factory shipped with standard static sheave and drive at 2.5
turns open (5200 cfm at 0.4 in. wg ESP Wet Coil). Other speeds
require field selection.
3. ISO/ARI rating point with standard static sheave and drive at 2 turns
open (5200 cfm at 0.48 in. wg ESP Wet Coil). Other speeds require
field selection.
4. For applications requiring higher static pressures, contact your local
representative.
5. Performance data does not include drive losses and is based on sea
level conditions.
6. Do not operate in gray region.
7. All airflow is rated at lowest voltage if unit is dual voltage rated, i.e.,
208 v for 208-230-v units.
8. For wet coil performance first calculate the face velocity of the air coil
(Face Velocity [fpm] = Airflow [cfm]/Face Area [sq ft]). Then for veloci-
ties of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by
0.08 in. wg, 400 fpm by 0.12 in. wg and 500 fpm by 0.16 in. wg.
Table 13 — 50VQL200 Blower Performance Data
LEGEND
NOTES:
1.
Bold
numbers require 2 horsepower motor.
2. Values are per blower and motor; 2 blowers and motors required.
3. Due to alternate sheaves, ‘Turns Open’ may vary within ±0.5 turn
from the position shown above.
4. Units factory shipped with standard static sheave and drive at 2.5
turns open (7000 cfm at 0.7 in. wg ESP Wet Coil). Other speeds
require field selection.
5. ISO/ARI rating point with standard static sheave and drive at 3.5
turns open (7000 cfm at 0.45 in. wg ESP Wet Coil). Other speeds
require field selection.
6. For applications requiring higher static pressures, contact your local
representative.
7. Performance data does not include drive losses and is based on
sea level conditions.
8. Do not operate in gray region.
9. All airflow is rated at lowest voltage if unit is dual voltage rated, i.e.,
208 v for 208-230-v units.
10. For wet coil performance first calculate the face velocity of the air
coil (Face Velocity [fpm] = Airflow [cfm]/Face Area [sq ft]). Then for
velocities of 200 fpm reduce the static capability by 0.03 in. wg,
300 fpm by 0.08 in. wg, 400 fpm by 0.12 in. wg and 500 fpm by
0.16 in. wg.
RATED
CFM
EXTERNAL STATIC PRESSURE (in. wg)
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
1.5
4000
BHP
0.71
0.79
0.86
0.94
1.02
1.10
1.18
1.26
1.34
1.43
1.51
1.60
1.69
1.78
1.87
1.96
RPM
600
641
681
720
757
794
829
864
898
931
964
996
1027
1058
1088
1117
Turns Open
3
2
1
0.5
4.5
3.5
3
2
1.5
1
0.5
3
2.5
2
1.5
1
4400
BHP
0.89
0.97
1.06
1.14
1.22
1.31
1.40
1.48
1.57
1.66
1.75
1.85
1.94
2.03
2.13
2.23
RPM
633
671
708
745
780
814
848
881
913
945
976
1006
1036
1066
1095
1123
Turns Open
2
1.5
0.5
4.5
4
3
2.5
2
1.5
0.5
0
3
2.5
2
1.5
1
4800
BHP
1.11
1.20
1.28
1.37
1.46
1.56
1.65
1.74
1.84
1.93
2.03
2.13
2.23
2.33
2.43
2.53
RPM
670
705
740
774
807
840
872
903
934
964
993
1022
1051
1079
1107
1134
Turns Open
1.5
1
4.5
4
3.5
2.5
2
1.5
1
0.5
3
2.5
2
2
1.5
1
5200
BHP
1.36
1.45
1.55
1.64
1.74
1.84
1.94
2.04
2.14
2.24
2.34
2.45
2.55
2.66
2.77
2.87
RPM
708
741
773
805
837
867
898
927
957
985
1013
1041
1069
1096
1122
1149
Turns Open
0.5
4.5
4
3.5
2.5
2
1.5
1
0.5
0
3
2.5
2
1.5
1
0.5
5600
BHP
1.64
1.74
1.84
1.94
2.05
2.15
2.26
2.36
2.47
2.58
2.69
2.80
RPM
744
775
806
836
866
895
924
952
980
1007
1034
1061
Turns Open
4.5
4
3.5
3
2
1.5
1
0.5
0
3
2.5
2
6000
BHP
1.95
2.05
2.16
2.27
2.38
2.49
2.60
2.71
RPM
777
807
836
865
893
921
948
975
Turns Open
4
3.5
3
2
1.5
1
0.5
0
6400
BHP
2.27
2.38
2.50
2.61
2.73
2.85
RPM
807
835
862
890
917
943
Turns Open
3.5
3
2.5
1.5
1
0.5
A
—
Standard Static Sheave/Standard Motor
B
—
Low-Static Sheave/Standard Motor
C
—
High-Static Sheave/Standard Motor
ARI
—
Air Conditioning and Refrigeration Institute
BHP —
Brake Horsepower
ESP —
External Static Pressure
ISO
—
International Organization for Standardization
RPM —
Revolutions Per Minute
RATED
CFM
EXTERNAL STATIC PRESSURE (in. wg)
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
1.5
5400
BHP
0.50
0.56
0.63
0.70
0.77
0.84
0.90
0.97
1.03
1.10
1.17
1.23
1.30
RPM
561
599
635
670
704
736
767
797
826
854
881
907
933
Turns Open
4.5
3.5
2.5
1.5
4.5
4
3.5
3
2
1.5
1
0.5
0
5800
BHP
0.57
0.63
0.70
0.78
0.86
0.92
0.99
1.06
1.13
1.20
1.26
1.33
1.40
RPM
576
613
648
682
714
746
776
805
833
861
887
913
938
Turns Open
4
3
2
1
4.5
4
3
2.5
2
1.5
1
0.5
0
6200
BHP
0.58
0.64
0.71
0.78
0.86
0.94
1.02
1.10
1.19
1.27
1.35
1.43
1.52
1.60
RPM
553
590
626
660
693
724
755
784
813
841
868
894
919
944
Turns Open
4.5
3.5
2.5
2
1
4.5
3.5
3
2.5
2
1.5
1
2.5
2
6600
BHP
0.66
0.73
0.80
0.87
0.94
1.02
1.11
1.19
1.28
1.36
1.45
1.53
1.62
1.70
RPM
569
604
638
671
703
734
764
793
821
848
874
900
925
950
Turns Open
4
3
2.5
1.5
4.5
4
3.5
3
2.5
2
3.5
3
2.5
2
7000
BHP
0.68
0.75
0.82
0.89
0.96
1.04
1.12
1.21
1.28
1.36
1.44
1.52
1.59
1.67
1.75
RPM
549
584
618
651
683
714
744
773
802
829
856
882
907
932
956
Turns Open
4.5
3.5
3
2
1
4.5
4
3.5
2.5
2
1.5
3 2.5
2
2
7400
BHP
0.78
0.85
0.92
0.99
1.07
1.15
1.23
1.31
1.40
1.48
1.55
1.63
1.70
1.78
RPM
566
600
633
665
696
726
755
783
811
838
864
889
914
939
Turns Open
4
3.5
2.5
1.5
1
4
3.5
3
2.5
4
3.5
3
2.5
2
7800
BHP
0.82
0.89
0.96
1.03
1.10
1.18
1.26
1.35
1.43
1.52
1.62
1.71
1.81
RPM
550
584
616
648
679
709
738
766
794
821
847
873
898
Turns Open
4.5
3.5
3
2
1.5
4.5
4
3.5
3
4
4
3.5
3
8200
BHP
0.93
1.00
1.08
1.15
1.23
1.31
1.39
1.48
1.56
1.66
1.75
1.85
RPM
570
602
633
664
693
722
751
778
805
832
857
883
Turns Open
4
3.5
2.5
1.5
1
4.5
3.5
5
4.5
4
3.5
3
A
—
Standard Static Sheave/Standard Motor
B
—
Low-Static Sheave/Standard Motor
E
—
High-Static Sheave/Large Motor
ARI
—
Air Conditioning and Refrigeration Institute
BHP —
Brake Horsepower
ESP —
External Static Pressure
ISO
—
International Organization for Standardization
RPM —
Revolutions Per Minute
B
A
C
B
A
E